Ieee std43 2000 PDF
Ieee std43 2000 PDF
Rotor Testing
Izzy Kerszenbaum
www.izzytech.com
Phone: 949-230-5986 1
References
• IEEE 115 (Guide): Test Procedures for Synchronous Machines
• IEEE 112: Standard Test Procedures for Motors and Generators
• IEC 60034-3: Specific Requirements for Cylindrical Rotor Synchronous
Machines
• IEEE C50.10: General Requirements for Synchronous Generators
• IEEE C50.13: Standard for Cylindrical Rotor 50 Hz and 60 Hz Synchronous
Generators Rated 10 MVA and Above
• IEEE 67: Guide for the Operation and Maintenance of Turbine Generators
• IEEE 62.2: Guide for Diagnostic Field Testing of Electrical Power Apparatus
– Electrical Machinery
• EPRI TR-107137: Main Generator Monitoring and Diagnostics
• Handbook of Large Turbo-Generator Operation and Maintenance, by
Klempner and Kerszenbaum
2
Electric Power Engineering Consulting and Training
Definitions:
• TEST
– A critical evaluation, observation, or
evaluation.
– Taking measurements/measures to check the
quality, performance, or reliability of
(something), especially before putting it into
MONITORING
widespread use or practice.
• MONITORING TEST
3
Electric Power Engineering Consulting and Training
Keeping track of the health of the rotor
• Monitoring
– Online (real-time or not real-time) measurement of certain variables.
– Operator most basic approach
– Dynamic some level of computing algorithm
– Expert System complex algorithms
– Typically with alarm set-points
– Some level of prioritization (importance of monitored parameter)
• Testing
– Offline or Online
– Typically PASS or NO-PASS
• Protection
– Online and offline (e.g.: inadvertent energization)
– Too fast for operator reaction
4
Electric Power Engineering Consulting and Training
Whole Generator
MONITORING PROTECTION
Mostly with alarm Trip or
set-points Alarm & Trip
MW Differential
MVAR Field grounds Volts per Hertz
Voltages (AC & DC) Loss of field
Stator grounds
Currents (AC & DC) O/U frequency
Temperatures Vibrations Neg. Seq. currents
Vibrations Reverse power
etc.
EMI/RF etc.
VCM
etc.
STATOR ROTOR
CONTROLLED DC OVER-VOLTAGE X X
C-CORE (shorted-turns)
(requires rotor outside bore) X
7
Electric Power Engineering Consulting and Training
ENERGIZED
OPEN NOMINAL DE- TURNING
TEST ONLINE CIRCUIT ANY SPEED SPEED ENERGIZED GEAR IDLE
BEARING INSULATION RESISTANCE
(may require partial disassembly of the X X
unit)
OVER-SPEED X
ROTOR VIBRATIONS X X X X X
DYE PENETRANT X X
ULTRASONIC X X
EDDY CURRENT X X
SLIPRING RUNOUT X X X X X X X
BRUSH VIBRATION X X X
8
Electric Power Engineering Consulting and Training
Testing Rotor Parameters
Some Examples:
9
Electric Power Engineering Consulting and Training
1) WINDING SERIES RESISTANCE
• A generator can, in theory, run for years with a single ground fault in
the rotor. However…..
• Most stations monitor and alarm on rotor grounds. Some also trip.
12
Electric Power Engineering Consulting and Training
Ground-fault propensity in water-cooled rotors
13
Electric Power Engineering Consulting and Training
Searching for grounds
1. Estimate the electrical distance to the ground from the collector rings,
3. Knowing the electrical distance and axial location of the fault helps in
determining in which coil and slot the ground is most probably
located.
14
Electric Power Engineering Consulting and Training
3) POLARIZATION INDEX (PI)
• Insulation resistance is time dependent as well as being a function of dryness for rotor
insulation.
• The amount of change in the IR measured during the first few minutes depends on: the
insulation condition, amount of contamination and moisture present.
• When the insulation system is clean and dry, the IR value tends to increase as the
dielectric material in the insulation absorbs the charge.
• When the insulation is dirty, wet or a gross insulation problem is present, the charge does
not hold and the IR value will not increase, due to constant leakage current at the problem
area.
• Ratio between the resistance reading at 10 minutes and the reading at 1 minute produces
a number or “Polarization Index”; it is used to determine how clean and dry the winding is.
• The recommended minimum PI values are as follows:
Class B insulation: 2.0 Class F insulation: 2.0
• Same Megger used for the IR readings should be used to determine the PI.
• PI readings should be done at the same voltage as the IR test and can be used as a
go/no-go test before subjecting the rotor to subsequent high voltage tests, either AC or
DC.
IEEE Std. 43, Ch. 12 has a long paragraph on the significance (or lack thereof) of
Polarization Index measurements on rotors. 15
4) DC & AC HIGH POTENTIAL (HI-POT)
16
5) SHORTED-TURNS IN FIELD WINDINGS
• There are offline (unit not synchronized) techniques for testing for
the existence of shorted-turns
– With the rotor at speed (e.g.: Impedance vs. speed; RSO vs. speed)
– With the rotor standing-still (e.g.: RSO; pole-drop, “C”-core, etc.)
17
Electric Power Engineering Consulting and Training
Rotor Flux Monitor (RFM)
18
Electric Power Engineering Consulting and Training
If the RFM does not exist, or if the machine is standing-still,
a number of alternative methods exist:
19
Electric Power Engineering Consulting and Training
6) ROTOR SPEED - TESTING FOR SHAFT CRACKS
20
Electric Power Engineering Consulting and Training
7) BRUSHGEAR INFRARED PERIODIC MONITORING
21
8) HYDROGEN SEALS AND BEARING INSULATION
• Megger tests of bearing insulation should yield results > 100 k.
Preferable to be in the M region.
22
Electric Power Engineering Consulting and Training
Bearing Insulation
Visual (VI)
Radiographic (RT)
Magnetic Particle (MPI)
Liquid Penetrant (LPI)
Ultrasonic (UT)
Eddy Current (ECT)
• Dye Penetrant
• Eddy Current
• Ultrasonic
• Radiography
25
Electric Power Engineering Consulting and Training
10) BORE PRESSURE TESTS
• Hydrogen must be kept from leaking out thru the bore of the forging.
• Leak of hydrogen is not only an operational problem, but also a
safety hazard. Explosions have occurred from H2 leaks into the
brushgear housing.
• Some rotors have only one vertical connector sealed (outer). Most
rotor seal the outer and inner vertical stud.
• Older units have a borehole that extends the entire length of the
shaft, thus must seal at both ends. In modern units the borehole
does not go thru the entire length; thus only one side must be
sealed.
26
Electric Power Engineering Consulting and Training
11) THERMAL SENSITIVITY TEST
• The purpose of this test is to uncover the source of rotor (and stator)
vibrations, before they reach a level that requires removing the unit from
operation.
• Identifying the source of vibrations with the unit in operation is considerable
easier than with the unit standing still.
• Thermal Sensitivity Testing provides information that can help ascertain if
the vibrations are caused by the electrical loading of the rotor winding or are
strictly mechanical in origin.
• These types of tests are carried out by all OEMs for troubleshooting
purposes; they can also be done by Station personnel.
• This testing will also help to determine if the origin of the vibrations is in the
generator or the turbines.
• They can also provide information that allows further filtering of probable
causes, narrowing the search.
27
Electric Power Engineering Consulting and Training