Nader NDW3 Series Products Specification
Nader NDW3 Series Products Specification
NDW3 Series
Air Circuit Breaker Product Specification
Date: 2018/03/30
2019.11.27
试制
2019.11.27
Zhang
试制
Zhang
1 Change the reduced capacity coefficient of NDW3-6300 20180509 He Chun Xiangang
Pengyu
Li Huimin
Zhang
Zhang
Change the reduced capacity coefficient of NDW3-2500 20180601 He Chun Xiangang
Pengyu
Li Huimin
Zhang
Change the reduced capacity coefficient of Zhang
20180601 He Chun Xiangang
NDW3-1600、NDW3-2500 and NDW3-4000 Pengyu
Li Huimin
Zhang
Zhang
Change the reduced capacity coefficient of NDW3-1600 20180810 He Chun Xiangang
Pengyu
Li Huimin
Zhang
Zhang
Update all wiring diagrams 20180810 He Chun Xiangang
Pengyu
Li Huimin
Zhang
Zhang
Add Lock to the button to the order specifications 20180810 He Chun Xiangang
Pengyu
Li Huimin
Zhang
Add installation direction external transformer Zhang
20180810 He Chun Xiangang
of N pole Pengyu
Li Huimin
Zhang
Zhang
Add two types mechanical chian 20180810 He Chun Xiangang
Pengyu
Li Huimin
NDW3-6300HU YinJiaCan
4 20190919 XiaBiJian TangRui
Modification of Technical Parameters WangCheng
Contents
Chapter 1 Product Overview ............................................................................................................ 4
Chapter 2 Technical Characteristics ...............................................................................................11
Chapter 3 Controller........................................................................................................................ 16
Chapter 4 Accessories ...................................................................................................................... 30
Chapter 5 Field of Application ........................................................................................................ 62
Chapter 6 Outline and Installation Dimensions ............................................................................ 67
Chapter 7 Electrical Wiring Diagram ............................................................................................ 93
Chapter 8 Ordering Type Selection Specification ....................................................................... 109
2019.11.27
试制
Product Overview 1
1.1 NDW3 Product Series
NDW3-1600
NDW3-2500
NDW3-4000
NDW3-6300
1.3 Breaking Capacity and Short Time Withstand Current of NDW3 Series Circuit
Breaker
Breaking Capacity and Short Time Withstand Current of NDW3 Series Shell Frame (Icu=Ics=Icw)
(kA)
135
140
120
120
100 100
100
85 85 85 85 85
75 75
80
66 66 66 66
60 60
55 55
60 50 50
40
20 2019.11.27
试制
0
AC415V AC690V AC415V AC690V AC415V AC690V AC800V AC1000V AC1140V AC400V AC690V AC400V AC690V AC800V AC1140V AC415V AC690V AC415V AC690V AC800V AC1140V
S H HU S H HU S H HU
NDW3-1600 NDW3-2500 NDW3-4000 NDW3-6300
Note:1) S-Conventional breaking, H-High breaking, HU-High voltage breaking. NDW3-1600 only has one breaking capacity,
which is not distinguished;
2) Icu=Ics=Icw for NDW3-2500, 4000, 6300. For details of NDW3-1600 breaking indicators, see NDW3-1600 technical
parameter list.
2019.11.27
试制
14 13 12 11
Circuit
Parti breaker body
Drawer
Rocker operating seat
Guid position
Guid Three-position
locking
and unlocking
button
■ Measurement and protection: With current, voltage, frequency, phase sequence, power, power factor and
harmonics measurement and protection functions;
■ Current protection features: A variety of overload long-time delay protection, a variety of short circuit
short-time delay protection, short circuit transient protection, earthing protection, neutral line N-pole protection,
current unbalance protection, MCR making capacity protection;
■ Maintenance function: With fault record (8 times), historical current peak record, contact wear equivalent,
query of operation times, clock function, self-diagnostic function, test function and fault display function;
■ With a remote reset device,2019.11.27
realize remote recovery (optional accessories) after fault tripping of the
试制
controller.
1.5.4 Integrated communication network
The NWK22/NWK32 type controller can realize remote sensing, remote control, remote regulating and remote
communication - "four remotes" data transmission function through the communication interface (to be used with
the communication adapter and signal unit).
With the communication adapter, realize the conversion of DeviceNet and Profibus-DP protocols for data
transmission.
1.5.5 AC 1140V circuit breaker
The HU (AC1140V) type circuit breaker is selected, which can be used in the power distribution system in
special fields such as metallurgy, rail transportation, pipe gallery, energy saving and environmental protection.
1.5.6 Three-proofing circuit breaker
The TH (thermal-humidity) type circuit breaker can be selected to meet the three-proofing requirements,
namely, moisture-proofing, mould-proofing and salt spray-proofing, and complies with JB-T834 Technical
Requirements of Tropical Type Low-voltage Apparatus while having passed the following standard related tests:
■ Thermal-humidity test: GB/T 2423.4-2008 Environmental Testing for Electric and Electronic Products.
Part 2: Test Method Test Db: Alternating Thermal-humidity (12h + 12h Cycle);
■ Mould growth test: GB/T 2423.16-2008 Environmental Testing for Electric and Electronic Products.
Part 2: Test Method Test J and Guidelines: Mould;
■ Salt spray test: GBT 2423.18-2012 Environmental Testing for Electric and Electronic Products. Part 2:
Test Method Test Kb: Salt Spray;
■ Enclosure protection grade: GB/T 4208-2008 Enclosure Protection Grade (IP code).
1.5.7 Convenient installation
■ Upper and lower wiring of the main circuit is available;
■ Connection mode.
Wiring mode NDW3-1600 NDW3-2500 NDW3-4000 NDW3-6300
■ Horizontal wiring
Conventional √ √ √ √
■ Vertical wiring
Annotation:6300A of NDW3-6300 only have two wiring modes: vertical wiring、vertical extended wiring.
1.5.8 Multiple safety protection devices
It has drawout type circuit breaker door interlocking, drawout type three-position locking and unlocking device
and off-position key lock, connection terminal protective cover and other protection devices.
1.6 Conforming Standards and Certification
GB/T 2423.4-2008 Environmental Testing for Electric and Electronic Products - Part 2: Test Method - Test
Db: Thermal, Humidity, Cyclic;
GB/T 4207-2003 Methods for the Determination of the Proof and the Comparative Tracking Indices of
Solid Insulating Materials;
GB/T 14048.1-2012 Low-voltage Switchgear and Control Equipment - Part 1: General Rules (IEC
60947-1:2001, MOD);
GB/T 14048.2-2008 Low-voltage Switchgear and Control Equipment - Part 2: Low-voltage Circuit Breaker
(IEC 60947-2:2006, IDT);
GB/T 14048.5-2008 Low-voltage Switchgear and Control Equipment - Part 5-1: Control Circuit Electrical
Appliances and Switch Elements - Electromechanical Control Circuit Electrical
Appliances (IEC 60947-5-1:2003, MOD);
GB/T 14092.3-2009 Environmental Condition for Machinery Products - High Altitude;
GB/T 19608.3-2004 Classification of Special Environmental Condition - Part 3: Plateau;
GB/T 20645-2006 Specific Environmental Condition - Technical Requirements of Low-voltage
Apparatuses for Plateau;
GB/T 20626.3-2006 Specific Environmental Condition - Electric and Electronic Products for Plateau - Part
3: Protection Requirement of Thunder and Lightning, Pollution, Condensation;
NDW3 series of universal circuit breaker has obtained China Compulsory Certification (CCC) for products.
2019.11.27
试制
ND W 3 4000 S
Note: 1. S-Conventional breaking, H-High breaking, HU-High voltage breaking. NDW3-1600 only has one breaking capacity, which is
not distinguished;
2. For details of the product ordering models and specifications, see Chapter 8.
2019.11.27
试制
Technical Characteristics 2
2.1 NDW3-1600 Technical Parameter List
Circuit breaker model NDW3-1600
Rated current In (+40℃) .................................................. (A) 200, 400, 630, 800, 1000, 1250, 1600
North pole rated current ................................................... 100%In
Rated working voltage Ue ................................................ (V) AC220/230/240, AC380/400/415, AC440/480, AC660/690
Rated frequency f ............................................................. (Hz) 50/60
Rated insulation voltage Ui .............................................. (V) 1000
Rated impulse withstand voltage Uimp ............................
2019.11.27 (kV) 12
试制
Number of poles ............................................................... pole 3, 4
Full break timeNote 1 .......................................................... (ms) <25
Closing timeNote 2 .............................................................. (ms) <60
AC220V/230V/240V
Rated limit short-circuit breaking 66
AC380V/400V/415V
capacity
AC440V/480V
Icu (effective value) (kA) 50
AC660V/690V
AC220V/230V/240V
Rated operating short-circuit breaking 55
AC380V/400V/415V
capacity
AC440V/480V
Ics (effective value) (kA) 42
AC660V/690V
AC220V/230V/240V
145
Rated short circuit making capacity AC380V/400V/415V
Icm (peak value) (kA) AC440V/480V
105
AC660V/690V
AC220V/230V/240V
50
Rated short-time withstand current AC380V/400V/415V
Icw (effective value) 1s (kA) AC440V/480V
42
AC660V/690V
AC220V/230V/240V
Electrical life (times) 15000 (200A~630A)、9000 (800A~1250A)、6500 (1600A)
AC380V/400V/415V
Operation frequency
Operating (20 times/h) AC440V/480V
15000 (200A~630A)、5000 (800A~1250A)、3000 (1600A)
performance AC660V/690V
Mechanical life (times) Maintenance-free 15000
Operation frequency
With maintenance 30000
(60 times/h)
Installation type Fixed type, drawout type
Horizontal wiring, vertical wiring, mixed wiring (upper horizontal and lower vertical),
Wiring method of the main circuit
mixed wiring (upper vertical and lower horizontal)
Boundary dimension: W×D×H (mm) Fixed type 3P 259×195×318
Fixed type 4P 329×195×318
Drawout type 3P 248×297×351.5
Drawout type 4P 318×297×351.5
Fixed type 3P 22 (200A~630A) 23 (800A~1600A)
Fixed type 4P 34 (200A~630A) 35 (800A~1600A)
Weight (kg)
Drawout type 3P 43 (200A~630A) 44 (800A~1600A)
Drawout type 4P 56 (200A~630A) 57 (800A~1600A)
Note: 1. Full break time: Interval from the beginning of the circuit breaker disconnection to the end of the arcing time (the same
below);
2. Closing time: Interval from the beginning of the circuit breaker closing to the end of the contact time for all pole contacts (the
same below).
Chapter 3 Controller
3.1 Controller Types .................................................................................................................... 17
3.2 Controller Functions ............................................................................................................. 18
3.3 Controller Panel Description ................................................................................................. 19
3.4 Setting Values and Protective Features of Controller ........................................................... 21
3.5 Working Power Supply of Controller ................................................................................... 28
2019.11.27
3.6 Introduction of Controller 试制
Functions .................................................................................... 29
3.7 Protection Characteristic Curve ............................................................................................ 29
Controller 3
Controller is one of the main components of the circuit breaker, which can provide the function of protecting
the overload, short circuit, grounding, current unbalance, overvoltage, undervoltage, voltage unbalance,
overfrequency, underfrequency, reverse power and other failures, and realize reasonable operation of the power grid
through the load monitoring, required value protection, regional interlocking and other functions. Controller has the
function of measuring the current, voltage, power, frequency, electric energy, required value, harmonic and other
power grid parameters; and the function of recording the fault, alarm, operation, maximum historical current,
contact wear and other operating maintenance parameters. When the power network is carrying on communication
network, the controller can realize the remote sensing, remote communication, remote control and remote regulating
at the remote terminal of the electric power automation network.
3.1 Controller Types
NWK22 /NWK32
Controller
Controller Controller
Pictures
Up Up
Function Function
Select
Exit
Select
Exit
NWK31 and NWK32 are applied to NDW3-1600,NWK21 and NWK22 are applied to NDW3-2500、NDW3-4000
and NDW3-6300
indicators
8. Setup, query indicators
9. 5 operation buttons
10. Unused temporarily
Function
Exit
Down
Note: 1. The double-point underline frame displays a controller with the voltage display function, while this display isn’t available
without the optional voltage function;
2019.11.27
2. Tx,Rx is only used for internal testing in the company. 试制
2) Express inverse time limit (power distribution protection) EI(G): t= 1.25 TR /(N2-1)
3) Express inverse time limit (motor protection) EI(M): t= 1.3974 TR ×ln[N2/(N2-1.15)]
4 types of protection curve 4) High-voltage fuse compatible HV: t = 4.0625 TR /(N4-1)
N= I/ Ir I—Fault current t—Long time-delay action time Ir—Long time-delay setting
current TR—Long time-delay setting time
Description: NWK21/NWK31 controller has only standard power distribution protection I2t;
NWK22/NWK32 controller provides 4 types of protection curves.
1) Standard power distribution NWK21/NWK31: 15s, 30s, 60s, 120s, 240s, 480s
protection I2t
Time setting valve tR (1.5 Ir) NWK22/NWK32: 15s, 30s, 60s, 120s, 240s, 360s, 480s, 600s, 720s, 840s, 960s
1.5Ir 15 30 60 120 240 360 480 600 720 840 960
Tripping time t
(s) 2.0 Ir 8.44 16.88 33.75 67.5 135 202.5 270 337.5 405 472.5 540
(Accuracy of 6.0 Ir 0.94 1.88 3.75 7.5 15 22.5 30 37.5 45 52.5 60
±10%)
7.2 Ir 0.65 1.30 2.60 5.21 10.4 15.6 20.8 26 31.3 36.5 41.7
NWK22/NWK32: See the table below for the overload long-time delay protection action delay
2)~4) Protection curve type
time of C1~C16
Current (I/Ir) Tripping time
1.05 > 2h Inaction
Protective features (accuracy of 1.3 (power distribution
< 1h Action
±10%) protection)
1.2 (generator protection) < 1h Action
The action time is calculated according to four types of
≥1.2 Ir
protection formula or curve queried
NWK21/NWK31: 30min (ON) or OFF
NWK22/NWK32: Instantaneous, 10min, 20 min, 30 min, 45 min, 1h, 2h, 3h or OFF
Thermal memory time Description: 1. The auxiliary power supply of controller features the thermal memory function;
turn off the auxiliary power supply to clear the thermal memory;
2. Setting OFF, it is possible to turn off the thermal memory function.
Overload pre-alarm NWK21/NWK31 &NWK22/NWK32
Short circuit short-time delay protection 8IR 0.2s Definite time limit, I2t-ON
Auxiliary contact output of the circuit breaker status, contact capacity: AC250V/16A
Overload long-time
delay protection
2019.11.27
试制
For each protection characteristic curve of controller, see the User Manual of NWK21 and NWK31 Controller and
User Manual of NWK22 and NWK 32 Controller
Chapter 4 Accessories
4.1 Accessories list ...................................................................................................................... 31
4.2 Electrical Control Accessories .............................................................................................. 32
4.3 Signal Output Accessories .................................................................................................... 35
4.4 Related Accessories of Controller ......................................................................................... 37
4.5 Safety Accessories................................................................................................................. 50
2019.11.27
4.6 Lock and interlocking device
试制................................................................................................ 51
Accessories 4
4.1 Accessories list
Accessory Type of the installation
Accessory name Configuration Remarks
category structure
Standard
Closed electromagnet Fixed type/drawout type
configuration
Standard
Shunt release Fixed type/drawout type
configuration
Electrical control Standard
Motor operating mechanism Fixed type/drawout type
accessories configuration
Undervoltage release Optional Fixed type/drawout type
Undervoltage release (loss of voltage Either
Optional Fixed type/drawout type
protection)
Remote reset electromagnet Optional Fixed type/drawout type
Standard
Auxiliary switch Fixed type/drawout type
configuration
Closing ready signal output device Optional Fixed type/drawout type
Signal output
Three-position status signal output
accessories Optional Drawout type
device of the drawer seat
Standard
Secondary terminal Fixed type/drawout type
configuration
External N-pole transformer
Optional Fixed type/drawout type
(rectangular, flexible type)
Shell frame level
External current leakage transformer Optional Fixed type/drawout type
≤4000A
Power supply module NWDF1 Optional Fixed type/drawout type
To be used with
Relay module NWDF1-RM Optional Fixed type/drawout type the power supply
module
Communication adapter
Optional Fixed type/drawout type
NWDF1-MD/MP
Related accessories
Message notification module
of controller Optional Fixed type/drawout type
NWDF1-SMS
Temperature alarm protection device Optional Fixed type/drawout type
Remote intelligent I/O module
Optional Fixed type/drawout type
NWDF1-C8/S12/SC64/SCM423
6-channel programmable output module
Optional Fixed type/drawout type
NWDF1-C6
Accessory monitoring unit NWDF1-AM Optional Fixed type/drawout type
Energy-storing signal communication
Optional Fixed type/drawout type
module NWDF1-S1
Voltage conversion module NWDF1-P2 Optional Fixed type/drawout type
Standard
Phase partition Fixed type/drawout type
configuration
Safety accessories Counter Optional Drawout type
Door frame Optional Fixed type/drawout type
Dust cover Optional Drawout type
Off-position key lock Optional Fixed type/drawout type
Lock and
Button lock Optional Fixed type/drawout type
interlocking device
Door interlock Optional Drawout type
Mechanical interlocking Optional 2019.11.27 type
Fixed type/drawout
Power supply 试制
For the two-way
conversion system Power automatic switching device (ATS) Optional Fixed type/drawout type
power supply
4.2.5 Undervoltage release (loss of voltage protection), loss of voltage release for short
◆ Action features of the loss of voltage release
1) When the applied voltage suddenly drops to 0~30% of the rated
operational voltage, the loss of voltage release will work to disconnect the circuit
breaker;
2) When the applied voltage is less than 30% of the rated operational voltage
of the loss of voltage release, the loss of voltage release will make the circuit breaker cannot be closed;
3) When the applied voltage is 85%~110%
2019.11.27 of the rated operational voltage of the loss of voltage release, the
试制
loss of voltage release can guarantee the reliable closing of the circuit breaker.
4) When the applied voltage drops no less than 35% of the rated operational voltage, the loss of voltage
release can be closed to guarantee the reliable closing of the circuit breaker.
◆ The loss of voltage release can be divided into instantaneous release and delayed release, which is
mainly composed of coil, iron core component and electronic parts.
◆ Loss of voltage delayed release
The loss of voltage delayed release sets the delay time of the release action through toggling the toggle
switch on the loss of voltage delayed device. Delay time: NDW3-1600/6300:0s~10s adjustable for
clients(factory default setting value is 3s), and its step length is 1s; NDW3-2500/4000:1s、3s、5s.
◆ See the table below for the power consumption of loss of voltage release.
Power Consumption Table of Loss of Voltage Release
Operating power
Rated insulation voltage (Ui) Rated operational voltage (Ue)
NDW3-1600 NDW3-2500、4000、6300
AC220V(AC230V) 50Hz/60Hz 0.8VA 4VA
400V
AC380V(AC400V) 50Hz/60Hz 0.8VA 8VA
4.2.6 Remote reset electromagnet
This accessory is installed in the controller base. In case of fault tripping and
troubleshooting of controller, the remote reset electromagnet can reset the reset
button of the circuit breaker for the normal closing/opening operation of the
circuit breaker
◆ Action features of remote reset electromagnet
1) When the power supply voltage of the remote reset electromagnet
maintains at 85%~110% of the rated control supply voltage, operation of the shunt release can make the
circuit breaker disconnect;
2) Remote reset electromagnet is the short-time duty-type;
3) Power-on time >200ms.
◆ Technical Parameters of Remote Reset Electromagnet
Power Consumption Table of Remote Reset Electromagnet
Rated insulation voltage (Ui) Rated control supply voltage (Us) Instantaneous power
AC220V/AC230V 50/60Hz
55VA
DC220V
400V
DC110V
50W
DC24V
DC-13 5A/250V
Breaking capacity
AC-15 16A/380V
250V 3A
Breaking capacity AC
125V 5A
2019.11.27
试制
4.3.3 Position status signal output device of the drawer seat (on the drawer seat)
When the drawer-seat circuit breaker body is in the "Separation", "Test" and
“Connection" positions of the drawer seat(Pop-up the red reset button in front of the
drawer seat), the triolocation electric indication device can output the electrical status
signal corresponding to the three positions with the signal output terminal located on
the left side of the drawer seat. See the table below for technical parameters
DC 125V 0.4A
Breaking capacity
AC 250V 16A
Pollution level 3
conductor
conductor
connection
Intelligent
controller
Intelligent
controller Intelligent
controller
External N-phase
transformer
3P 4P (3P+N)T
Intelligent
controller
PE or
PEN
◆ Transformer type
For rectangular and flexible-type transformers, users can select the shell frame current (or N-pole current)
and dimensions.
1) Rectangular transformer
★ Rectangular transformer code
Transformer code Hole dimensions mm Applicable shell frame
N1 62×21 1600
N2 102×32.5 1600
★ See the figure below for outline and installation dimensions of the rectangular transformer.
★ pay attention to the direction for use:the current flows from P1 to P2.
2019.11.27
试制
N3 external transformer N4 external transformer
★ See the figure below for outline and installation dimensions of the flexible transformer.
★ pay attention to the direction for use:the inlet wire direction is shown in the picture.
★ Install the flexible transformer on the busbar as shown in the figure, and connect the transformer
conduction to the secondary circuit: Red to No. 25 and green to No. 26. Standard configuration of the
conductor is 3m.
4.4.2 External current leakage transformer
◆ When the grounding protection mode is residual current protection (E) type, an external current
leakage transformer is required. The controller judges action via the output signal of the external current
leakage transformer.
◆ See the figure below for the current leakage protection schematic (3P and 4P system).
External current External current
leakage transformer leakage transformer
N
PE
R Intelligent
controller Intelligent
controller
transformer
◆ When install the circumscribed electric leakage mutual inductor, there is no need in distinguishing
directedns.
2019.11.27
试制
Outline and Installation Dimension Diagram of the External Current Leakage Transformer
Outline and Installation Dimension Diagram of Power Supply Outline and Installation Dimension Diagram of Power Supply
Module NWDF1-P1 Module NWDF1-P3/P5
4.4.4 Relay module NWDF1-RM
◆ Function: Signal unit of controller is commonly used in fault alarm or
indication, etc. When the circuit breaker is opened, closed or when the load
capacity is larger, the control should be carried out after conversion through
this module. Match with the power supply module NWDF1 to achieve the
"four remotes" function;
◆ Contact capacity: AC250V, 10 A; DC24V, 10 A;
◆ Appearance and installation: To be used with the controller power supply
module ST-IV, see the installation diagram of relay module.
products to achieve the remote communication, remote regulating, remote control and remote sensing
functions on DeviceNet and ProfiBus DP.
1) NWDF1-MD(MDC-225) communication adapter realizes conversion from the ModBus-RTU protocol to
the DeviceNet protocol;
2) NWDF1-MP(PM-127) communication adapter realizes conversion from the ModBus-RTU protocol to
the Profibus DP protocol;
3) NWDF1-ME(ES-301A) communication
2019.11.27
adapter realizes conversion from the ModBus-RTU protocol to
试制
the Ethernet protocol;
4) NWDF1-MC(NT50-CO-RS) communication adapter realizes conversion from the ModBus-RTU
protocol to the CAN protocol;
5) See the attached manual of each accessory for the communication protocol.
6) NWDF1-MD and NWDF1-MP only support communication for a single device.
◆ Appearance and function indication Power
Communica
1. Button
RS485
PROFIBUS DP
interface
address setting
4. Devicenet
2. Module status address shows
indicator MS
LED
indicator NS interface
NWDF1-MD NWDF1-MP
Install the
guide rail here
Unit: mm
NWDF1-MD Outline and Installation Dimension Diagram NWDF1-MP Outline and Installation Dimension Diagram
2019.11.27
试制
Reverse polarity effects Does not work, but does not damage the module
Voltage above 40VDC may cause the permanent damage of
Voltage mismatch
the module
Voltage sag Sag for 10ms can still work without interruption
interface Standard RS485, 2-wire, Modbus RTU
Optional Modbus address 1~247
Baud rate 1200/2400/4800/9600/19200/38400bps
Communication Parity bit CRC check, without support for parity
Isolation voltage 1000Vrms
Maximum number of
32
modules for a single bus
Protection class IP20
Dimensions 91.6 x 54 x 58.5mm
Installation
Installed with two 35mm standard guide rails
mode
Outline and Installation Dimension Diagram of the Remote Intelligent I/O Module
See the figure for outline and installation dimensions of 6-channel programmable output module.
2019.11.27
试制
2019.11.27
试制
Fixed type appropriative holder Phase Partition Input and output line partition
NDW3-2500HU
Fixed type appropriative holder Phase Partition Input and output line partition
NDW3-4000HU
Note:When installing, NDW3-4000HU input and output line partition side with N, A, B and C should be
installed upturned.
4.5.2 Counter
Counter is used to record the number of the "close-open" operation of the circuit
breaker.
4.5.3 Doorframe
Divided into fixed type and drawout type, it is mainly placed on the door of the cubicle for sealing effect, and can
make the protection level of the circuit breaker reaches IP40. It is beautiful and practical.
Fixed type
Drawout type
When the off-position lock is optionally selected, this accessory is sent to the user after being assembled
with the circuit breaker. As the off-position lock protrudes out of the circuit breaker mask, the installer shall pay
attention to the protruding dimension when opening the power distribution cabinet door. This dimension diagram
and data are as follows.
2019.11.27
试制
Mounting plate of the circuit Mask centerline of the Mounting plate of the circuit
breaker cabinet circuit breaker breaker cabinet
Unit: mm
a b c d
Model Fixed Drawout Fixed Drawout Fixed Drawout Fixed Drawout
type type type type type type type type
NDW3-1600 17 220 134 114 42
NDW3-2500 27 247 125 163 45
NDW3-4000
NDW3-6300
4.6.2 Button lock
◆ To be used with a padlock, it is used to prevent non-staff from illegally
operating the opening/closing button (padlock should be prepared by
users).
◆ When the off-position lock is optionally selected, this accessory is sent
to the user after being assembled with the circuit breaker. As the
off-position lock protrudes out of the circuit breaker cover, the installer shall pay attention to the
protruding dimension when opening the power distribution cabinet door.
This dimension diagram and data are as follows.
Fixed
2019.11.27
试制
Mounting plate of the Mask centerline of the Mounting plate of the Drawer seat connection
circuit breaker cabinet circuit breaker circuit breaker cabinet position
Drawo
Unit: mm
a b c d
Model Fixed Drawout Fixed Drawout Fixed Drawout Fixed Drawout
type type type type type type type type
NDW3-1600 18 155 187.5 91.7 108.2 26.4
NDW3-2500
27 204 243.7 106 143.8 26.4
NDW3-4000
NDW3-6300 27 204 243.7 106 104.4 26.4
Circuit breaker can be applicable to the following power supply state interlocking
1) Two circuit breakers (one for closing and one for opening)
Usage mode is shown in the figure below, while interlocking action state is shown in the figure below.
2) Three circuit breakers (one for closing and two for opening)
Usage mode is shown in the figure below, while interlocking action state is shown in the figure below.
2019.11.27
试制
Adjustment schematic diagram: One for closing and two for opening
Adjustment schematic diagram: Two for closing and one for opening
Adjusted to the
hole position I
2019.11.27
试制
Circuit breaker 1
Cabinet
900 (max)
Circuit breaker 2
Circuit breaker 1
Mounting hole of the
circuit breaker
600 (max)
Circuit breaker 2
600 (max)
Circuit breaker 3
Note: During the process of assembly adjustment, the overlong part of the connecting rod can be appropriately eliminated.
Adjustment schematic diagram:
Adjusted to the
hole position II
2019.11.27
试制
Hole dimensions
Note: Due to the power automatic switching control device has overvoltage and undervoltage protection functions, in order to
guarantee the consistency and reliability of the system protection, the universal circuit breaker used for power supply automatic
switching control device can't install undervoltage release, and the power automatic switching control device and the mechanical
interlocking (two interlocking) shall be used together.
SIM
AC230
DC24V DC24V
Status
(control)
Note: 1. The red line represents the RS485 communication line, which is connected from the communication interface of controller;
the black line represents the power supply line; the blue line represents the signal output line of the circuit breaker secondary terminal
to output the circuit breaker status or control signal.
2. The message notification module needs to use a SIM card, which shall be prepared by users.
With the Modbus-RTU mode, connect to the computer system via the conversion interface of RS485/RS232
and twisted shielded wire line from the controller RS485 interface, or connect the RS485 signal interface of circuit
breaker via the serial port server or communication manager, and then connect with computer via the Ethernet
interface (RJ45 interface). Related communication parameters of Modbus-RTU are shown in the table below.
Communication protocol Modbus 2019.11.27
试制
Communication address 0~255
With the communication network, the same line can connect up to 32 communication circuit
breakers (16 drawout circuit breakers) at the same time.
The NDW3 series of universal circuit breakers (hereinafter referred to as circuit breakers) can be applied to
the distribution network with AC of 50 Hz / 60 Hz, rated current of 200A ~ 6300A, rated insulation voltage of
1140V, rated operational voltage of AC220/230/240V, AC380/400/415V, AC440/480V, AC660/690V , AC800V,
AC1000V and AC1140Vfor distribution of electrical energy and protecting circuit and power equipment from
overload, under-voltage, short circuit, single phase grounding and harm of other faults. It also has an isolating
function at the same time. The circuit breaker has multiple protection functions. It can avoid unnecessary sudden
power failure while realizing highly accurate selective protection, and improve the reliability and security of the
power supply system.
If the altitude of the installation site is between 2,000 m to 5,000 m, it can be specially customized. For the
working performance, refer to the correction value in the following table.
Rated working current Altitude
Type Rated current(A) 2000m 3000m 4000m 5000m
200~630 1.0In 1.0In 1.0In 1.0In
NDW3-1600 800~1000 1.0In 1.0In 1In 1In
1250~1600 1.0In 1.0In 0.97In 0.87In
630~1600 1.0In 1.0In 1.0In 1.0In
NDW3-2500
2000~2500 1.0In 0.93In 0.88In 0.85In
2019.11.27
800~2500 试制 1.0In 1.0In 1.0In 1.0In
NDW3-4000 3200 1.0In 1.0In 1.0In 1.0In
4000 1.0In 0.93In 0.88In 0.82In
4000、5000 1.0In 1.0In 1.0In 1.0In
NDW3-6300
6300 1.0In 0.93In 0.88In 0.82In
Annotation:NDW3-1600 is not included in this table, the correction value of NDW3-1600 refer to the following
table.
Altitude m 2000 3000 4000 5000
Note: 1. The table indicates the copper bar specifications adopted when the circuit breaker is under the ambient temperature of 40℃
and the open wide installation under the heating condition meets the stipulation in GB/T14048.2. If the temperature is higher than
40℃, the quantity of copper bar should be increased, or the capacity should be reduced.
2. The above data is calculated according to the test and theory, and for reference only.
3. The maximum permissible temperature of the copper bar is no more than +110℃.
4. The electrical gap of copper bar is ≥15mm with the altitude more than 5, 000m and relative humidity more than 90%; the
electrical gap shall be adjusted according to the table 1 of 7.1.1in the sdandard GB/T 20645.
5.4 The power loss of the incoming and outgoing lines of the circuit breaker (ambient
temperature +40℃)
The power loss2019.11.27
of the incoming and outgoing lines of the circuit breaker
试制
Model Power loss of the fixed type Power loss of the drawout type
2019.11.27
试制
6.1 NDW3-1600
NDW3-1600 fixed type (unit: mm)
Dimensions Fixed Details
cabinet door
2019.11.27
试制
Note: For the 3-pole circuit breaker, X and Y are the Rated current Size of busbar a (mm)
symmetric axes of the front panel; 200A, 400A, 630A 10
Note: For the 3-pole circuit breaker, X and Y are the Rated current Size of busbar a (mm)
symmetric axes of the front panel; 200A, 400A, 630A 10
2019.11.27
试制
cabinet door
2019.11.27
试制
Note: For the 3-pole circuit breaker, X and Y are the Rated current Size of busbar a (mm)
symmetric axes of the front panel; 200A, 400A, 630A 10
Note: For the 3-pole circuit breaker, X and Y are the Rated current Size of busbar a (mm)
symmetric axes of the front panel; 200A, 400A, 630A 10
2019.11.27
试制
6.2 NDW3-2500
NDW3-2500 fixed type (unit: mm)
Dimensions Fixed Details
cabinet door
2019.11.27
试制
Note: For the circuit breaker, X and Y are the symmetric axes Size of busbar a
Rated current
of the front cover; (mm)
2019.11.27
Note: For the circuit breaker, X and Y are the symmetric axes Rated current 试制 Size of busbar a (mm)
of the front cover; 630A, 800A, 1000A, 1250A 15
2019.11.27
试制
Note: For the circuit breaker, X and Y are the symmetric axes Rated current Size of busbar a (mm)
of the front cover; 630A, 800A, 1000A, 1250A 15
cabinet door
50 min.
2019.11.27
Note: For the circuit breaker, X and Y are the symmetric axes Rated current 试制 Size of busbar a (mm)
of the front cover; 630A, 800A, 1000A, 1250A 15
2019.11.27
试制
Note: For the circuit breaker, X and Y are the symmetric axes Rated current Size of busbar a (mm)
of the front cover; 630A, 800A, 1000A, 1250A 15
Note: For the circuit breaker, X and Y are the symmetric axes Rated current Size of busbar a (mm)
of the front cover; 630A, 800A, 1000A, 1250A 15
2019.11.27
试制
6.3 NDW3-4000
NDW3-4000 fixed type (unit: mm)
Dimensions Fixed Details
Direction A
cabinet door
2019.11.27
试制
Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;
2019.11.27
试制
Note: X and Y axes are the symmetric axes of the front mask;
2019.11.27
试制
Note: X and Y axes are the symmetric axes of the front mask;
cabinet door
50 min.
2019.11.27
试制
2019.11.27
试制
Note: X and Y axes are the symmetric axes of the front mask;
2019.11.27
试制
Note: X and Y axes are the symmetric axes of the front mask;
6.4 NDW3-6300
NDW3-6300 fixed type (unit: mm)
Dimensions Fixed Details
Direction A
Direction A
cabinet door
2019.11.27
试制
Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;
Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;
2019.11.27
试制
Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;
Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;
2019.11.27
试制
Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;
50 min.
Direction A
Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;
2019.11.27
试制
Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;
Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;
Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;
Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;
2019.11.27
试制
6.5 The Circuit Breaker Cabinet Door Open Hole and the Installation Pitch
Hole dimensions of NDW3-1600 door frame (unit: mm)
2019.11.27
Mask center Mask center
试制
Mask center
Mask center
Mask center
Mask center
Mask center
Mask center
★ Conduct reliable grounding protection when installing the circuit breaker. The grounding place of the
circuit breaker has an obvious grounding symbol.
★ Carry out wiring of the control circuit according to the wiring diagram when installing the circuit
breaker; check whether the working voltage of the undervoltage, shunt, closed electromagnet, motor,
controller and related parts conforms to the actual voltage, and then carry out the secondary circuit
energizing. In case of drawout circuit breaker, the circuit breaker should be shaken into the test
position, then the undervoltage release will close and then the circuit breaker can be closed.
★ Pressing (or powering on) the closing button after the energy storage of the motor, the circuit breaker
will close.
★ Pressing (or powering on) the
2019.11.27
opening button, the circuit breaker will open.
试制
★ For manual storage of energy, pull the handle on the front panel up and down, when a "click" sound
can be heard after seven times; the panel shows "storage of energy", and the storage of energy ends.
At this point, if there's undervoltage tripping, power on it (no need if without undervoltage tripping),
then carry out closing operation.
★ Installation screws of the circuit breaker is shown in the table below
Installation Screws of the Circuit Breaker
Circuit breaker Connection conditions between bus and terminal
NDW3-1600 M10 bolt, level 8.8, with contact washer, tightening torque 45N.m
NDW3-2500 M12 bolt, level 8.8, with contact washer, tightening torque 60N.m
800-2500A M12 bolt, level 8.8, with contact washer, tightening torque 60N.m
NDW3-4000
3200-4000A M14 bolt, level 8.8, with contact washer, tightening torque 97N.m
Extended vertical wiring M12 bolt, level 8.8, with contact washer, tightening torque 60N.m
NDW3-6300
Other wiring modes M14 bolt, level 8.8, with contact washer, tightening torque 97N.m
The circuit breaker is installed in the cabinet, the safe distance between the circuit breaker and the
cabinet
When users install the circuit breaker into the cabinet, the safe distance between the circuit breaker and
the cabinet is shown in the figure below, and the installation dimensions are shown in the table below.
2019.11.27
试制
2019.11.27
试制
2019.11.27
试制
break monitoring
2019.11.27
Page 96 of 117
output (3P+N)
Current leakage transformer
output end
Remote reset function
input end
Definition table of NDW3-1600 terminal number is shown in the following table
Energy-storing signal
unit output
Communication interface
Electric energy storage and
energy storage indicators
Undervoltage release
Loss of voltage release
Shunt release
Closed electromagnet
Document Version: 3
Connecting terminals of
auxiliary switch
NDT2920213 Document Version: 3
Note:
1. The current state of the circuit breaker is de-energized, disconnected, connected, no energy stored;
2. The dashed part shall be wired by users;
3. When the power supply of Q, F, B, M, controllers is not the same, they shall be powered on respectively;
7. All the signal units are passive signals. Users can choose S1, S2, S3 modes as required.
SB1 - Shunt button (to be prepared by users); SB2 - Close button (to be prepared by users);
SB3 - Remote reset button (to be prepared by users); SA1 - Motor travel switch;
SA2 - Closing ready travel switch; SA4 - Fault tripping travel switch;
SA5 - Opening and closing indicating travel switch;
ST power
ST power
supply supply module
module IV IV
Device-net protocol
试制
2019.11.27
Motor Energy
energy storage Undervoltage Electric Electric Closing ready Remote reset
Main power supply Controller storage indicator off opening closing Auxiliary switch
Green
Page 98 of 117
Optional function
Power supply
The following diagram is the NDW3-2500 and NDW3-6300 full-function wiring diagram
Red
Document Version: 3
The following diagram is the input/output interface of NDW3-2500 and NDW3-6300 controller
Controller
Communication
interface Signal unit
N-phase external
transformer
2019.11.27
试制
Definition table of NDW3-2500 and NDW3-6300 terminal number is shown in the following table
2019.11.27
试制
Note:
1. The current state of the circuit breaker is de-energized, disconnected, connected, no energy stored;
7. To realize “four-remote” functions, clients should choose signal unit, and add power source module and relay module.
8. When choose check-for-voltage closing device, electrical wiring diagram of closed electromagnet and under-voltage trip
SB1 - Shunt button (to be prepared by users); SB2 - Close button (to be prepared by users); SB3 - Remote reset button (to be
prepared by users);
SA1 - Motor travel switch; SA2 - Closing ready travel switch; SA4 - Fault tripping travel switch;
SA5 - Opening and closing indicating travel switch;
ST power
supply module
IV
ST power
supply module
IV
Device-net protocol
Modbus protocol
试制
2019.11.27
Green
Optional function
Power supply
Red
7.3 NDW3-4000 Electrical Wiring Diagram and Terminal Number Definition
Document Version: 3
NDT2920213 Document Version: 3
Remote reset
Controller
Communication
interface Signal unit
N-phase external
transformer
2019.11.27
试制
break monitoring
Grounding wire of controller
Three-phase three-wire
Voltage signal input ends
system: 21#23# shall be
(N, A, B, C) short connected to U2
NDT2920213
Communication interface
Electric energy storage and
energy storage indicators
Undervoltage release
Loss of voltage release
Shunt release
Closed electromagnet
Document Version: 3
Connecting terminals of
auxiliary switch
NDT2920213 Document Version: 3
Note:
1. The current state of the circuit breaker is de-energized, disconnected, connected, no energy stored.
7. All the signal units are passive signals. Users can choose S1, S2, S3 modes as required.
SB2 - Undervoltage button (to be prepared by users); SB5 - Remote reset button (to be prepared by users);
SA1 - Motor travel switch; SA2 - Closing ready travel switch; SA2 - Closing ready travel switch;
SA3 - Undervoltage indicating travel switch; SA4 - Fault tripping travel switch;
SA5 - Opening and closing indicating travel switch; XT - Secondary terminal; F - Shunt release;
B - Closed electromagnet; Q - Undervoltage release or loss of voltage release (instantaneous or delayed); YF - Remote reset;
T - Auxiliary contact of the circuit breaker (see attached figure); Fu - Fuse (to be prepared by users); M - Energy
storage motor.
Four-group switch contacts Four normally opened and Six-group switch contacts
four normally closed
2019.11.27
试制
Secondary
Terminals of
Circuit Breaker
Check-for-voltage
Wiring Harness
(Optional)
1)6、7——The check-for-voltage closing device need to monitor the state of circuit breaker, and clients should
make a choice between it and circuit open contactors output function.
Note: Check-for voltage module’s 6 and 7terminals should be connected to without-power normally closed
contactors;
2)12、13 和 14、15——Choose one of appropriative under-voltage trip controlled by check-for-voltage closing
device, PV appropriative under-voltage (voltage-loss) trip (adjustable from 0~10s) and signal unit function;
3)33、34——Check-for-voltage closing device power source is the same to common under-voltage trip power
source, and clients can wire according to practical requirements, and only AC220V/230V、AC380V/AC400V
power source can be allowed to connect.
4)37、38——When choose check-for-voltage closing device function, the closed electromagnet will be 37 and 38,
and turn closing voltage rotary button of check-for-voltage closing device to non-off state, the closed
electromagnet will be controlled by check-for-voltage closing device automatically, and a to b wires are suggested
not to be connected.
5)If only take controlling closed electromagnet manually, we should turn off closing voltage rotary button of
check-for-voltage closing device module, and connect a to b wires including SB2.
6)If clients do not choose check-for-voltage closing device, and the closed electromagnet is still 37 and 38, then
they should wire according to general electrical wiring diagram of ACB.
7)6, 7, 12, 13, 14, 15, 38 should be connected to corresponding secondary terminals by wiring harness.
8)The imaginary line is wiring of clients, and real line is internal wiring of products.
2019.11.27
试制
2019.11.27
试制
2019.11.27
试制
Enterprise
1 brand low-voltage electrical appliance
code
2019.11.27
2 Product code Air circuit breaker 试制
3 Design SN 3
Shell frame
4 16-1600, 25-2500, 40-4000, 63-6300
level
NDW3-1600 is only
Installation
7 Non-marked - fixed type, C - drawout type
structure
KM2-NWK21/NWK31 (AC220V/AC230V),
KY4-NWK22/NWK32 (DC110V),
KY5-NWK22/NWK32 (DC24V)
Continued:
Protection type: Not-standard - conventional type, V - voltage measurement and
protection, P - harmonic measurement and protection
Communication function: H (Modbus protocol) MP (Profibus-DP protocol) 1. This shall be
MD (Devicenet protocol) DXX-Message notification module omitted
Signal unit: S1- 4DO S2- 3DO, 1DI S3-2DO, 2DI if the controller has
Continued:
3. The special
under-voltage
Conventional undervoltage delay: 0-Instantaneous, 1-1s delay, 3-3s delay, 5-5s delay
release and closed
electromagnet
controlled by the
Under-voltage NDW3-1600/6300 loss of voltage: 0s~10s adjustable by users (the factory default voltage-check
release/loss of setting value is 3s), with a step of 1s; closing device are
voltage release
15 internal accessories,
Delay
2019.11.27 while the
time/voltage-ch 试制
NDW3-2500/4000 loss of voltage delay: 1-1s delay, 3-3s delay, 5-5s delay voltage-check
eck harness
closing controller
module is the
external accessory
0- Without harness, 1 - With harness
(applicable to
NDW3-2500)
Applicable to
Not-marked - four groups conversion, A6 - six groups conversion
NDW3-1600
Applicable to
Auxiliary Not marked - Four opened and four closed, A55 - Five opened and five closed, A66 -
16 NDW3-2500
contact Six opened and six closed
and NDW3-6300
Not-marked - Four groups conversion, A6 - Six groups conversion, A44 - Four Applicable to
opened and four closed NDW3-4000
Continued:
1. Power supply module,
M - Doorframe
relay module, external
current leakage
transformer,
F - Dust cover
programmable output
module, message
R - Relay module module, communication
adapter and N-pole
external transformer
P - Power supply module (in line with the controller voltage in default)
should be used with the
controller;
2. Carry out the
S - Button lock
sequence arrangement
according to the table,
External BC - Programmable output module (6-channel) with “/” for separation;
18
accessories 3. The accessory
IO1 - Remote I/O module C8 monitoring unit can’t be
selected with the
IO2 - Remote I/O module S12
communication function,
signal unit and controller
IO3 - Remote I/O module SC64
with “V” and “P”
IO4 - Remote I/O module SCM423 functions
simultaneously;
AM - Accessory monitoring unit 4. The energy-storing
signal communication
module component can’t
P2 - Voltage conversion module
be selected with the
controller with “V” and
“P” functions
TC - Energy-storing signal communication module component
simultaneously.
Not marked - Horizontal wiring, J1 - Horizontal extended wiring, J3 Vertical NDW3-6300 with the
wiring, J4 - Vertical extended wiring rated current of 6300A
J5 - Mixed wiring (upper horizontal, lower vertical), J6 - Mixed wiring (upper only has two wiring
19 Wiring mode
vertical, lower horizontal) modes: Vertical wiring
J7 - Mixed extended wiring (upper horizontal and lower vertical), J8 - Mixed
2019.11.27
and vertical extended
extended wiring (upper vertical and lower horizontal) 试制 wiring.
Product usage
20 Not-marked - Conventional, TH - Thermal and humidity
type
21 Special notes Customer’s special requirements
Rated working Not-marked - AC690V and below, KV4-AC800V, KV5-AC1000V,
22
voltage KV6-AC1140V
SF11 - key lock device (one lock and one key), SF21 - key lock device (two locks and one
key),
Key lock SF31 - key lock device (three locks and one key), SF32 - key lock device (three locks and 1. Select one from five
two keys), key locks;
SF53 - key lock device (five locks and three keys) 2. Select one from five
SR11 - Mechanical interlocking device (two sets of steel cables, one for closing and one for mechanical interlocks;
opening) 3. SR21 and SR12 are
2019.11.27
SR12 - Mechanical interlocking试制
device (three sets of steel cables, one for closing and two only applicable to the
for opening) NDW3-2500 frame and
Mechanical SR21 - Mechanical interlocking device (three sets of steel cables, two for closing and one above;
interlocking for opening) 4. NDW3-1600 fixed type
SY11 - Mechanical interlocking device (two sets of hard rods, one for closing and one for is not provided with a
opening) mechanical interlock.
SY12 - Mechanical interlocking device (three sets of hard rods, one for closing and two for
opening)
1. It is standard with a
mechanical interlock
Power
with the type selected by
automatic ATS-R/S/F (R: Auto switch and auto recover; S: Auto switch and non-auto recover; F:
customers;
switching Mains - Generator)
2. NDW3-1600 fixed
device
type is not provided with
this accessory.
Number of units
User unit Date of ordering:
ordered:
Shell frame □ NDW3-1600 □ NDW3-2500 □ NDW3-4000 □ NDW3-6300
level
Installation
□ Fixed type □ C - Drawout type
structure
NDW3-1600: □200 □400 □630 □800 □1000 □1250 □1600
Rated current NDW3-2500: □630 □800 □1000 □1250 □1600 □2000 □2500
(A) NDW3-4000: □800 □1000 □1250 □1600 □2000 □2500 □3200 □4000
NDW3-6300: □4000 □5000 □6300
□ S-Conventional breaking (AC690V and below) □ H-High breaking (AC690V and below)
□ HU-High voltage breaking (AC800V) □ HU-High voltage breaking (AC1000V)
Breaking type
□ HU-High voltage breaking (AC1140V)
Ba Note: These options are not distinguished with NDW3-1600, no selection required
sic Number of
□ 3 (3 poles) □ 4 (4 poles) □ 5(3P+N)
par poles
a □ Horizontal wiring (standard configuration) □ J3 - Vertical wiring
me NDW3-1600 □ J5 - Mixed wiring (upper horizontal and lower vertical) □ J6 - Mixed wiring
ters (upper vertical and lower horizontal)
□ Horizontal wiring (standard configuration) □ J1 - Horizontal extended wiring □ J3 -
NDW3-2500 Vertical wiring □ J4 - Vertical extended wiring □ J5 - Mixed wiring (upper
horizontal, lower vertical) □ J6 - Mixed wiring (upper vertical, lower horizontal)
Wiring mode □ Horizontal wiring (standard configuration) □ J1 - Horizontal extended wiring □ J3 -
NDW3-4000
Vertical wiring □ J4 - Vertical extended wiring
□ Horizontal wiring (standard configuration) □ J1 - Horizontal extended wiring □ J3 -
Vertical wiring □ J4 - Vertical extended wiring □ J5 - Mixed wiring (upper
NDW3-6300 horizontal, lower vertical) □ J6 - Mixed wiring (upper vertical, lower horizontal)
□ J7 - Mixed extended wiring (upper horizontal and lower vertical) □ J8 - Mixed
extended wiring (upper vertical and lower horizontal)
Product type □ Not-marked - Conventional (standard configuration) TH - Thermal and humidity
Voltage
□ Q1(AC380V/AC400V) □ Q2(AC220V/AC230V)
specificat
Under-voltage □ Q3(DC220V) □ Q4(DC110V) □ Q5(DC24V)
ions
release
delay
□ 0-Instantaneous (0s) Delay: □ 1 (1s delay) □ 3 (3s delay) □ 5 (5s delay)
time
Voltage
Specificat □ S1(AC380V/AC400V) □ S2(AC220V/AC230V)
Loss of ions
voltage release 0s-10s adjustable by users Note: The factory default setting is 3s,
delay NDW3-1600/6300
with a step of 1s
time
NDW3-2500/4000 □ 1 (1s delay) □ 3 (3s delay) □ 5 (5s delay)
Op Voltage-check □ J1(AC380V/AC400V) □ J2(AC220V/AC230V) Note: Applicable to NDW3-2500
tio closing device Included harness or not: □ 0(without harness) □ 1 (with harness)
nal NDW3-1600 □ Four-group conversion (standard configuration) □ A6 - Six-group conversion
acc NDW3-2500/6300 □ Four normally opened and four normally closed (standard configuration) □ A55 - five
ess Auxiliary normally opened and five normally closed □ A66 - six normally opened and six
ori contact normally closed
es NDW3-4000 □ Four-group conversion(standard configuration) □ A6 - six-group conversion
□ A44 - four normally opened and four normally closed
Closing ready □ BX - Closing ready signal output unit
Counter □ JS - Counter
Drawer seat
□ CM1 - Right side of the door interlock □ CM2 - Left side of the door interlock
door interlock
Position
□ CX - Drawer seat three-position signal output
indicator
Door frame □ M Door frame
Dust cover □ F Dust cover
Relay module □ R Relay module
Power supply □ P Power supply module (in line with the operating voltage of controller in default)
module
Button lock □ S Button lock
Programmable
□ BC Programmable output module (6-channel)
module
□ IO1 remote I/O module C8 □ IO2 remote I/O module S12 □ IO3 remote I/O module SC64 □ IO4 remote
Remote I/O
I/O module SCM423
module
Note: To be used with the optional power supply module
Accessory □ AM - Accessory monitoring unit
monitoring Note: It can’t be selected with the communication function, signal unit and controller with “V” and “P”
unit functions simultaneously
Voltage
conversion □ P2 - Voltage conversion module
module
Energy-storing
□ TC - Energy-storing signal communication module component
signal
Note: It can’t be selected with the controller with “V” and “P” functions simultaneously
communication
Off-position □ SF11-One lock one key □ SF21-Two locks one key □ SF31-Three locks one key
lock □ SF32-Three locks two keys □ SF53-Five locks three keys
□ SR11 - Two groups, one for closing and one for opening Note: SR21 and SR12 are only
Cable
Inter □ SR12 - Three groups, one for closing and two for opening applicable to the NDW3-2500
type
lock Mechanical □ SR21 - Three groups, two for closing and one for opening frame and above, while the
ing interlocking NDW3-1600 fixed type is not
Hard rod □ SY11 - Two groups, one for closing and one for opening
acce provided with a mechanical
type □ SY12 - Three groups, one for closing and two for opening
ssori interlock.
es Power supply □ ATS-R type □ ATS-S type □ ATS-F type
automatic Note: 1. Please select a type if mechanical interlocking is standard,; 2. There's no need to select undervoltage
switching release if undervoltage protection is included; 3. The electrical accessories must select the working voltage of
device AC220V; 4. NDW3-1600 fixed type is not provided with this accessory.
Factory setting of the special requirements:
Overload long time-delay current____A time_____s; short-circuit short time-delay current____A
Special requirements time_____s
short circuit transient current____A; ground fault current ____A time____s
Other requirements:
Note: 1. In case of no special requirements, the current and time setting value of controller shall be set according to the factory setting;
2. If you have special requirements, please indicate in the special requirements column.
2019.11.27
试制