100% found this document useful (3 votes)
556 views

Generator Calcu

This document provides generator protection relay settings for a 25MW multi-fuel power plant in the Philippines, including: 1) Differential, loss of excitation, under/over voltage, under/over frequency, negative phase sequence, and backup protection settings. 2) Reverse/low forward power, overfluxing, overcurrent, earth fault, and dead machine protection settings. 3) Neutral voltage displacement protection settings to trip the turbine relays. The settings reference the generator data and CT/PT ratios to configure 16 protection functions in the generator relay.

Uploaded by

Aditya Pandey
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (3 votes)
556 views

Generator Calcu

This document provides generator protection relay settings for a 25MW multi-fuel power plant in the Philippines, including: 1) Differential, loss of excitation, under/over voltage, under/over frequency, negative phase sequence, and backup protection settings. 2) Reverse/low forward power, overfluxing, overcurrent, earth fault, and dead machine protection settings. 3) Neutral voltage displacement protection settings to trip the turbine relays. The settings reference the generator data and CT/PT ratios to configure 16 protection functions in the generator relay.

Uploaded by

Aditya Pandey
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

SHIN THERMO DYNAMIC ENGINEERING PVT.

LTD
Raheja Towers, Sigma Wing Ground Floor,
No.177, Anna Salai, Chennai – 600 002. India.
Phone: +91 - 44-2860 6261 / 62 Fax: +91 - 44 - 2860 6259
Email: [email protected]
web site: www.shinthermo.co.in

Project : 25MW MULTI FUEL FIRED CO .GEN POWER PLANT SAMAL,BATAAN, PHILLIPINES.
Doc. No: 8084 – 001 – 60, Rev-02
Date : 13-07-2018
Document: Generator Protection Relay Settings.

GENERATOR PROTECTION RELAY SETTINGS


GENERATOR DATA:
Rating = 31.25 MVA
Terminal Voltage = 13.8 kV
Synchronous reactance (Xd) = 1.539 Pu
= 1.539 x 13.8 x 13.8/31.25
= 9.378 Ohm
Transient reactance Xd’ = 0.258 Pu
= 0.258 x 13.8 x 13.8/31.25
= 1.572 Ohm

Sub Transient reactance Xd” = 0.205 Pu


= 0.205 x 13.8 x 13.8/31.25
= 1.249 Ohm
CT/PT Details:
Generator Phase/Neutral CT Primary = 1600 A
Generator Phase/Neutral Secondary = 1A
Generator PT ratio = 13.8 kV/1.732/110 V/1.732
= 125.4545.
CT/PT Ratio = 1600/125.4545 = 12.7536.
Generator rated Current = 1307 Amps.
Referred to Secondary = 1307/1600/1
= 0.816 A

Page 1 of 13
All Setting values are i n secondary values in MICOM P343 relay.
Active Settings Group 1

1) Generator Differential (87G)

Operating to 86TA, 86TB & 86GA, 86GB Master trip relays


Gen Diff function: Percent age bias.
Gen Diff Is1: 50.0 mA
Gen Diff k1: 0%
Gen Diff Is2: 1A Gen
Diff k2: 150%

2) Loss of Excitation (40)


Operating to 86GA and 86GB Master trip relays

Transformation ratio = CT ratio/PT ratio


= 12.75
Diameter of Circle (Xb1) = Xd x 12.75
= 9.378 x 12.75
= 119.5695 Ohm
Offset (Xa1) = 0.5 x Xd ’x (CT Ratio/PT Ratio)
= 0.5 x 1.572 x 12.75
= 1 0 . 0 2 1 5 Ohm
Field Fail status: Enabled
FFail Alm Angle : 30.0 Deg
FFail Alm Delay : 5.0 Sec
FFail 1 status : Enabled
FFail 1 X a 1 : 10.0215 Ohm
FFail 1 Xb1 : 119.5695 Ohm
FFail 1 Time Delay : 10.0 Sec FFail
FFail 1 DO Timer : 2 Sec
FFail 2 status: Enabled
FFail2 Xa2 = - 0.5 x Xd’
= - 0.5 x 1.572 x 16
= -12.576 Ohm

Page 2 of 13
FFail2 xb2 = KV2 / MVA x 16 = 97.505 Ohm
FFail2 time Delay: 4 Sec
FFail2 DO timer: 2 Sec
FFail Dim Line: Disabled

3) Under Voltage (27)

Under Voltage Element 1 to 86GRA & 86GRB (Trip to Grid Master Trip Relay)
Operate V< Measur’t mode : Phase to Phase
V< Operate mode : Any Phase
V<1 Function : DT
V<1 Voltage set : 1 01 V
V<1 time delay : 1.0 Sec
V<1 Pole Dead Inh : Enabled

Under Voltage Element 2 to 86GA & 86GB (Trip to Generator Master Trip Relay)
V<2 status : Enabled
V<2 Voltage set : 99 V
V<2 time delay : 3 .0 Sec
V<2 Pole Dead Inh: Enabled

4) Over Voltage (59)

Over Voltage Element 1 to 86GRA & 86GRB (Trip to Grid Master Trip
Relays)
V>1 Measurement Mode: Phase to Phase
V> Operate Mode : Any Phase
V>1 Function : DT
V>1 Voltage set : 119.0 V
V>1 time delay : 1.0 Sec

Over Voltage Element 2 to 86GA & 86GB (Trip to Generator Master Trip
Relays)
V>2 status Enabled
V>2 Voltage set : 121.0V

Page 3 of 13
V>2 time delay : 2.0 Sec
NPS over Voltage:
V2>1 Status: Disabled.

5) Under Frequency (81U)

Under Frequency Element 1 to 86 GRA & 86 GRB (Trip to Grid Master Trip
Relays)
F<1 status Enabled
F<1 setting : 57.6 Hz
F<1 time delay : 1.0 Sec
Under Frequency Element 2 to 86 GA & 86GB (Trip to Generator Master
Trip Relays)
F<2 status Enabled
F<2 setting : 57 Hz
F<2 time delay : 3.0 Sec
F<3 status Disabled
F<4 status Disabled
F<Function Link: 0000

6) Over Frequency (81O)

Over Frequency Element 1 to 86 GRA and 86 GRB (Trip to Grid Master Trip
Relays)
F>1 status Enabled
F>1 setting : 62.4 Hz
F>1 time delay : 1.0 Sec
Over Frequency Element 2 to 86 GA and 86 GB (Trip to Generator Master Trip Relays)
F>2 status Enabled
F>2 setting : 63 Hz
F>2 time delay : 8.0 Sec
Turbine F Protection:
Page 4 of 13
Turbine F Status: Disabled.

7) DF/DT (81R)

Group1 DF/DT to Grid master trip relays 86 GRA & 86 GRB.


Operating Mode : Rolling window
df/dt Avg cycles : 6
df/dt Interations : 2
df/dt >1 status : Enabled
df/dt >1 setting : 2.0 Hz/sec
df/dt>1 Dir’n : Both
df/dt>1 Time : 500 ms
df/dt >1 f L/H : Enabled
df/dt >1 f low : 57.6 Hz
df/dt>1 f High : 63 Hz
df/dt >2 status : Disabled
df/dt >3 status : Disabled
df/dt >4 status : Disabled

8) Negative phase sequence thermal protection (46)

NPS Alarm stage 1 trip to 8 6 G RA & 86 GRB (Grid Master Trip Relays)
I2therm>1 Alarm Enabled
I2therm>1 Current set: 70.0 mA
I2therm>1 time delay: 4.0 Sec
NPS Trip stage 2 to 86GA & 86 GB (Trip to Generator Master Trip Relays)
I2therm>2 Trip :Enabled
I2therm>2 Current set : 80.0 mA
I2therm>2 K setting : 6 Sec
I2therm>2 K reset : 2.0 Sec
I2therm>2 t max : 1.000 K Sec
l2therm>2 t min : 60.0 Sec

9) System Backup Protection (51V)

Backup Function: Voltage Controled o v e r c u r r e n t (51V) to operate 86GA & 86GB (Trip
to Generator Master Trip Relays)
Page 5 of 13
Vector rotation: None
V dep OC Char: IEC S Inverse
V dep OC I> set : 900 mA
V dep OC TM : 0.3
V dep OC t reset : 0.000 Sec
V dep OC V<1 set : 99.0 V
Vdep OC V<2 set : 33.0V
V dep OC K set : 0.250

Z<Function: Enabled
Vector rotation: None
Z<1 status: 2 Sec
Z<1 setting: 6.159 Ohm
Z<1 time delay: 2 Sec
Z<1 Reset: 0 Sec
Z<2 status: Disabled

The first impedance setting should 70 % of impedance.


Z<1 = Root 3 x 0.7 x (( VPh-n) / IFLC x 1.2)
Z<1 = 1.732 x 0.7 (7967.66 / 1307 x1.2) = 6.159 Ohm

10) Reverse Power Protection (32R)

Reverse power setting is recommended to be set based on the mechanical loss of turbine
and generator + No load electrical losses of generator,
This is approximately 1 %.
Generator capacity in 0.8 PF in MW: 25 MW
At 1% Power level at Primary in MW: 25 x 0.01 = 0.25 MW
At 1% Power level at Sec. in Watts: 0.25x 106 / (CT Ratio x PT Ratio) = 1.245 Watts

Power 2 function : Over


Power 2 direction : Reverse
Power 2 mode : Active
Power 2 3Phase watts : 1 watts
P o w e r 2 t i me d el a y : 2 s ec
P2 Pole dead inh : Enabled.

Page 6 of 13
11) Low Forward Power (32L)
Comp Angle : 0 Deg
Power 1 function : Under power
Power 1 direction : Forward
Power 1 mode : Active
Power 1 3 Phase watts : 1 watts
P o w e r 1 t i me d el a y : 1 s ec
P1 Pole dead inh : Enabled.

12) Over Fluxing Protection VOLTS/Hz (24)


Alm status : Enabled.
V/Hz Alarm Set: 1.95 V/Hz
V/Hz Alarm Delay: 2.0 S.
V/Hz >1 Status: Enabled.
Operate to 86 GA & 86GB (Trip to Generator
Master Trip Relays)
V/Hz >1Trip function: IDMT
V/Hz>1 Trip set : 2.0 V/Hz
V/Hz>1 Trip TMS : 500 mS.
V/Hz>2 Status: Disabled.
V/Hz>3 Status: Disabled.
V/Hz>4 Status: Disabled.

13) Over Current


Operate to 86 GA & 86 GB (Trip to Generator Master Trip Relays)
Phase O/C:
I>1 function : IEC S Inverse
I>1 Direction : Non Directional
I>1 Current set : 820 mA
I>1 TMS : 0.125
I>1 t reset : 0.000 Sec
I>2 function : DT
I>2 Direction : Non directional
I>2 Current set : 2 A
Page 7 of 13
I>2time delay : 7 50 mSec.
I>3 Status : Disabled.
I>4 Status: Disabled.
I> Char Angle: 30.0 Deg
I> Function link: 1111
NPS Over current:
I2>1 Status: Disabled
I2>2 Status: Disabled
I2>3 Status: Disabled
I2>4 Status: Disabled.
I2> VTS Blocking: 1111
I2> V2 pole set: 5.0 V
I2> Char Angle: - 60.0 Deg.

14) Earth Fault Protection (51N)

Operate to 86TA & 86 TB (Turbine Master Trip Relays) & 86 GA & 86GB (Generator Master Trip
Relays)
IN> Input: Measured
IN>1 function : IEC S Inverse
IN>1 Current set : 100.0 mA
IN>1 TMS : 0.15
IN>1 t reset : 0.000 Sec
IN>2 Function : DT
IN>2 Current : 100 mA.
IN>2 Time Delay : 750 mSec.

15) Dead Machine (50/27)


Operate to 86 GA & 86 GB (Trip to Generator Master Trip Relays)
Dead Machine status Enabled
Dead Machine I> : 100.0 mA
Dead Machine V< : 80.0V
Dead Machine tpu : 1.000 Sec
Dead Machine t DO : 500.0 m Sec

Page 8 of 13
16) Neutral Voltage Displacement protection (59N)
Operate to 86TA & 86 TB (Trip to Turbine Master Trip Relays) & 86GA & 86 GB (Trip to Generator
Master Trip Relays)
VN >3 Status : Enabled.
VN> 3 Input : VN1
VN >3 Function :IDMT
VN>3 Voltage set : 4 volts
VN>3 TMS : 0.5
VN>3 tReset : 0 Secs
VN>4 status : Enabled
VN>4 Input : VN1
VN>4 Function : IDMT
VN>4 Voltage set : 5 Volts
VN>4 TMS : 0.5
VN>4 treset : 0 Secs
17) 100% Stator EF (27TN)

Operate to 86 TA & 86 TB (Trip to Turbine Master Trip Relays) & 86 GA & 86GB (Trip to Generator
Master Trip Relays)
100% St EF status: VN3H > Enabled
100% St EF VN3H > 7 Volts (Note : setting to be assigned after seeing this third harmonic voltage
at full load).
VN3H > Delay: 2.00 S

18) Pole slipping (78)

Operate to 86 GA & 86 GB (Trip to Generator Master Trip Relays)


Impedance of Power Transformer = 12.5%
% Fault level at 13.8 KV side = 18.3 KA
Power transformer rating = 32 MVA
Xd' = 1.572 Ohm
Transformer Impedance (ZT) = (KV^2/MVA) X Percentage Impedance
= (13.8 x 13.8/32) x .125
= 0.7439
Fault MVA at 13.8 KV level (18.3 KA fault contribution from grid for a fault i n 69 KV
bus) = 1.732 x 69 x 1000 x 18300
Page 9 of 13
= 2186.99 MVA.
System Impedance seen from 13.8 KV level (Z 1 in ohms) = 13.8 x 13.8/2186.99 x 10^6
=0.00000008707
Transformation Ratio (CTR/PTR) = (1600/1)/(13800/110) = 12.75
Za ( In secondary) in ohms = (ZT + Z1) x (CTR/PTR)
= (0.7439 + 0.00000008707) x (12.75)
= 9.4847
Zb ( In Secondary) in ohms = 2 x Xd' x (CTR/PTR)
= 2 x 1.572x 12.75
= 40.086
Zc (in ohms) = 90% of transformer impedance
= 0.9 x 0.7439
= 0.66951

Zc (In Secondary) = Zc x (CTR/PTR) =0.66951 x 12.75 = 8.5362


P Slip Function - Enabled
Z based Pole Slip
Pole Slip Mode = Generating.
Pslip Za Forward in ohms = 9.4847
Pslip Zb reverse in ohms = 40.086
Lens Angle = 90 deg
Pslip Timer T1 = 15 msec
Pslip Timer T2 = 15 msec
Blinder Angle = 80 deg Pslip
Zc in ohms = 8.5362
Zone 1 Slip count = 1
Zone 2 Slip count = 2
PSlip reset time = 30 sec

19) Circuit Breaker failure protection ( 5 0 B F ) : -


Operate to 86 GRA & 86 GRB (Trip to Grid Master Trip
Relays):
Breaker Fail:
CB Fail 1 status: Enabled CB
Fail 1 timer: 200 ms
Page 10 of 13
CB Fail 2 status: Disabled
CBF Non I Reset: I < only
CBF Ext Reset: I< only
Under current:
I < current set: 200 mA
IN < current set: 100 mA
I SEF < current: 20.000 mA
I < CT source: IA-1 IB-1 IC-1

20) Reverse Reactive Power Protection (32Q)

Reactive power setting Q = VN2 / Xd


VN – System voltage.
Q = 13.8 x 13.8 / 9.378 = 20.30 MVr
Revers Power level at Sec. in VAr = 20.30 x 106 / (CT Ratio x PT Ratio) = 101.13 VAr.
Power 3 direction : Reverse
Power 3 Mode : Reactive
Power 3 3 Ph VArs : 101.13
Power 3 time delay : 2 seconds.
Power 3 DO timer : 0 Sec
P3 Poledead Inh : Enabled.

21) Current operated Backup earth fault relay (CDG11, Alstom Make)

Operate to 86 TA & 86 TB (Trip to Turbine Master Trip Relays) & 86 GA & 86 GB (Trip to Generator
Master Trip Relays)
Current setting: 10 %, (0.10 Amps)
Function: IDMT
CT ratio : 1 00 /1 Amps.
TMS : 0 . 25 .

22) Rotor earth fault relay (XR1, Woodward Make)


Operate to 86 TA & 86 TB (Trip to Turbine Master Trip Relays) & 86 GA & 86 GB (Trip to Generator
Master Trip Relays)

Rotor Earth Fault: Ist stage (Alarm): 20.0 K Ohms, Time – 2 seconds.
IInd stage (Trip): 8 K Ohms, Time – 3 seconds.
Page 11 of 13
23) Generator Stator Winding Temperature High:

Alarm: 125 Deg C, Operating time: 3 second.


Trip : 130 Deg C, Operating time: 1 Seconds.

24) Generator Hot Air Temperature High:

Alarm: 80 Deg C, Operating time: 3 Second.


Trip : 85 Deg C, Operating time: 1 second

25) Generator Cold Air Temperature high:

Alarm: 50 Deg C, Operating time: 3 Second.


Trip : 55 Deg C, Operating time: 1 second

26) Generator Bearing Temperature high:

Alarm: 85 Deg C, Operating time: 3 Second.


Trip : 90 Deg C, Operating time: 1 second.

27) Generator Stator Core Temperature high:

Alarm: 125 Deg C, Operating time: 3 Second.


Trip : 130 Deg C, Operating time: 1 second.

28) Exciter Field Winding Temperature high:

Alarm: 125 Deg C, Operating time: 3 Second.


Trip : 130 Deg C, Operating time: 1 second.

Page 12 of 13
29) Thermal Over load Protection:

Operate to 86GA & 86 GB (Trip to Generator Master Trip Relay)


Gen.Thermal
Thermal: Enabled
Thermal: 1.2 Amps
Thermal Alarm:90%
T-Heating: 1 Min
T-Cooling: 1 Min
M-factor:0

30) Sensitive Earth Fault Protection:

ISEF>1 Function:DT
ISEF>1 Direction:Non-directional
ISEF>1 Current:100 mA
ISEF>1 Delay: 1 Sec

Page 13 of 13