01 - SVC PLUS - DECRETO422 - Class Room Training - Principle - of - Operation Rev0
01 - SVC PLUS - DECRETO422 - Class Room Training - Principle - of - Operation Rev0
Principle of Operation
© Siemens AG 2019
Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
What is FACTS?
FACTS
IEEE definition:
© Siemens AG 2019
Page 2 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Reactive Power Compensation and FACTS
© Siemens AG 2019
Page 4 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Voltages for different operating conditions
V1 V2 c Outage of 1 line
SVC (at full load)
d Load rejection
at bus 2
a b c d
1.2
0.8
© Siemens AG 2019
Page 5 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Reactive Power Compensation and FACTS
Series Compensation
Conventional SC (Fixed Series Compensation, FSC)
Thyristor Protected Series Compensation (TPSC)
Thyristor Controlled Series Compensation (TCSC)
© Siemens AG 2019
Page 7 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Reactive Power Compensation and FACTS
Series Compensation:
Conventional SC (Fixed Series Compensation, FSC)
© Siemens AG 2019
Page 8 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Classic Static VAr Compensator
© Siemens AG 2019
Page 9 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Classic Static VAr Compensator
© Siemens AG 2019
Page 10 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
STATCOM Static VAr Compensator (VSC)
© Siemens AG 2019
Page 11 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Advanced Static VAr Compensator (VSC)
© Siemens AG 2019
Page 12 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Advanced Static VAr Compensator (VSC)
The SVC Plus contains two stations which respectively contains one transformer, one SVC
PLUS converter, and two MSR’s, which together provides reactive power in the range of 100 Mvar
capacitive to 400 Mvar inductive on the 500 kV bus.
The STATCOM in the substation Nueva Pan de Azúcar will support reactive power for the 500kV
power system.
Due to the 4 FSCs near the substation Pan de Azúcar overvoltage conditions can be generated in
the 500kV interconnection between Los Changos and Polpaico under several daily power transfers
from SING to SIC or otherwise, especially before power zero crossing.
The main goal of the two STATCOMs is to provide dynamic reactive power and automatically
regulate and support the voltage of the 500 kV bus at Nueva Pan de Azúcar Substation.
© Siemens AG 2019
Page 13 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Single Line Diagram
© Siemens AG 2019
Page 14 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Single Line Diagram
© Siemens AG 2019
Page 15 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Single Line Diagram
© Siemens AG 2019
Page 16 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Main components
Transformer
CTs and VTs
Reactors / Capacitors / Resistors
Power modules
Arrestors / Surge Capacitors
Control / Protection / HMI
Cooling
Air conditioning
© Siemens AG 2019
Page 17 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Switchyard components
Function HV
• Connection to busbars
• Protection of components
Elements
MV
• Circuit breakers
• Insulators & disconnectors
• Voltage transformers
• Current transformers
• Surge arresters
• Surge capacitors
Design criteria
• Max. operating voltages
• Max. operating current
R
• Short-time overload
• Short circuit power
© Siemens AG 2019
Page 18 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Power Transformer
Function HV
© Siemens AG 2019
Page 19 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Reactors
Function HV
• Coupling of converter to power system
• Smoothing effect on current
• Limitation of possible fault currents
MV
Reactor details
• Single phase air core reactors in different
3-phase arrangements
• Outdoor installation
Design criteria
• Continuous operating range
• Short-time overload
• Harmonic stresses
• Transportation limits
• Environmental conditions R
© Siemens AG 2019
Page 20 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
SVC PLUS Container
Length: 12.5 m
Width: 3.4 m
Height: 3.6 m
Weight: 27000 kg
© Siemens AG 2019
Page 21 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
SVC Container - Main Systems
© Siemens AG 2019
Page 22 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Current transformer for AC/DC currents
Function HV
© Siemens AG 2019
Page 23 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Sub-modules
Function HV
• Modularity 4/6-packs
• DC voltage 1.7 kV DC
• Fiber optic communication
Design criteria
• Current 1200 amps
• Isolation at DC side
• Compact
• Allow cooling of IGBTs
© Siemens AG 2019
Page 24 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Sub-modules
HV
MV
© Siemens AG 2019
Page 25 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Resistor and bypass switch
Function HV
Design details MV
• DC motor controlled
by sequence
• Feedback contacts
Design criteria
• Converter current
© Siemens AG 2019
Page 26 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Resistor and bypass switch
Function HV
Design details MV
• DC motor controlled
by sequence
• Feedback contacts
Design criteria
• Converter current
© Siemens AG 2019
Page 27 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Protection Current Transformers
Function HV
© Siemens AG 2019
Page 28 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Cooling System
Function
• Provide reliable and efficient cooling
to IGBTs
Design details
• Single- or dual-circuits
• Closed / open cooling system
• Non conducting
Design criteria
• Temperature rise
• Ambient temperature
• Redundancy of components
• Noise level
• Environmental protection conditions
© Siemens AG 2019
Page 29 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Cooling System
© Siemens AG 2019
Page 30 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Subsystems
• Air Conditioning
• Fire detection
• Auxiliary Supply
• Batteries
© Siemens AG 2019
Page 31 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Components and Subsystems
Subsystems
IR SENSOR
© Siemens AG 2019
Page 32 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
SVC PLUS based on STATCOM technology
STATCOM
Function
► Active voltage generation with controllable magnitude and phase angle similar
to synchronous condenser (synchronous machine)
► VSC with much faster step response time in comparison to synchronous
condenser
► No rotating components or mechanical inertia
► Capacitive or inductive reactive power supplied by one unit only, no need of
separate TCR, filter(s) and/or TSC components like in classic (thyristor) SVC
► Definition of VSC level: 2N + 1 (N = no. of IGBT full bridges with own floating
DC capacitor)
► Multilevel converter with approximated sinus and low harmonics generation
© Siemens AG 2019
Page 33 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
SVC PLUS based on STATCOM technology
© Siemens AG 2019
Page 34 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
SVC Control Systems
© Siemens AG 2019
Page 35 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
SVC PLUS Multilevel Converter
© Siemens AG 2019
Page 36 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
SVC PLUS configuration
SVC
Modules
PLUS
1...22
© Siemens AG 2019
Page 37 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Methods of voltage generation using VSC
3-level
converter
PWM
Advantages of multi-level converter in
comparison to 2-/3-level converter:
multi-level
converter
© Siemens AG 2019
Page 38 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Modular multilevel converter – voltage generation
N1
UC=0
N2
UC
N3
UC
N4
UC=0 Ud
N5...8
N9
UC
I I
IN IE Simplified V dV
Simplified SVC PLUS reactor converter as
grid source
X I ideal source
E
Capacitive power!
V dV E
Synchronisation
voltage
V
E dV
I I
Inductive power!
VTr V Re
I
VCon I {Re}
VN VTr
© Siemens AG 2019
Page 41 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Inductive Operation
Currents Voltages
Voltage in kV
Current in kA
Time in sec
© Siemens AG 2019
Page 42 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Capacitive Operation
V Re
VTr
I I
{ Re}
VN VCon
VTr
© Siemens AG 2019
Page 43 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Capacitive Operation
Current Voltages
Voltage in kV
Current in kA
Time in sec
© Siemens AG 2019
Page 44 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
SVC PLUS NUEVA PAN DE AZÚCAR
Simplification of VSC to a voltage source
© Siemens AG 2019
Page 45 October 2019 Siemens AG Restricted Gas and Power / Transmission Solutions
Thank you for your attention!