APFC
APFC
net/publication/332757863
CITATIONS READS
4 3,872
2 authors, including:
Basil Hani
University of Basrah
42 PUBLICATIONS 52 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Basil Hani on 16 November 2020.
Abstract: In the current scenario, power factor has become an important concern in all industries. Poor power factor
gives rise to many problems which result in financial loss of industries and also for the commercial users. The main
concern of this work is to improve the usage of real power with respect to reactive power hence improving the power
factor. Here we have used the technique of relay switching method with a capacitor so that any drop in power factor
can be sensed by the controller and switch the capacitor as required. This will not only help to improve power factor
but also demand of electricity supply on utility side will be reduced. The Significance of this work is to build an
APFC (Automatic Power Factor Correction) Unit. The APFC appliance calculates the reactive power (KVAR)
expended by a system’s load and compensates the lagging PF (power factor) utilizing capacitances from capacitor
banks.
Keyword: Potential Transformer, Amplifier (Op-Amp), Current Transformer, Two Microcontroller, Capacitors,
Conductors, Relays, LCD 20x4 (Liquid Crystal Display).
the needed KVAR, however, practically,
I. INTRODUCTION correcting PF much nearer to unity.
Automatic power factor controller project is
The PF is the ratio between the actual load power
planned to improve power factor automatically,
(KW) and the apparent load power (KVA) drawn
whenever power factor falls below convinced
via an electrical load [1]. It can be also stated as
level [2]. As we know that the requirement of
usage of real power to total power provided. Poor
electrical energy is increasing day by day, more
power factor gives rise to many problems such as
and more inductive loads are increasing in
large kVA rating of the equipment, larger
industries as well as for household purpose [3].
conductor size, poor voltage regulation, increased
Inductive loads are the main reason for low
copper loss, reduced power handling capacitor
power factor in power system [4].
and much more. There are several methods for
This paper will describe how the power factor
improving the power factor of the system such as
will be improved by using reactive power
a synchronous condenser, static compensator,
technique.
static capacitor, etc. they are either highly priced
methods or inefficient methods. To overcome
these disadvantages, the new method depends on II. ADVANTAGES OF POWER FACTOR
reactive power and this method is very efficient IMPROVEMENT
and also less expensive compared to other The power factor derives the actual usage of real
methods. A necessary capacitance is connected so power by the equipment. The power triangle is
that PF is adjusted as close to unity as possible. shown in Fig.1. In this figure, real power is
Theoretically, capacitors could provide 100% of
30
Iraqi Journal of Electrical and Electronic Engineering اﻟﻣﺟﻠﺔ اﻟﻌراﻗﯾﺔ ﻟﻠﮭﻧدﺳﺔ اﻟﻛﮭرﺑﺎﺋﯾﺔ واﻻﻟﻛﺗروﻧﯾﺔ
Volume 14, No. 1- 2018 2018-1 اﻟﻌدد،14 اﻟﻣﺟﻠد
denoted by kW, reactive power denoted by will be large. To overcome this, conductor with a
KVAR and apparent power is denoted by kVA. larger diameter will be required. This will cause
The power factor from Fig.1 can be derived as an increase in the cost of the conductor.
cosine angle of apparent power and real power 3. Copper loss
which is denoted by CosØ. If the PF of the As referred from above if the current drawn by
system is “1‟, then it can be said that 100% the system is increased the copper loss of the
power has been used and no reactive power is system will also increase. This will cause an
present. Similarly, if power factor is “0.5‟, then it increase in total loss of system and hence the
can be stated that 50% real power is consumed efficiency of the system will be decreased.
and remaining 50% is reactive power. So power 4- Voltage regulation
factor is a very important concept which has to be Due to large currents, a high voltage drop occurs
studied to specify the system power usage and in the alternator which reduces the voltage at the
also losses [5], [6], [7], [8]. The power factor can terminal of the alternator. As no load gives
be denoted mathematically as shown in fig1 voltage regulation to full load voltage drop the
………(1) regulation will be poor.
Current
Transformer
220V
Potential Load
50HZ Transformer
Capacitor Bank
First Second
microcon microcon
Contactors
troller troller
Relay Shield
32
Iraqi Journal of Electrical and Electronic Engineering اﻟﻣﺟﻠﺔ اﻟﻌراﻗﯾﺔ ﻟﻠﮭﻧدﺳﺔ اﻟﻛﮭرﺑﺎﺋﯾﺔ واﻻﻟﻛﺗروﻧﯾﺔ
Volume 14, No. 1- 2018 2018-1 اﻟﻌدد،14 اﻟﻣﺟﻠد
V. DESIGN METHODOLOGY C. network of Inductive load
The inductive load is a mixture of loads
The whole Automated Power Factor Correction consuming huge electrical power and having
unit involves of several modules these modules inductive characteristics due to lagging power
are: Capacitor Banks, 4x20 LCD monitor, two factor.
microcontrollers, main supply, Current sensor,
Current sensor circuit, a Voltage sensor, Voltage D. Potential transformer
sensor circuit, conductors, Relay driver and The potential transformer in proposed system
Inductive load network. transfers 220V to 9V shown in Fig.4 .
A. AT328 Microcontroller
It is a low power CMOS 8-bit MCU based on
the AVR enhanced RISC architecture. The
powerful execution of instructions in a single
clock cycle leads to the achievement of 1
MIPS per MHz throughputs allowing the
designer to optimise power consumption
versus processing speed. The CPU is the brain
of the MCU which controls the execution of
the program. The microcontroller consists of
256/412/1K bytes EEPROM along with the
Fig.4 Potential Transformer
512/1K/2K bytes of SRAM, 4K/8K bytes of
in system programmable flash with reading
1. Voltage Measurement
while writing capabilities. The AT328-MCU
To read the main power supply voltage, first
has many advantages as 23 general purposes
the system voltage 9 V RMS must be stepped
I/O lines, three adjustable timer/counters with
down to the level that the microcontroller is
compare modes, 32 general purpose working
compatible. Microcontroller A/D converter deals
registers, a byte oriented 2-wire serial
with the signal in the range of 0 to 5 V, So the
interface, external, internal interrupts and a
next step should be taken is converting the
serial programmable USART, a 6-channel 10-
stepped down RMS voltage to signal voltage in
bit ADC, an SPI serial port [14]. The AT328
the range of (0-5V).
and pins configuration is shown in Fig.3.
Ti = t
Td=Tv-Ti
Fig.8 Sinusoidal, square wave converter of
voltage
Td<0? N
Y
Power factor is Lead Power factor is Lag
Start
Is PF> 0.9? Y
N N N
76 < Q<=152 152< Q<=228 228< Q<=304 304< Q<=380
Y N
Y Y Y
N N
Y Y
Y
C1& C2& C3: ON C2& C3: ON, C1& C3: ON
C1: OFF C2: OFF
37
Iraqi Journal of Electrical and Electronic Engineering اﻟﻣﺟﻠﺔ اﻟﻌراﻗﯾﺔ ﻟﻠﮭﻧدﺳﺔ اﻟﻛﮭرﺑﺎﺋﯾﺔ واﻻﻟﻛﺗروﻧﯾﺔ
Volume 14, No. 1- 2018 2018-1 اﻟﻌدد،14 اﻟﻣﺟﻠد
IX. EXPERIMENTAL SET UP OF
SYSTEM UNDER CONSIDERATION
38
Iraqi Journal of Electrical and Electronic Engineering اﻟﻣﺟﻠﺔ اﻟﻌراﻗﯾﺔ ﻟﻠﮭﻧدﺳﺔ اﻟﻛﮭرﺑﺎﺋﯾﺔ واﻻﻟﻛﺗروﻧﯾﺔ
Volume 14, No. 1- 2018 2018-1 اﻟﻌدد،14 اﻟﻣﺟﻠد
Table I
The experimental results of APFC on real home
Appliances P (W) S V I PF Q(VAR) CµF State
(VA) (V) (A)
2 FL +1fan 196 229.2 214 1.1 0.86 120 NO Before
Correction
196 202 215 0.9 0.97 40 5 After Correction
As shown in Table I, we note that the value of the power factor before the addition of the
capacitance was low, i.e. less than 0.9, while at the addition of the capacitance we note that
the power factor value is close to 1.
39
Iraqi Journal of Electrical and Electronic Engineering اﻟﻣﺟﻠﺔ اﻟﻌراﻗﯾﺔ ﻟﻠﮭﻧدﺳﺔ اﻟﻛﮭرﺑﺎﺋﯾﺔ واﻻﻟﻛﺗروﻧﯾﺔ
Volume 14, No. 1- 2018 2018-1 اﻟﻌدد،14 اﻟﻣﺟﻠد
Besides automatically correcting PF of an [2] J. G. Cho, J. W. Baek, D. W. Yoo, H. S. Lee, “Reduced
electrical load, the designed system also performs Conduction Loss Zero Voltage Transition Power
Factor Correction Converter With Low Cost ”, IEEE,
power observing. The 4x20 LCD shows the
Transactions on Consumer Electronics, Vol. 45, Issue
power consumption. It shows the user the 3, pp. 395- 400, Jun 1998.
immediate P (real power), S (apparent power),
[3] L. D. Jones, D. Blackwell, “Energy Saver Power Factor
voltage (Vrms), current flow (Irms), PF (power
Controller for Synchronous Motors”, IEEE,
factor) and Q (reactive power) consumption. Transactions on Power Apparatus and Systems, Vol.
102, Issue 5, pp. 1391 -1394, May1983.
XII. REFERENCES