Transformer Protection
Transformer Protection
Fault level
Extent of
damage Duration of
fault
Winding failures
Voltage
regulating load
changers
Transformer
Transformer
bushing failure
faults
Transformer core
problem
Miscellaneous
failures
Insulation
breakdown
Improve cooling
Time
system
Ageing of
insulation
Temperature
Condition Over heating
leading to faults due to excitation Reduced load
Oil
contamination %
& oil Leakage
Reduced cooling
FAULT OF TRANSFORMER
➢ Earth fault on H.V external connection
➢ Phases to phase fault on H.V external connection
➢ Internal earth fault on H.V windings
➢ Internal phase to phase fault on H.V windings.
➢ Short circuit between turns L.V windings.
➢ Earth fault on L.V external winding
➢ Phase to phase fault on L.V external connection.
➢ Internal earth fault on L.V windings
➢ Internal phase to phase fault on L.V winding
➢ Short circuit b/w turn L.V windings
➢ Earth fault on tertiary windings
➢ Short circuit b/W turns tertiary windings
➢ Sustained system phase to phase fault
➢ Sustained system earth fault
Differential relay
Overall percentage
biased differential
relay
L.H&H.V Connection
circulating protection
Overall percentage
biased differential relay
L.H&H.V Connection
circulating protection
Tap changer
buchhloz elay
MECHANICAL Winding
PROTECTION: Temperature
0IL
temperature
Pressure relieve
valve
• Factors:
• The shape, magnitude and duration of the inrush
current depend on the factors:
• Size of power transformer
• Source Impendence
• The magnetic properties of the core i.e.
saturation density
• The remanence of core
• Resistance in power system from source to
transformer.
• The moment when transformer is switch on.
Effect of magnetising current
➢ Appears on one side of transformer only
➢ Seen as fault by differential relay
➢ Normal steady state magnetising current is less than relay
setting
➢ Transient magnetising inrush could cause relay to operate
• The vector group shows the connection of
windings of transformer and numerical index
(hour numbers) for displacement of vector of
two star voltages.
• Capital Letter DY11 Small letter (
clock dial reference)
• The first capital letter donates the connection
of high voltage winding of transformer
• The small letter represent the connection of
low voltage secondary winding of transformer
• Yy0d5
• The first capital letter Y is referred to H.V or
primary winding, the second letter y is
referred as secondary winding and third letter
is referred as tertiary winding.
• Primary winding is taken as phase referred ‘O’
means that phase angle b/W H.V and M.V
winding is zero. Whereas ‘5’ denotesthat
phase angle b/W H.V and tertiary winding is
150 (5x30)
OVER CURRENT PROTECTION
HV1 HV2
Time
LV
Current
IF(LV) IF(HV)
1.2IF(LV)
Use of Instantaneous Overcurrent
Protection
Source LV
50
51
Differential Protection
• Overall differential protection may be justified for larger
transformers (generally > 5MVA).
• Provides fast operation on any winding
• Measuring principle :
• Based on the same circulating current principle as the
restricted earth fault protection
• However, it employs the biasing technique, to maintain stability
for heavy thro’ fault current
• Biasing allows mismatch between CT outputs.
• It is essential for transformers with tap changing facility.
• Another important requirement of transformer differential
protection is immunity to magnetising inrush current.
PROTECTED ZONE
HV LV
R
• Correct application of differential
protection requires CT ratio and winding
connections to match those of
transformer.
• CT secondary circuit should be a
“replica” of primary system.
• Consider :
• (1) Difference in current magnitude
• (2) Phase shift
• (3) Zero sequence currents
Biased Differential Scheme
Differentia
l
Current
I1 - I2 OPERATE
I1 BIAS BIAS I2
I1 - I2
OPERATE RESTRAIN
I1 + I2 Mean Thro
2 Current
LV restricted E/F
protection trips
both HV and LV breaker
Recommended setting : 10% rated
Restricted E/F Protection
Low Voltage Windings (2)
A B C N
Source
Protected zone
REF
n
`
Combined Differential and Restricted
Earthfault Protection
A2 A1 a1 a2 P1 P2
S1 S2
P1 S1 P2
REF
S2 P1
P2
S1
S2
To differential relay
Integral Vectorial and Ratio
Compensation
Power transformer
Ratio
correction
Vectorial
correction
Differential
Virtual interposing CT element Virtual interposing CT
In Zone Earthing Transformer
a1 a2
P1 P2
A1 A2 P2 P1
S2 S1
S2 S1 T2 T1 P1 P2
Three Winding Transformer
63MVA 25MVA
132KV 11KV
300/5 1600/5
50MVA
33KV
1000/5
Twice
Normal
Flux
Normal
Flux
Normal
No
Load No Load
Current Current at
Twice Normal
Flux
Parallel Transformers
T1 NAB C
T2
Inter-Turn Fault
CT
E
Load
Shorted
turn
Oil conservator
3 minimum
Transformer
Buchholz Relay
Petcock
Alarm bucket Counter balance
weight
Mercury switch
Oil level
To oil
conservator From transformer
Deflector plate
Drain plug
Overfluxing Basic Theory
2m
V = kf
Causes m
Low frequency
High voltage Ie
Geomagnetic disturbances
Effects
Tripping of differential element (Transient overfluxing)
Damage to transformers (Prolonged overfluxing)
EFFECTS OF OVER FLUXING:
V f K
Settings
Pick-up 1.5 to 3.0 i.e. 110V x 1.05 = 2.31
50Hz
Ex
G
VT
AVR RL
THERMAL OVERLOAD:
• EFFECT OF OVER LOAD ON TRANSFORMER
INSULATION LIFE:
Overheating Protection
Trip
Iload
Alarm
TD
setting
On
Top oil of Fan
Iload
power control
transformer Off
On
Pump
control
Off
Heater Temp. indication
Local
Thermal Temperature Remote
replica sensing resistor
Overload Protection
• Overcurrent protection designed for fault
condition
• Thermal replica provides better protection
for overload
Time
– Current based
– Flexible characteristics
– Single or dual time constant
– Reset facility
– Non-volatile Current
Thermal Overload Oil Filled Transformers
Dual characteristic
100
Single
10 characteristic:
1 2 3 4 5 6 = 5 mins
Current (multiple of thermal setting)
ZA
DIGITAL RELAYS FOR TRANSFORMER
THERMAL WINDING PROTECTION