NORMAL CLAD
GENERAL DESCRIPTION
PAGE 3 // 24
MAIN COMPARTMENTS
PAGE 4 // 24
MAIN COMPARTMENTS
Isolation of the VT’s and relevant fuses is by an compartment. In specific plants, the exhaust gases
cannot normally be evacuated out of the room and
external operating handle.
therefore the gas duct must always be closed on both
When the primary VT’s are isolated the VT secondary the end-sides and equipped with top chimneys. If there
are cases when it is not possible to evacuate gases out
circuits are also isolated automatically.
of the room, the switchgear can be supplied with outlet
The truck movement is carried out through a control gas duct.
system managed by an operating handle.
PAGE 5 // 24
GENERAL FEATURES
The characteristics of the switchgear are guaranteed The normal operating altitude is up to 1.000 m above
under the following operating conditions: the sea level.
AMBIE NT H U M I D I T Y
PAGE 6 // 24
GENERAL FEATURES
The degree of protection of the Normal Clad switchgear C.R. Technology Systems counts on skilled personnel
is conform to the IEC 60529 standards and it is normally for preventive and predictive maintenance operations.
supplied with the following degree of protection: A proper maintenance limits product deterioration over
time, which can cause a loss in terms of quality and
IP4X for the enclosure (higher degree
improve the safety of the work environment and of the
on request).
people that operate it. Moreover, maintenance activity
IP2X for internal compartments. has a direct effect on the footprint impact, as the
It is possible to provide switchgear with higer degree product works longer, and energy losses are avoided.
of protection. 1. Create a checklist for routine maintenance.
The painting is realized with epoxy powders, suitable 3. Check the condition of the coating and the
for processes like washing, degreasing, phosphation, outer casing.
passivation and treatments with water without salts.
4. Replace the components before their
The standard colour for metallic structures and doors
obsolescence.
is RAL 7035– light grey (front doors and side sheets).
Other colours available on request. 5. Always follow the manufacturer’s instructions,
The minimal thickness of the internal painting is 80µm, concerning timing and manner.
while for the external part it is 120µm. 6. Pay attention to warning signs, even if they
don’t lead to immediate functional failures.
PAGE 7 // 24
TECHNICAL DATA
DATASHEET NORMAL CLAD
(1 min)
3.600 3.600
4.000 4.000
50 50 40 40 40
Rated frequency Hz 50 - 60 50 - 60 50 - 60 50 - 60 50 - 60
PAGE 8 // 24
TECHNICAL DATA
UNIFILARS
PAGE 9 // 24
SWITCHGEAR TYPES
PAGE 10 // 24
TECHNICAL DATA
SWITCHGEAR CLASS
busbars;
withdrawable components;
PAGE 11 // 24
MAIN EQUIPMENT
CIRCUIT BREAKER PROTECTION RELAYS & COMMUNICATION
PROTOCOLS
Normal Clad can host SF6 gas-insulated or vacuum-
insulated circuit breakers for short-circuit interruption The digital protection relay, or numeric relay, uses a
and for isolation of the systems connected to the panel. microprocessor to analyze power system voltages and
currents for the purpose of detecting faults in an electric
In accordance with the specific applications, circuit power system.
breakers have different voltage levels (up to 40.5kV),
rated current (up to 4000A) and breaking capacity (up Protection relays are used to protect the feeder,
to 50kA). Customized circuit breakers can be installed transformer, generator, and other equipment.
inside the switchgear. C.R. Technology Systems mostly uses protection relays
of the main brands like ABB, Schneider Electric, Alstom,
C.R. Technology Systems uses mostly circuit breakers Siemens.
of the main brands like ABB, Schneider Electric, Eaton,
Siemens. Digital protection relays have communication protocol
ports, allowing it to become an element in a SCADA
system. Communication protocol ports may include be
MEASUREMENT TRANSFORMERS AND SENSORS MODBUS TCP/IP, RS485, IEC 61850 type.
PAGE 12 // 24
MAIN EQUIPMENT
SURGE ARRESTERS
INTERNAL LIGHTING
Enclosure Heaters or Switchgear Space Heaters are The main busbar is formed of conductors of copper or
designed to maintain temperature and minimize aluminum, supported by insulators, that interconnects
moisture inside electrical and mechanical equipment the loads and the sources of electric power.
enclosure. On request it is possible to have the following versions
of main busbar:
Copper;
AUTOMATIC AND MANUAL TRANSFER SYSTEMS
Aluminum;
A transfer switch in an electrical switch that reconnects Bars with insulating material (resin or heat shrinkable
electric power source from its primary source to sheath);
a standby source. Switches may be manually or
Silvered copper;
automatically operated. An Automatic Transfer Switch
(ATS) is often installed where a backup generator is Tinned copper.
located, so that the generator may provide temporary
electrical power if the utility source fails. The main busbar system placed inside the busduct and
fixed by insulators can be either air or gas insulated,
or it can be insulated through heat shrinkable sheath.
PAGE 13 // 24
SMART EQUIPMENT
Thanks to its long experience and the research for the improvement of the product in order to satisfy the customer
requirements, C.R. Technology Systems has created two smart measurement systems for the prevention and mitigation
of phenomena linked to the overtemperature and the electrical arc.
TEMPARATURE DETECTION
Sensors used are the latest technological finding in These sensors provide internal switchgear
the field of temperature measurement inside medium- temperature and operate in presence of current.
voltage switchgears. They are wireless and batteryless These sensors have been designed specifically for
sensors. power asset monitoring, like air-insulated medium-
voltage switchgears, and feature high dielectric
Through SAW (Surface Acoustic Wave) technology it strength. By design, they do not impact the electric
is possible to monitor the temperature in all its critical performance of the equipment and preserve its
points inside the switchgear in order to record an dielectric properties. They are certified according to
efficient and effective measurement plan. In this way IEC 62271 for their dielectric strength and operation
it is possible to obtain a significant technical and free of partial discharge inside the cubicle.
economic improvement of the plant.
This antenna, centered at 434 MHz, can be used
as:
The main components are the following:
- emission antenna for SAW sensors (when
connected to the transceiver/platform);
- probe for partial discharge measurements (when
connected to the transceiver/platform, with partial
discharge detection feature);
- remote sensor antenna from the measurement point/
sensitive element of the sensor (when connected to
the sensor – custom sensor design – upon request).
PAGE 14 // 24
SMART EQUIPMENT
INSTALLATION ROOM
The installation room must be prepared according to the switchboard size and type. Compliance with the dimensions
guarantees correct operation of the apparatus. It must be possible to ventilate the installation room.
PAGE 15 // 24
TYPE TESTS
Type tests certifications are issued by a certifying authority and they are internationally recognized. They are carried
out in independent, duly accredited test laboratories. A certificate contains a record of a series of type tests carried out
strictly in accordance with a recognized standard. C.R. Technology Systems switchgears are tested in the prestigious
laboratory of CESI, SVEPPI and KEMA.
Short-circuit and peak withstand current test: Temperature rise test: provides verification of the
provides verification of the short-circuit ratings temperature-rise limits and measurement of the
assigned by the manufacturer, as design data resistance of the main circuits of a circuit-breaker
reviews, quality control checks and stage inspection in accordance with sub-clause 4 d) of IEC 62271–
of various power system equipment in accordance 100:2008. The certificate comprises those tests
with clause 4, items e) to p) inclusive and also s) of necessary to prove compliance with sub-clause 6.5
IEC 62271–100:2008. of IEC 62271-1:2017 and sub-clauses 6.4 and 6.5
of IEC 62271–100:2008.
Dielectric test: provides verification of the dielectric
performance of a circuit-breaker in accordance with Internal arc test: intended to verify the effectiveness
the requirements of clause 4, item b) of IEC 62271– of switchgear design in protecting personnel in case
100:2008. The certificate comprises those tests of an internal arc fault. The current valid international
necessary to prove compliance with the following standard for metal-enclosed switchgear from 1 kV
requirements: and up to and including 52 kV is written in the first
- industrial frequency voltage test; edition IEC 62271-200:2011. The test arrangement
- impulse voltage test; shall include fully equipped test objects. The test
- radio interference voltage tests. shall be performed in every compartment of the
switchgear and controlgear containing main circuits.
PAGE 16 // 24
TYPE TESTS
PAGE 17 // 24
PAGE 18 // 21
NORMAL CLAD
NORMAL CLAD
SPECIAL APPLICATIONS
PAGE 19 // 21
IP65 NORMAL CLAD FOR MINING APPLICATION (Up to 40.5kV)
The degree of protection of switchgear affects the Thanks to its design, Normal Clad supplied by C.R.
capacity of resisting to the heat: the higher the degree Technology Systems is able to work at over 5.000
of protection is, the less the switchgear manages meters above the sea level and in underground
to get rid of heat. For this reason, it is advisable to locations, with severe ambient conditions and dusty
use a degree of protection suitable for the installation environments.
environment.
PAGE 20 // 24
NORMAL CLAD - SPECIAL APPLICATIONS
PAGE 21 // 24
DUPLEX SWITCHGEAR
The Duplex switchgear is generally used for naval interface. The internal arc-proof switchgear is equipped
applications, since its configurations allow a drastic with a duct for the evacuation of gases produced by
reduction of the occupied space, with particular regard the electric arc. Each compartment of the unit on the
to the width of the switchgear. second floor is equipped with a deflector positioned
Each panel is composed of two overlapped units that on its top. The pressure generated by the fault causes
are completely independent and identical, therefore it to open, allowing the gases to pass through the duct.
each unit consists of three independent power The gases produced by faults generated in the power
compartments that are metallically segregated from compartments of the unit located on the first floor are
each other: appliances, bars and line. However, the evacuated to the main duct by means of a dedicated
important components are identical to those used for duct, positioned on the side of the switchboard. Thanks
the units of the classic panel, therefore the same service to this solution the units controlled in the second floor
and maintenance procedures are guaranteed. are not affected by the fault.
In the central part, the panel is equipped with a
compartment for the auxiliary instrumentation of both
units, whose height allows the operator to easily
PAGE 22 // 24
NORMAL CLAD - SPECIAL APPLICATIONS
The double busbar AIS switchgear can be supplied Free access to one busbar system during
up to 36kV. It is highly recommended where there is maintenance operation, while the other is working
the request to increase the service continuity, as in and the considered unit is out of operation
power utility companies, main substations and heavy
Circuit-breaker maintenance and testing without
industries.
feeder shutdown
Moreover, the double busbar switchgear is
recommended in the following situations: Fewer number of components and less switching
apparatus
Isolation of particular outgoing feeders from the
normal network
Each panel is made up of four independent power
Outgoing feeders balancing on two busbar systems compartments: apparatus, busbar 1, busbar 2 and
during normal operating condition cable. There is a metallic segregation between all the
compartments. On request, the double busbar system
Flexibility during inspection and maintenance
can be arc-proof version and supplied with a duct for
procedures without switchgear load interruption
the evacuation of the gases produced by an arc.
PAGE 23 // 24
C.R. TECHNOLOGY SYSTEMS S.P.A. For further information contact us
[email protected]
Via Rossaro, 9
24047 Treviglio (BG) – Italy www.crtsgroup.com
Ph. +39036334981
Fax +390295732316
VAT 01637141001
HEADQUART E RS
Via Crescenzio 82
00193 Roma
Italy
HEADQUART E RS
Ave 7ma 6203
Miramar, La Habana
Cuba
CONNECTING THE POWER
HEADQUART E RS
23 Avenue Hédi Nouira
Immeuble Mohamed Chérif
4éme etage bureau C4, Nabeul
8000
Tunisia
HEADQUART E RS
Angré 8° tranche
28 BP 65
Abidjan
Ivory Coast
HEADQUART E RS
Via della Pila 3A
01100 Viterbo
Italy