Structural Analysis: Proposed Three (3) Storeys Residential

This document provides a structural analysis and design criteria for a proposed 3-storey residential building. It specifies materials and loads to be used, including dead loads from partitions, finishes, utilities, and more. It also outlines earthquake analysis criteria based on the National Structural Code of the Philippines, including seismic zone factors, coefficients, and load combinations. Structural system types of steel or reinforced concrete special moment frames are identified.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
532 views

Structural Analysis: Proposed Three (3) Storeys Residential

This document provides a structural analysis and design criteria for a proposed 3-storey residential building. It specifies materials and loads to be used, including dead loads from partitions, finishes, utilities, and more. It also outlines earthquake analysis criteria based on the National Structural Code of the Philippines, including seismic zone factors, coefficients, and load combinations. Structural system types of steel or reinforced concrete special moment frames are identified.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 4

STRUCTURAL ANALYSIS

PROPOSED THREE (3) STOREYS RESIDENTIAL


LOT 30-A, BLOCK 9, PHASE 3, EAGLE CREST SUBDIVISION, BAKAKENG, BAGUIO CITY
(VILOETA M. CORPUZ)

It is the full intention of the Engineer that these calculations conform to the National Structural Code of the Philippines 2015; 7 th
Edition. Volume 1; Buildings, Towers, and other Vertical Structures; C101-15, ISSN 2094-5477.
These calculations shall govern the structural portion of the working drawings. However, where any discrepancies occur between
these calculations and the working drawings, the Engineer shall be notified immediately so proper action may be taken. The
structural computations included here are for the analysis and design of the primary structural system.
The attachment of non-structural elements is the responsibility of the Architect or designer, unless specifically shown otherwise. The
Engineer assumes no responsibility for work not a part of these calculations. When structural observation or field investigation is
required, the Architect or contractor shall make separate special arrangements with the Engineer.

ENGR. MARK GREGORY ARO RIMANDO. PICE, ASEP


CIVIL ENGINEER – STRUCTURAL ENGINEER
PRC Reg.No. 0116018
Valid Until: April 17, 2024
PTR No. 6316482
Issued On: January 4, 2021
Issued at: La Trinidad, Benguet
BIR Reg. TIN No. 739-230-657-000
STRUCTURAL DESIGN CRITERIA

Applicable Design Standards and References:

 National Structural Code of the Philippines. (N.S.C.P.)


Buildings, Towers, and other Vertical Structures. 2015. 7TH Edition.

 National Structural Code of the Philippines. (N.S.C.P.)


Buildings, Towers, and other Vertical Structures. 2010. 6TH Edition.

 Association Of Structural Engineers of the Philippines (A.S.E.P.) Handbook

 Building Code Requirements for Structural Concrete (ACI 318-02) and Commentary
(ACI318R-02), American Concrete Institute

 Uniform Building Code (UBC) 1997 Edition.

Material Properties
 Concrete = 3,000 psi
o Specified Concrete Compressive Strength at 28-days, fc’ = 20.70mPa
o Concrete Weight per Unit Volume = 23.5631 kN/m 3
 Main Reinforcing Steel Bars = Deformed Steel Bars (A.S.T.M. A615 Grade 40)
o Minimum Yield Stress, fy = 275.80 mPa
o Weight per Unit Volume = 76.9729 kN/m3
 Shear Reinforcing Steel Bars = Deformed Steel Bars (Grade 33)
o Minimum Yield Stress, fy = 227.53 mPa
o Weight per Unit Volume = 76.9729 kN/m3
 Soil Bearing Capacity (as recommended in attached Geotechnical Investigation Report)

o 150.00kPa (3,140 psf) for foundation subjected to Dead Load or in combination with Live Load.
o 199.00 kPa (4,170psf) should the Foundation Design Load be under consideration with Seismic Loads.
o Footing Minimum Width = 1.60m
o Depth of Embedment of Foundations should not be less than 1.50m
SUPERIMPOSED DEAD LOADS
 Interior and Exterior Partitions
o 100mm thick Concrete Hollow Block, plastered both faces = 2.11 kPa
o Movable Partitions = 1.00 kPa
 Floor Tile Finish on 25mm mortar bed = 0.77 kPa
 Cement Plaster = 0.24 kPa
 Utilities
o HVAC, Electrical Lighting and Fixtures, Plumbing Fixtures = 0.24 kPa
 Ceiling System (Joists and Furring included) = 0.24 kPa
 Waterproofing Membrane with topping = 1.00 kPa
 Steel Truss = 0.15 kPa
 Steel Purlins = 0.09 kPa
 G.I. Roof Cover = 0.12 kPa

DESIGN LIVE LOADS


 All Floors = 2.00 kPa (Residential Occupancy)
 Roof Live Load = 1.00 kPa

EARTHQUAKE ANALYSIS AND DESIGN


N.S.C.P. 2010, 6th Edition Section 208 EARTHQUAKE LOADS

NSCP 103-1 (Occupancy Category)


 Standard Occupancy Structures

NSCP Table 208-1 (Seismic Importance Factor)


 I = 1.0

NSCP Figure 208-4 (Referenced Seismic Zone Map of the Philippines)


 Zone 4 (Baguio City, Benguet)

NSCP Table 208-3 (Seismic Zone Factor)


 Z = 0.40

NSCP Table 208-6 (Seismic Source Type)


 Type A

NSCP Table 208-4 (Near Source Factor)


 Na = 1.00 (distance to known seismic source ≤ 15 km)

NSCP Table 208-5 (Near Source Factor)


 Nv = 1.00
NSCP 208.4.3 (Site Geology and Soil Characteristics)
 Type SD
o When soil properties are not known in sufficient detail to determine the soil profile type,
Type SD shall be used.

NSCP Table 208-7 (Seismic Coefficient)


 Ca = 0.44Na

NSCP Table 208-8 (Seismic Coefficient)


 Cv = 0.64Nv

NSCP Table 208-11 (Structural System)


 R = 8.0 (Steel Special Moment Resisting Frames)
 R = 8.50 (Reinforced Concrete Special Moment Resisting Frames)

NSCP 208.5.2.2 (Structure Period)


 Method A
 T = Ct (hn)3/4
Ct = 0.085 (for steel moment resisting frames)
= 0.0731(for reinforced concrete moment resisting frames)
= 0.050 (for all other buildings)
hn = Height of structure

LOAD COMBINATIONS
N.S.C.P. 2010, 6th Edition Provision 203.5 (Special Seismic Load Combinations)
 U = 1.2D + f1L +1.0EM
 U = 0.9D ± 1.0EM
Where:
f1 = 1.00 for floors in public assembly, for live loads in excess of 4.8 kPa, and for garage live load
= 0.50 for other live loads
EM = estimated maximum earthquake force that can be developed in the structure.
D = dead load
L = live load