Goulds/Vogel Hydrovar: What Is The Hydrovar?
Goulds/Vogel Hydrovar: What Is The Hydrovar?
FREQUENCY
CONVERTER
BLOCKPUMPS totally enclosed IP 54
2 PCS-1A
Motor Power:
from 1,1 kW up to 22,0 kW
Highlights
Fitting of oversized
motor allows
increased output in
overspeed range.
Shut down of
pump during zero
consumption.
Energy saving up to
70% at partial load.
34,748 kWh
PCS-1A 3
Highlights
SIMPLE INSTALLATION!
1) mechanical installation 2) electrical connection 3) setting of desired parameters
Rigid Aluminum
housing totally
enclosed IP 54
Sufficient cooling
of inverter by
motor fan
Simple design of multiple pump units (max. 4 pumps) by integral processor and
interface connection (RS 485) which allows automatic switch over in case of pumps
being out of sequence, cyclic change of lead and lag pumps, automatic start
and stop of lag pumps following the system demand, provision for connection
into central control system.
CCS
4 PCS-1A
Engineering
Control:
The built-in frequency inverter and microprocessor pro-
vides pump control based on pressure, differential pres-
sure, or low. The VOGEL pressure control version stops
the pump at zero consumption. The discharge of the
pump is being calculated via the speed indirectly and
may be programmed to compensate for varying friction
losses following a programmable system curve.
The Hydrovar variable speed pump may additionally be
controlled externally with the required speed fed in by an
external control system.
To prevent unauthorized personnel from changing
operating data, a password may be set up. The starting
and stopping of the pump as well as the setting of
control parameters is done at the keyboard and shown
at the LCD display at the drivehead (not in MINVEVAR).
The display is two lined and programmed for seven
languages. There are also three diodes to indicate pump
ready, pump running and fault.
An analogue signal to monitor speed or pressure is
provided. Communication with a central control system is
also possible via an RS 485 interface. Each HYDROVAR
drivehead contains an individual microprocessor which
controls the automatic operation of lead and lag pumps
according to demand. Cyclic change over of lead and lag
pumps, automatic start and start of the next pump to
come in case a pump gets out of order. No external
controls are necessary.
The voltage controlled frequency inverter supplies a
sinus variated pulse width modulated output voltage. It
works with controlled sinusoidal current synthesis and
dynamic overcurrent limitation. The high switching fre-
quency of 8 kHz prevents undesired noise from driving
motors. Reactions to the feeder are prevented by a filter
(according to EN 55011). Inverter cooling is enhanced by
the motor fan.
There is also a memory for inverter “fault” signals, oper-
ating hour counter and an automatic cyclic start up of the
pump as a test run.
.
PCS-1A 5
Primary Applications
Any process requiring various hydraulic data
Application for the HYDROVAR systems are similar to those for the pumps they are used on. The deciding factor is a
variable demand for either pressure, or flow, or both. These conditions are normally found in applications involving
water supply and circulation.
Market Applications
Municipal Pressure booster stations
Water works supply
Building Trades Pressure boosters for high rise
Irrigation systems
HVAC Boiler feed
Heat exchangers
Chillers
Induction heating
Air filtration
Water circulation
Fans (wall mounted version)
Water Purification Reverse Osmosis systems
Filter Feed
Production of deionised and ultra pure water
Agricultural/Recreational Irrigation systems
Water supply and transfer
OEM Variable flow and pressure wash systems
Fluid circulation with variable demand
Packaged booster systems
Fountains
Waste Water & Sewage Treatment - Sewage pumps & Mixers (wall mounted version)
- Cleaning systems
Industrial Applications Formulation Systems
Spray Wash Systems
Seal Barrier Fluid Systems
Cooling Tower Systems
Product Overview
differential transducer for constant flow settings. These
What is the typical HYDROVAR System? are mounted to eliminate the need for special piping.
No separate microprocessor systems:
With the HYDROVAR, one or more pumps are connected In a multi-pump system a microprocessor is used to
to common headers as in a standard system, but that is sequence the pumps or control the VFD on pump motors.
where the similarity ends. Since the HYDROVAR is a Microprocessor system, no
No special pumps or motors: other controllers are needed.
The HYDROVAR will mount directly onto standard No separate control panels and inverters:
240/415 volt, three phase TEFC motors with class F insu- A control panel has protections such as overload, temper-
lation up to 22kW. Preselected combinations are available ature, short circuit (and others) built in. It also acts as the
with the Lowara SSV, HTS and C series range of pumps interpreter between the pumps and the pressure sensor
and the Vogel PMV, LMR and LMRZ range of pumps. and may have an inverter to change motor speed. As a
No separate pressure sensors: system the HYDROVAR acts as the control panel on the
The HYDROVAR system comes with your choice of pump. An isolated fused main supply is the only external
pressure transducer for various maximum readings or a device required.
6 PCS-1A
Product Overview continued
No bypass lines and metering valves: need for large break tanks on the suction side. In addition,
Most standard control systems are designed to control the operation of the pump at the correct speed for the
motors and do not offer much in the way of hydraulic required duty leads to a significant reduction in energy
protection. Protection from dead heading and running off consumption.
the end of the curve must be provided in the piping. With Anti-condensation Heater
the HYDROVAR, the pump will shut down at zero All units are supplied with anti-condensation heaters to
demand or low suction, or maximum flow (one pump). switch on when the units are in standby mode.
No Large Pressure Accumulators:
Without a supply tank, a constant speed pump will be What are the various configurations?
constantly turning on and off and running up and down
the curve at maximum power to satisfy system demands. The HYDROVAR control is currently available with the
In the HYDROVAR system, each pump changes its LOWARA SSV, HTS, and C series pumps together with
operating speed from zero to 3600 rpm to constantly VOGEL PMV, LMR and LMRZ pumps up to 22 kW. Each
maintain constant pressure or flow and therefore elimi- of these configurations was specifically selected to
nates the need for a large pressure accumulator. A small provide optimum performance and energy savings on a
pressure tank is required to maintain system pressure at wide range of system needs 30, 37 and 45 kW only for
zero demand, however this is less than half that required wall mounting. Each system comes with a standard three
for a constant speed system. Where local regulations phase TEFC motor selection. Specifications for the
permit, HYDROVAR pump sets can be connected directly HYDROVAR controller portions of these systems are as
onto the water supply line therefore also eliminating the follows:
NOTE: A 3 phase TEFC motor must always be used with the HYDROVAR controller. The motor connects to the HYDROVAR and the
HYDROVAR connects to the power supply. For 2,2 kW and below, the HYDROVAR input requirement is single phase 230 volt.
For 2,2 kW and above the HYDROVAR input requirement is three phase 400 volt.
Att: Both options available for 2,2 kW.
The HYDROVAR controller comes with a pressure trans- the difference in pressure (up to 2 bar) on each side of
ducer, transducer connection cable and transducer the pump circulator system or orifice plate (constant flow
mounting hardware as standard. systems). This difference is converted to flow and used to
The standard pressure transducer is 316 L stainless steel adjust the pump running speed.
with a viton gasket and is designed for pressures up to 10 The HYDROVAR can work with any sensor (i.e. lever.
bar. For higher pressure applications a 25 bar transducer velocity, temperature, chem concentration, flow...) emitting
is supplied. If constant flow is selected a differential a 4-20 mA signal.
pressure transducer option is available. This measures
PCS-1A 7
Product Overview continued
Motor mounted HYDROVAR units
8 PCS-1A
Product Overview continued
HYDROVAR for mounting on the wall (Industrial HYDROVAR)
Hydrovar wall mounting version Hydrovar split size 18,5 and 22 kW
1,5 - 3,0 kW 4,0 - 11,0 kW 15 - 45 kW
Applications:
PCS-1A 9
Product Overview continued
2. Many pumps in process must have Explosion area Non-explosion area
Split version
30-45 kW
later 15-22 kW
Explosion-proofed
motor
10 PCS-1A
Product Overview continued
What does the HYDROVAR do?
The basic function of the HYDROVAR is to control the pump to meet your system demands in one of three ways.
It performs these functions by: • Shut off a single pump at maximum flow or
automatically turn on the next pump in a multiple
1. Measuring the system pressure or flow via a series.
transducer mounted on the pump discharge. • Protect the pump and motor from over voltage, under
2. Calculating the motor speed to maintain the correct voltage, overload, and earth fault.
flow or pressure. • Vary the time of pump speed acceleration and
3. Sending out a signal to the pump motor start, increase deceleration.
speed, decrease speed or stop. • Compensate for higher friction losses at high flow rates.
4. In the case of multiple pump installations the • Send out a signal for remote monitoring of pressure
HYDROVAR will vary the order of the lead pump and and frequency.
turn on the lag pumps automatically in the case of
• Conduct an automatic test run of the pump at set times.
duty/assist sets.
• Keep track of the amount of time the pump(s) has run.
In addition to the basic functions, the HYDROVAR can
do things only the most advanced computerized control • Display all functions in an LCD window in English and
systems can do, such as: choice of languages. (English, German, Spanish,
Portuguese, French, Italian, Dutch)
• Shut off the pump(s) at zero demand.
Or: communicate with another HYDROVAR,
• Shut off the pumps ar zero suction. computer, or other controller via an RS 485
interface.
PCS-1A 11
HYDROVAR Single Pump Operation and Control, con’d
2. Compensation for system losses (following sys-
tem curve).
The operator can increase the discharge pressure of
the pump as the flow increases to compensate for the
added friction losses in the system. This allows the
pump to “follow the system curve.” To do this, the
operator enters the percentage increase in discharge
pressure required at the maximum speed at which this
increased pressure will start.
The pump should be selected so that the maximum
flow is on or below the 2950 curve. An alternative
method is to use a differential pressure transducer on
a circulator suction and discharge. The HYDROVAR
will automatically compensate the friction losses
depending on the increasing flow and speed.
4. Actuator Mode.
In actuator mode the pump speed can be varied via an
external source using a 4-20 mA signal. In this case
the built in controller is taken out of circuit.
Actuator Mode
12 PCS-1A
HYDROVAR Single Pump Control
PCS-1A 13
HYDROVAR Multiple Pump Operation and Control
Up to four HYDROVAR controlled pumps can operate
together to form a system. No other control panels are
necessary.
In a multi-pump system, the RS-485 interface is used as
a controller. The microprocessors monitor the activity in
each HYDROVAR to adjust overall system performance.
HYDROVAR controllers must be of the same size
and type.
14 PCS-1A
HYDROVAR Regulation Mode “NORMAL”
PCS-1A 15
HYDROVAR Regulation Mode “INVERS”
This regulation mode will be used to control on: The environment should also be free of excess amounts
• Constant incoming pressure of dust, acids, corrosive gases, salts etc.
• Constant level on a tank which is mounted before the An interference filter is included in the HYDROVAR to
HYDROVAR pump prevent interference with other electronic devices.
An LCD display on the control panel supplies all
Environment information and programming help.
Pressure sensitive switches are included for on, off,
Ambient temperature requirements for the HYDROVAR increase, decrease and select. Display lights indicate
are 5°C - 40°C, the same range as most TEFC motors. power on to the HYDROVAR, pump running and fault.
Temperature limits may be extended to 52°C by using the Operating temperatures for the pressure transducer
next size of HYDROVAR controller upon request. are -25°C to 80°C. The upper limit may be extended to
Humidity requirements for the HYDROVAR cannot 120°C by using the extended mounting hardware on the
exceed more than 50% at 40°C and no more than 90% SSV station.
at 20°C. The unit should be protected from the weather
and condensation.
16 PCS-1A
External Control and Monitoring
RS-485 Interface
Constant Flow
In a constant flow application a single pump, which has the
flow range needed is typically selected as shown in the
opposite graphs.
Selection of flow controlled pump
PCS-1A 17
System Comparison
more expensive than a standard panel.
HYDROVAR System vs Fixed Speed Systems
With the HYDROVAR, no control panel is needed. The
Since a conventional pump can only operated along its HYDROVAR contains all the functions of the most sophis-
performance curve, a constant pressure system must ticated microprocessor based VDF panels. Sequencing
always involve other components in order to regulate the and start/stop controls are communicated directly by the
supply of liquid to the “user.” These other components HYDROVAR to each pump - extra controls are not need-
can add up to much more than the cost of the pump ed for multi-pump systems. The HYDROVAR requires
alone. only a circuit breaker panel.
With the HYDROVAR system, large pressure tanks are
not required. Each unit has a soft start and gradual ramp Automatic Valves
up to eliminate premature pump wear and water hammer
and also reduce energy costs at periods of low demand. Solenoid valves or modulating/metering valves are used
A typical two pump HYDROVAR system requires no to control flow and pressure as the pumps keep running.
more than a vessel volume of 10% of the lit/min continuous duty boilers use this method. Use of these
performance of one pump. valves can create problems of water hammer and dead
heading for the pump. Bypass lines and pressure tanks
The precharge pressure of the vessel must be set to
are used to handle these types of problems.
approximately 15% less than the system pressure
requirement. The HYDROVAR eliminates the need for automatic
valves to control the pressure, flow or shut off of liquid to
the system. All these features are contained within the
Pressure Switches microprocessor controlled variable speed pump. In
addition, since there is no danger of valve water hammer
Pressure switches are normally installed at the discharge
or dead heading, bypass lines and pressure accumulators
of each pump in the system and used to turn each one
are not required.
on and off as demand changes and are connected to a
control panel to sequence the pumps. The pressure
switch is an on/off device that does not provide informa- Jockey Pump
tion on the system demand below or above the set point -
a distinct disadvantage. The standard booster system is sized for peak capacity
and is very inefficient when demand is low. For this rea-
In the HYDROVAR system, each pump is equipped with
son, a high head low flow pump is added to the system to
its own pressure transducer to measure the required
handle occasional demand during off peak periods. This
system pressure. This allows the pump to react to very
pump will run with a much lower power requirement and
slight changes in demand with the correct amount of
reduces wear on the main pumps.
pressure and flow. A pressure switch or float control may
be used on the suction side of a HYDROVAR equipped The HYDROVAR can drive the pumps at very low speeds
pump as a cut off for low/no suction. and energy consumption, eliminating the need for a jock-
ey pump. Off peak demand can be handled efficiently and
easily with the same system used for peak periods.
Control Panels
However, if main pumps become bigger a smaller pump
A typical multi-pump booster package has a control panel also driven by a HYDROVAR can be incorporated into the
that provides electrical protection and sequencing of the system to cover low demand duties in a more efficient
pumps. More sophisticated units will have a microproces- way.
sor that controls pumps and valves and interprets input
from the switches and floats. Some panels also have a
variable frequency drive inverters. Panels with micro-
processor control and or VFD control are significantly
18 PCS-1A
Hydraulic Performances
PCS-1A 19
Features and Benefits
Feature Advantage Benefits
Variable Speed Match Pump Performance Maximizes system performance
to system demands
Reduces power consumption
One pump selection for full
performance range
Constant pressure Stepless transition for steady supply
Reduces intermittent operation
Eliminates large storage tank cost
and space
Lower mechanical load Energy savings
Higher reliability
Less system components Space savings
Single source supply
Simplified design
Microprocessor Control Pump protection No flow shutoff
Various fault protections
Eliminates bypass lines
Eliminates pressure modulation
and metering valves
System curve compensation Reduces power consumption
Meets changing demand
Multi-pump control Eliminates separate panel
Automatic sequencing
Automatic lead/lag
On-line-interface Remote monitoring and status display
Remote control
On-line transducer Pressure sensing Maintain constant pressure
Friction loss compensation
Maintain constant flow
Electronic Control Electrical protection Long service life
Soft start and stop Low starting current
Eliminates start stress No water hammer
20 PCS-1A
HYDROVAR
Multistage pumps SVH, PMVH Design VDAH (with HYDROVAR variable speed pumps)
PCS-1A 21
HYDROVAR
22 PCS-1A
PUMPSMART
TM
PROCESS SYSTEMS
Innovative
Pumping Solution:
- Significantly lowers life cycle cost
- Significantly increases MTBF
- Will not cavitate
- Will not run dry
- Will not run against
closed discharge valves
- Eliminates flow control valves
- Eliminates flowmeters
- Eliminates starters
- More effective process control
BECAUSE FAILURE IS NOT AN OPTION
24 PCS-1A
PUMPSMART
PumpSmart is a system that utilizes a standard process pump in conjunction with ITT Industries’
unique and patented PumpSmart Control System and Software.*
The software, which resides on the controller microprocessor chip, is the brains of the system,
allowing the pump to monitor and REACT to any system condition. The result is lower
lifecycle costs. Here’s How:
*Patent pending
Initial
Capital
1
Costs 2
3
$ 4
Flowmeters
1
2 are eliminated -
PumpSmart utilizes
patented internal flow 3 2
measurement.
Reduced
Operating
Costs
■ Pump operation matches system
$ ■ requirements without control valves.
Energy consuming control valves,
flowmeters and recirculation lines are
eliminated.
■ Savings are calculated and displayed at
the DCS or on the PumpSmart keypad.
26 PCS-1B
ITT Industries has developed proprietary LifeCycle CostwareTM that assists our
customers in quantifying life cycle cost savings...
LIFE CYCLE COST COMPARISON
Conventional System PUMPSMART
Rating, design 2700 GPM @ 120 TDH
Rating, actual 2700 GPM @ 51 TDH
Pump Model and Size 3196XLT, 8x10-13 3196XLT, 8x10-13
RPM 1,780 1,458
Yearly hours of Operation 8,760 8,760
Actual BHP 96 61
Maximum BHP 99 74
Installed Motor Size (HP) 100 75
Equipment Life (Years) 15 15
Estimated Cost/Repair $2,500 $2,500
Initial Cost
Total Life Cycle Initial Costs $20,600 1 $19,800 2
Installation Cost
Pump & Motor Assembly $41,000 $39,000
PumpSmart 0 $4,500
Control Valve $15,600 Not Required
Flowmeter $18,000 Not Required
Starter $3,600 Not Required
Total Life Cycle Installation Costs $78,200 $43,500
Operating Costs
Yearly Energy Use (kW-hr) 43,776 26,577
Years Operating 15 15
Total Energy Use (kW-hrs) 656,639 398,652
Electricity Cost ($/kW-hr) 0.45 0.45
Total Life Cycle Operating Cost $443,231 $269,090
Maintenance Costs
Average MTBF (months) 18 36
Total No. Repairs 10 5
Total Pump Maintenance Cost $25,000 $12,500
PumpSmart Maintenance 0 1,100
Control Valve Maintenance $3,200 Not Required
Flowmeter Maintenance 2,800 Not Required
Total Life Cycle Maintenance Costs $31,000 $13,600
Life Cycle Savings
Initial Purchase $800
Installation $34,700
Operating $174,141
Maintenance $17,400
Total Savings $227,041
Present Value of Savings $112,230
PumpSmart Payback 2.6 months
1
Includes pump and motor, flow control valve, flowmeter
and starter.
2
Includes pump and motor and PumpSmart Process
System. Flow control valve, flowmeter and starter are not
required.
$227,041
Total Life Cycle
Cost Savings Initial Capital Cost
Installation Cost
Maintenance Cost
Operating Cost
PCS-1B 27