ZETA Addressable Loop Powered Interface Units

The document discusses addressable loop powered interface units that connect ancillary devices to a fire alarm system. There are three versions available: input only, input with output, and sounder circuit controller (output only). The modules address is set via an internal 8 way dil switch and they communicate with the fire alarm panel via an internal LED. The unit fits a standard 2 gang back box for surface or flush mounting.

Uploaded by

Fahri Adrian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
127 views

ZETA Addressable Loop Powered Interface Units

The document discusses addressable loop powered interface units that connect ancillary devices to a fire alarm system. There are three versions available: input only, input with output, and sounder circuit controller (output only). The modules address is set via an internal 8 way dil switch and they communicate with the fire alarm panel via an internal LED. The unit fits a standard 2 gang back box for surface or flush mounting.

Uploaded by

Fahri Adrian
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Addressable Loop Powered Interface Units

The Zeta Addressable Interface Unit is used to connect ancillary


devices to a Zeta Addressable Fire Alarm System.

There are 3 versions available: Input only, Input with Output, and
Sounder Circuit Controller (output only)

As with all addressable modules, their outputs are controlled by the


fire alarm panel. Consequently the modules will behave differently
on different Fire alarm panels. See table below for more information.
The modules address is set via an internal 8 way dil switch.

These modules have the option of connecting the inputs (or output
of the ZSCC) as a loop (Class A). That is, the cable is fed to each
device, and then returned to the interface. The jumper link for input
(or output) must then be moved to position A.

These modules have an internal LED, which flashes as the device


communicates with the Fire Alarm Panel.

The unit fits a standard 2 gang back box, so can be surface or flush
mounted.

Input Unit

SPECIFICATIONS Not Used


Style B (Class B) Wiring
Model ZIU ZIOU ZSCC
Not Used
Part No 48-100 48-105 48-110
Supply Voltage 17-33V DC Not Used
Average quiescent current at 24V 2mA 2mA 2mA 47K EOL 0.5W

Alarm current at 24V 2mA 10mA 10mA Input


Relay Max Switching Power N/A 24W N/A -
Addressable Loop In
Loop +
- & Loop Out
Relay Max Switching Current N/A 1A N/A +
Relay Max Switching Voltage N/A 24V N/A
Relay Minimum Capability N/A 10uA,10mV N/A
Max Number of switches 20 (in parallel) N/A
Input Output Unit
End of line Resistor (Class B) 47k 47k 47k
Not Used Style B (Class B) Wiring
Maximum Sounder Load N/A N/A 400mA
Requires external 24v supply No No Yes Not Used
Maximum Quantity per Loop 126 20 20
NC SELV
Maximum Humidity 95% RH non condensing Relay O/P CM
NO Only 47K EOL 0.5W
Operating Temperature -20 to +90oC (non condensing or icing)
Max wind Speed Not affected Input
Connections See Diagrams Loop Addressable Loop In
& Loop Out
Size 150 x 85 x 45(inc b/box)
Weight 220g

Interface Module Outputs with different Fire Sounder Circuit


Alarm Panels Controller Style Y Wiring (Class B)
Part No ZIU ZIOU ZSCC See Note 1
External
Simplicity 64 & No outputs Common to Common to all alarms 24VSupply
126 all alarms
Premier AD No outputs Common to Common if in a zone with Ext supply 47K EOL 0.5W
all alarms outputs only, Zonal if in a
Output
zone with inputs & outputs
Premier AL No outputs Programmable Programmable
Not Used

N/A
-
Addressable Loop In
Loop +
- & Loop Out
+

13