Nader NDW3 Series Products Specification

This document provides product specifications for the NDW3 series of air circuit breakers. It includes 3 versions and was last updated in September 2019. The NDW3 series features universal circuit breakers in various rated currents with breaking capacities and short circuit withstand ratings. The document describes the circuit breaker structure, technical characteristics, controller, accessories, applications, installation dimensions, wiring diagrams, and ordering specifications.

Uploaded by

aktrctq
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
910 views117 pages

Nader NDW3 Series Products Specification

This document provides product specifications for the NDW3 series of air circuit breakers. It includes 3 versions and was last updated in September 2019. The NDW3 series features universal circuit breakers in various rated currents with breaking capacities and short circuit withstand ratings. The document describes the circuit breaker structure, technical characteristics, controller, accessories, applications, installation dimensions, wiring diagrams, and ordering specifications.

Uploaded by

aktrctq
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 117

NDT2920213 Document Version: 3

NDW3 Series
Air Circuit Breaker Product Specification

Project Name: NDW3 Series of Universal Circuit Breaker

Project No.: P05009

Prepared by: Zhang Pengyu

Date: 2018/03/30
2019.11.27
试制

Internal & confidential file Page 1 of 117 https://www.quisure.com


NDT2920213 Document Version: 3

Date: 2019/09/19Revision History


Implementati Prepared Reviewed Approved
Version Revision Reason/Content
on Date by by by
Zhang
Zhang
0 Newly increased document 20180401 He Chun Xiangang
Pengyu
Li Huimin

2019.11.27
Zhang
试制
Zhang
1 Change the reduced capacity coefficient of NDW3-6300 20180509 He Chun Xiangang
Pengyu
Li Huimin

Zhang
Zhang
Change the reduced capacity coefficient of NDW3-2500 20180601 He Chun Xiangang
Pengyu
Li Huimin

Zhang
Change the reduced capacity coefficient of Zhang
20180601 He Chun Xiangang
NDW3-1600、NDW3-2500 and NDW3-4000 Pengyu
Li Huimin

Zhang
Zhang
Change the reduced capacity coefficient of NDW3-1600 20180810 He Chun Xiangang
Pengyu
Li Huimin

Zhang
Zhang
Update all wiring diagrams 20180810 He Chun Xiangang
Pengyu
Li Huimin

Zhang
Zhang
Add Lock to the button to the order specifications 20180810 He Chun Xiangang
Pengyu
Li Huimin

Zhang
Add installation direction external transformer Zhang
20180810 He Chun Xiangang
of N pole Pengyu
Li Huimin

Zhang
Zhang
Add two types mechanical chian 20180810 He Chun Xiangang
Pengyu
Li Huimin

Change the Installation Dimensions of


2 20190611 Heguibo Zhangying Yangyuyong
NDW3-2500
ZhangHaiLi
NDW3-2500HU、NDW3-4000HU
3 20190909 XiaBiJian ng TangRui
Modification of Technical Parameters
WangCheng

NDW3-6300HU YinJiaCan
4 20190919 XiaBiJian TangRui
Modification of Technical Parameters WangCheng

Internal & confidential file Page 2 of 117


NDT2920213 Document Version: 3

Contents
Chapter 1 Product Overview ............................................................................................................ 4
Chapter 2 Technical Characteristics ...............................................................................................11
Chapter 3 Controller........................................................................................................................ 16
Chapter 4 Accessories ...................................................................................................................... 30
Chapter 5 Field of Application ........................................................................................................ 62
Chapter 6 Outline and Installation Dimensions ............................................................................ 67
Chapter 7 Electrical Wiring Diagram ............................................................................................ 93
Chapter 8 Ordering Type Selection Specification ....................................................................... 109

2019.11.27
试制

Internal & confidential file Page 3 of 117


NDT2920213 Document Version: 3

Chapter 1 Product Overview

1.1 NDW3 Product Series ............................................................................................................. 5


1.2 Rated Current of NDW3 Series Circuit Breaker ..................................................................... 5
1.3 Breaking Capacity and Short Time Withstand Current of NDW3 Series Circuit Breaker ..... 5
1.4 Structure Design ...................................................................................................................... 6
2019.11.27
试制
1.5 Product Features ...................................................................................................................... 7
1.6 Conforming Standards and Certification ................................................................................ 9
1.7 Product Model ....................................................................................................................... 10

Internal & confidential file Page 4 of 117


NDT2920213 Document Version: 3

Product Overview 1
1.1 NDW3 Product Series

NDW3-1600 NDW3-2500 NDW3-4000 NDW3-6300


1.2 Rated Current of NDW3 Series Circuit Breaker
Rated current (A)
200 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Shell frame level

NDW3-1600

NDW3-2500

NDW3-4000

NDW3-6300

1.3 Breaking Capacity and Short Time Withstand Current of NDW3 Series Circuit
Breaker
Breaking Capacity and Short Time Withstand Current of NDW3 Series Shell Frame (Icu=Ics=Icw)
(kA)
135
140

120
120

100 100
100
85 85 85 85 85

75 75
80
66 66 66 66
60 60
55 55
60 50 50

40

20 2019.11.27
试制

0
AC415V AC690V AC415V AC690V AC415V AC690V AC800V AC1000V AC1140V AC400V AC690V AC400V AC690V AC800V AC1140V AC415V AC690V AC415V AC690V AC800V AC1140V
S H HU S H HU S H HU
NDW3-1600 NDW3-2500 NDW3-4000 NDW3-6300

Note:1) S-Conventional breaking, H-High breaking, HU-High voltage breaking. NDW3-1600 only has one breaking capacity,
which is not distinguished;
2) Icu=Ics=Icw for NDW3-2500, 4000, 6300. For details of NDW3-1600 breaking indicators, see NDW3-1600 technical
parameter list.

Internal & confidential file Page 5 of 117


NDT2920213 Document Version: 3

1.4 Structure Design


■ Installation Structure

2019.11.27
试制

Fixed type Drawout type

■ Brief Description of Structure and Indications


1. Reset button 9. Nameplate
1
2 2. Specification sign 10. Counter (optional function)

3. Disconnected position key lock 11. “Connection”, “Test”,


3
4 (optional function) “Separation” position locking and

4. Nader sign unlocking device


5. Disconnection button 12. Rocker operating position
5
6. Closing button 13. “Connection”, “Test”,
6
7 7. Energy releasing and storing “Separation” position indicator
8
indication 14. Rocker and its storage position
9 8. Opening and closing indication
10 Note: 1 ~ 10 is fixed type, while 1 ~ 14 is drawout type.

14 13 12 11

■ Drawout Type Circuit Breaker Structure


Drawout type circuit breaker is composed of the circuit breaker and the drawer seat. The drawer seat has guide
rails on both sides. There's guide plate on the guide rail. The circuit breaker is placed on the left and right guide
plates. The drawout type circuit breaker connects to the main circuit by inserting the busbar on the circuit breaker
into the bridge contact on the drawer seat.

Internal & confidential file Page 6 of 117


NDT2920213 Document Version: 3

Circuit
Parti breaker body
Drawer
Rocker operating seat
Guid position

Guid Three-position
locking
and unlocking
button

Rocker and its


“Separation”, “Test”, “Connection” position storage position Drawout type circuit breaker
indication "separation" position lock

 Drawout type circuit breaker "separation" position lock:


When the drawout type circuit breaker is in the separation position, pull out the black lever below the drawer
to lock. Then the circuit breaker can only pull out the drawer seat, and cannot be shaken to the "test" or
"connection" position. Padlock should be prepared by users, with the specification of 40 mm or less.
 Drawout three-position lock:
On the drawer seat, there’s “connection”, “test” and “separation” position status, which is indicated through a
indicator.
When the handle shakes, the circuit breaker will be locked respectively in these three positions, and unlocked
only through the reset button (red).
1.5 Product Features
1.5.1 Efficient arc extinguishing and breaking
■ The design of the circuit breaker arc extinguishing chamber and contact system has a number of invention
patents. It adopts the principle of air-blast arc extinguishing, optimizes the arc extinguishing gate design, increases
the driving force of arc, and improves the breaking ability of the product. In addition, it also designs and optimizes
the time for acquiring signal and giving command by the controller, and can greatly shorten the time when there is a
large fault current.
■ Zero flashover.
1.5.2 High electrical life and short time tolerance ability
The body design adopts high strength reinforced moulded plastics, and has extremely high impact strength and
insulating properties. The design of the arcing contact structure improves the electric life of products; the greatly
optimized design of the contact system and operating mechanism realizes compensation to the contact pressure, and
improves the product reliability and short time tolerance ability with more strength of the metal structure.
1.5.3 The controllers are of full range and versatile 2019.11.27
试制
■ NWK21/NWK31 type controller - Digital tube display, practical function and simplicity, which can adapt
to the low-temperature places with the optional voltage measurement function;
■ NWK22/NWK32 type controller - LCD display, multiple and diversified functions, with optional voltage
and harmonics measurement and protection functions. Applicable to high-end application places, and more
powerful if applied to intelligent system;

Internal & confidential file Page 7 of 117


NDT2920213 Document Version: 3

■ Measurement and protection: With current, voltage, frequency, phase sequence, power, power factor and
harmonics measurement and protection functions;
■ Current protection features: A variety of overload long-time delay protection, a variety of short circuit
short-time delay protection, short circuit transient protection, earthing protection, neutral line N-pole protection,
current unbalance protection, MCR making capacity protection;
■ Maintenance function: With fault record (8 times), historical current peak record, contact wear equivalent,
query of operation times, clock function, self-diagnostic function, test function and fault display function;
■ With a remote reset device,2019.11.27
realize remote recovery (optional accessories) after fault tripping of the
试制
controller.
1.5.4 Integrated communication network
The NWK22/NWK32 type controller can realize remote sensing, remote control, remote regulating and remote
communication - "four remotes" data transmission function through the communication interface (to be used with
the communication adapter and signal unit).
With the communication adapter, realize the conversion of DeviceNet and Profibus-DP protocols for data
transmission.
1.5.5 AC 1140V circuit breaker
The HU (AC1140V) type circuit breaker is selected, which can be used in the power distribution system in
special fields such as metallurgy, rail transportation, pipe gallery, energy saving and environmental protection.
1.5.6 Three-proofing circuit breaker
The TH (thermal-humidity) type circuit breaker can be selected to meet the three-proofing requirements,
namely, moisture-proofing, mould-proofing and salt spray-proofing, and complies with JB-T834 Technical
Requirements of Tropical Type Low-voltage Apparatus while having passed the following standard related tests:
■ Thermal-humidity test: GB/T 2423.4-2008 Environmental Testing for Electric and Electronic Products.
Part 2: Test Method Test Db: Alternating Thermal-humidity (12h + 12h Cycle);
■ Mould growth test: GB/T 2423.16-2008 Environmental Testing for Electric and Electronic Products.
Part 2: Test Method Test J and Guidelines: Mould;
■ Salt spray test: GBT 2423.18-2012 Environmental Testing for Electric and Electronic Products. Part 2:
Test Method Test Kb: Salt Spray;
■ Enclosure protection grade: GB/T 4208-2008 Enclosure Protection Grade (IP code).
1.5.7 Convenient installation
■ Upper and lower wiring of the main circuit is available;
■ Connection mode.
Wiring mode NDW3-1600 NDW3-2500 NDW3-4000 NDW3-6300

■ Horizontal wiring
Conventional √ √ √ √
■ Vertical wiring

■ Horizontal extended wiring


— √ √ √
■ Vertical extended wiring
Special
■ Mixed wiring (upper horizontal, lower vertical)
√ √ — √
■ Mixed wiring (upper vertical, lower horizontal)

Internal & confidential file Page 8 of 117


NDT2920213 Document Version: 3

■ Mixed extended wiring (upper horizontal, lower


vertical)
— √ — √
■ Mixed extended wiring (upper vertical, lower
horizontal)

Annotation:6300A of NDW3-6300 only have two wiring modes: vertical wiring、vertical extended wiring.
1.5.8 Multiple safety protection devices
It has drawout type circuit breaker door interlocking, drawout type three-position locking and unlocking device
and off-position key lock, connection terminal protective cover and other protection devices.
1.6 Conforming Standards and Certification
GB/T 2423.4-2008 Environmental Testing for Electric and Electronic Products - Part 2: Test Method - Test
Db: Thermal, Humidity, Cyclic;
GB/T 4207-2003 Methods for the Determination of the Proof and the Comparative Tracking Indices of
Solid Insulating Materials;
GB/T 14048.1-2012 Low-voltage Switchgear and Control Equipment - Part 1: General Rules (IEC
60947-1:2001, MOD);
GB/T 14048.2-2008 Low-voltage Switchgear and Control Equipment - Part 2: Low-voltage Circuit Breaker
(IEC 60947-2:2006, IDT);
GB/T 14048.5-2008 Low-voltage Switchgear and Control Equipment - Part 5-1: Control Circuit Electrical
Appliances and Switch Elements - Electromechanical Control Circuit Electrical
Appliances (IEC 60947-5-1:2003, MOD);
GB/T 14092.3-2009 Environmental Condition for Machinery Products - High Altitude;
GB/T 19608.3-2004 Classification of Special Environmental Condition - Part 3: Plateau;
GB/T 20645-2006 Specific Environmental Condition - Technical Requirements of Low-voltage
Apparatuses for Plateau;
GB/T 20626.3-2006 Specific Environmental Condition - Electric and Electronic Products for Plateau - Part
3: Protection Requirement of Thunder and Lightning, Pollution, Condensation;
NDW3 series of universal circuit breaker has obtained China Compulsory Certification (CCC) for products.

2019.11.27
试制

Internal & confidential file Page 9 of 117


NDT2920213 Document Version: 3

1.7 Product Model


Description of the certification model:

ND W 3 4000 S

Breaking type: S, H, HUNote1

Shell frame level


2019.11.27
试制
Design SN 3

Universal circuit breaker

“Nader” brand low-voltage apparatus

Note: 1. S-Conventional breaking, H-High breaking, HU-High voltage breaking. NDW3-1600 only has one breaking capacity, which is

not distinguished;
2. For details of the product ordering models and specifications, see Chapter 8.

Internal & confidential file Page 10 of 117


NDT2920213 Document Version: 3

Chapter 2 Technical Characteristics


2.1 NDW3-1600 Technical Parameter List ................................................................................. 12
2.2 NDW3-2500 Technical Parameter List ................................................................................. 13
2.3 NDW3-4000 Technical Parameter List ................................................................................. 14
2.4 NDW3-6300 Technical Parameter List ................................................................................. 15

2019.11.27
试制

Internal & confidential file Page 11 of 117


NDT2920213 Document Version: 3

Technical Characteristics 2
2.1 NDW3-1600 Technical Parameter List
Circuit breaker model NDW3-1600
Rated current In (+40℃) .................................................. (A) 200, 400, 630, 800, 1000, 1250, 1600
North pole rated current ................................................... 100%In
Rated working voltage Ue ................................................ (V) AC220/230/240, AC380/400/415, AC440/480, AC660/690
Rated frequency f ............................................................. (Hz) 50/60
Rated insulation voltage Ui .............................................. (V) 1000
Rated impulse withstand voltage Uimp ............................
2019.11.27 (kV) 12
试制
Number of poles ............................................................... pole 3, 4
Full break timeNote 1 .......................................................... (ms) <25
Closing timeNote 2 .............................................................. (ms) <60
AC220V/230V/240V
Rated limit short-circuit breaking 66
AC380V/400V/415V
capacity
AC440V/480V
Icu (effective value) (kA) 50
AC660V/690V
AC220V/230V/240V
Rated operating short-circuit breaking 55
AC380V/400V/415V
capacity
AC440V/480V
Ics (effective value) (kA) 42
AC660V/690V
AC220V/230V/240V
145
Rated short circuit making capacity AC380V/400V/415V
Icm (peak value) (kA) AC440V/480V
105
AC660V/690V
AC220V/230V/240V
50
Rated short-time withstand current AC380V/400V/415V
Icw (effective value) 1s (kA) AC440V/480V
42
AC660V/690V
AC220V/230V/240V
Electrical life (times) 15000 (200A~630A)、9000 (800A~1250A)、6500 (1600A)
AC380V/400V/415V
Operation frequency
Operating (20 times/h) AC440V/480V
15000 (200A~630A)、5000 (800A~1250A)、3000 (1600A)
performance AC660V/690V
Mechanical life (times) Maintenance-free 15000
Operation frequency
With maintenance 30000
(60 times/h)
Installation type Fixed type, drawout type
Horizontal wiring, vertical wiring, mixed wiring (upper horizontal and lower vertical),
Wiring method of the main circuit
mixed wiring (upper vertical and lower horizontal)
Boundary dimension: W×D×H (mm) Fixed type 3P 259×195×318
Fixed type 4P 329×195×318
Drawout type 3P 248×297×351.5
Drawout type 4P 318×297×351.5
Fixed type 3P 22 (200A~630A) 23 (800A~1600A)
Fixed type 4P 34 (200A~630A) 35 (800A~1600A)
Weight (kg)
Drawout type 3P 43 (200A~630A) 44 (800A~1600A)
Drawout type 4P 56 (200A~630A) 57 (800A~1600A)
Note: 1. Full break time: Interval from the beginning of the circuit breaker disconnection to the end of the arcing time (the same
below);
2. Closing time: Interval from the beginning of the circuit breaker closing to the end of the contact time for all pole contacts (the
same below).

Internal & confidential file Page 12 of 117


NDT2920213 Document Version: 3

2.2 NDW3-2500 Technical Parameter List


Circuit breaker model NDW3-2500
Rated current In (+40℃) ................................................. (A) 630, 800, 1000, 1250, 1600, 2000, 2500
North pole rated current ................................................... 100%In
AC220/230/240, AC380/400/415, AC440/480,
Rated working voltage Ue ......................................... (V)
AC660/690, AC800, AC1000, AC1140
Rated frequency f............................................................. (Hz) 50/60
Rated insulation voltage Ui ............................................. (V) 1140
Rated impulse withstand voltage Uimp ........................... (kV) 12
Number of poles .............................................................. pole 3, 4
Full break time ................................................................. (ms) <30
Closing time..................................................................... (ms) <70
Breaking type S H HU
AC220V~415V 66 85 -
Rated limit short-circuit breaking AC440V/480V/660V/690V 55 66 -
capacity AC800V - - 60
Icu (effective value) (kA) AC1000V - - 55
AC1140V - - 50
AC220V~415V 66 85 -
Rated operating short-circuit AC440V/480V/660V/690V 55 66 -
breaking capacity AC800V - - 60
Ics (effective value) (kA) AC1000V - - 55
AC1140V - - 50
AC220V~415V 145.2 187 -
AC440V/480V/660V/690V 121 145.2 -
Rated short circuit making capacity
AC800V - - 132
Icm (peak value) (kA)
AC1000V - - 121
AC1140V - - 110
AC220V~415V 66 85 -
AC440V/480V/660V/690V 55 66 -
Rated short-time withstand current
AC800V - - 60
Icw (effective value) 1s (kA)
AC1000V - - 55
AC1140V - - 50
AC220V~ 415V 15000 (630A~1250A)、11500 (1600A~2000A)、11000 (2500A)
Electrical life (times)
Oper AC440V/480V/660V/690V 12500 (630A~1250A)、10000 (1600A~2000A)、8000 (2500A)
Operation frequency (20
ating AC800V 5000(630A~2000A)、4500 (2500A)
times/h)
perfo AC1000V/1140V 3000(630A~2000A)、2000 (2500A)
rman Mechanical life (times) Maintenance-free 17000(3P) 15000(4P)
ce Operation frequency (60
With maintenance 30000
times/h)
Installation type Fixed type, drawout type
Wiring method of the main Horizontal wiring, vertical wiring, horizontal extended wiring, vertical extended wiring,
circuit Mixed wiring (upper horizontal and lower vertical), mixed wiring (upper vertical and lower horizontal)
Boundary dimension: W×D×H Fixed type 3P 368×309.5×394
(mm) Fixed type 4P 463×309.5×394
Drawout type 3P 375× 393×432
2019.11.27
试制
Drawout type 4P 470×393×432

Fixed type 3P 49.4 (630A~1250A) 50 (1600A~2500A)


Fixed type 4P 61.5 (630A~1250A) 62.3 (1600A~2500A)
Weight (kg)
Drawout type 3P 87.1 (630A~1250A) 87.4 (1600A~2500A)
Drawout type 4P 106.2 (630A~1250A) 106.7 (1600A~2500A)

Internal & confidential file Page 13 of 117


NDT2920213 Document Version: 3

2.3 NDW3-4000 Technical Parameter List


Circuit breaker model NDW3-4000
Rated current In (+40℃) ................................................ (A) 800, 1000, 1250, 1600, 2000, 2500, 3200, 4000
North pole rated current ................................................... 100%In
AC220/230/240、AC380/400、AC415、
Rated working voltage Ue ................................................ (V)
AC440/480、AC660/690、AC800、AC1000/1140
Rated frequency f ............................................................. (Hz) 50/60
Rated insulation voltage Ui .............................................. (V) 1140
Rated impulse withstand voltage Uimp ............................ (kV) 12
Number of poles ............................................................... pole 3, 4
2019.11.27
Full break time .................................................................
试制 (ms) <30
Closing time ..................................................................... (ms) <70
Breaking type S H HU
AC220V~ 400V 85 100 -
Rated limit short-circuit breaking AC415V、AC440V/480V
75 85 -
capacity AC660V/690V
Icu (effective value) (kA) AC800V - - 75
AC1000V/1140V - - 60
AC220V~ 400V 85 100 -
Rated operating short-circuit AC415V、AC440V/480V
75 85 -
breaking capacity AC660V/690V
Ics (effective value) kA AC800V - - 75
AC1000V/1140V - - 60
AC220V~ 400V 187 220 -
AC415V、AC440V/480V
Rated short circuit making capacity 165 187 -
Icm (peak value) (kA) AC660V/690V
AC800V - - 165
AC1000V/1140V - - 132
AC220V~ 400V 85 100 -
AC415V、AC440V/480V
Rated short-time withstand current 75 85 -
Icw (effective value) 1s (kA) AC660V/690V
AC800V - - 75
AC1000V/1140V - - 60
AC220V~400V 10000 (800A~1600A)、8000 (2000A, 2500A)、6000 (3200A, 4000A)
Electrical life (times) AC415V、AC440V/480V
10000 (800A~1600A)、6000 (2000A, 2500A)、3000 (3200A, 4000A)
Operation frequency AC660V/690V
(20 times/h) AC800V 2000(800A~1600A)、1000(2000A~4000A)
Operating
performance AC1000V/1140V 2000 (800A~1600A)、1000 (2000A, 2500A)、600 (3200A, 4000A)
Mechanical life Maintenance-free 12000(3P) 10000(4P)
(times)
Operation frequency With maintenance 15000
(60 times/h)
Installation type Fixed type, drawout type
Wiring method of the main circuit Horizontal wiring, vertical wiring, horizontal extended wiring, vertical extended wiring
Boundary dimension: W×D×H Fixed type 3P 428×300×392
(mm) Fixed type 4P 543×300×392
Drawout type 3P 435×401×432(800A~2500A) 435×395.5×432(3200A、4000A)
Drawout type 4P 550×401×432(800A~2500A) 550×395.5×432(3200A、4000A)
Fixed type 3P 59 (800A~2500A) 60 (3200A, 4000A)
Fixed type 4P 70 (800A~2500A) 71.5 (3200A, 4000A)
Weight (kg)
Drawout type 3P 97 (800A~2500A) 103 (3200A, 4000A)
Drawout type 4P 114 (800A~2500A) 120 (3200A, 4000A)

Internal & confidential file Page 14 of 117


NDT2920213 Document Version: 3

2.4 NDW3-6300 Technical Parameter List


Circuit breaker model NDW3-6300
Rated current In (+40℃).................................................. (A) 4000, 5000, 6300
North pole rated current ................................................... 100%In
AC220/230/240, AC380/400/415, AC440/480,
Rated working voltage Ue ............................................... (V)
AC660/690, AC800, AC1000/1140
Rated frequency f ............................................................. (Hz) 50/60
Rated insulation voltage Ui.............................................. (V) 1140
Rated impulse withstand voltage Uimp ........................... (kV) 12
Number of poles .............................................................. pole 3, 4
Full break time ................................................................. (ms) <30
Closing time..................................................................... (ms) <70
Breaking type S H HU
AC220V~415V 120 135 -
Rated limit short-circuit breaking
AC440V/480V/660V/690V 85 100 -
capacity
Icu (effective value) (kA) AC800V - - 85
AC1000V/1140V - - 66
AC220V~415V 120 135 -
Rated operating short-circuit breaking
AC440V/480V/660V/690V 85 100 -
capacity
Ics (effective value) (kA) AC800V - - 85
AC1000V/1140V - - 66
AC220V~415V 264 297 -
Rated short circuit making capacity AC440V/480V/660V/690V 187 220 -
Icm (peak value) (kA) AC800V - - 187
AC1000V/1140V - - 145.2
AC220V~415V 120 135 -
Rated short-time withstand current AC440V/480V/660V/690V 85 100 -
Icw (effective value) 1s (kA) AC800V - - 85
AC1000V/1140V - - 66
AC220V~415V 6000 (4000A)、4000 (5000A)、2000 (6300A)
Electrical life (times)
AC440V/480V/660V/690V 3500 (4000A)、2500 (5000A)、1500 (6300A)
Operation frequency
(20 times/h) AC800V 3000(4000A)、1500(5000A)、1000(6300A)
Operating
performance AC1000V/1140V 2000 (In=4000A)、1000 (In=5000A)、500 (In=6300A)
Mechanical life (times) Maintenance-free 7000(3P) 6500(4P)
Operation frequency
With maintenance 13000
(60 times/h)
Installation type Fixed type, drawout type
Horizontal wiring, vertical wiring, horizontal extended wiring, vertical extended wiring,
Mixed wiring (upper horizontal and lower vertical), mixed wiring (upper vertical and
Wiring method of the main circuit lower horizontal),
Mixed extended wiring (upper horizontal and lower vertical), mixed extended wiring
(upper vertical and lower horizontal)
Boundary dimension: W×D×H (mm) Fixed type 3P 803×300×392
Fixed type 4P 1033×300×392
2019.11.27
Drawout type 3P 试制
809× 399×475
Drawout type 4P 1039×399×475
Fixed type 3P 125 (4000A, 5000A) 127 (6300A)
Fixed type 4P 167 (4000A, 5000A) 170 (6300A)
Weight (kg)
Drawout type 3P 193 (4000A, 5000A) 195 (6300A)
Drawout type 4P 257 (4000A, 5000A) 260 (6300A)

Internal & confidential file Page 15 of 117


NDT2920213 Document Version: 3

Chapter 3 Controller
3.1 Controller Types .................................................................................................................... 17
3.2 Controller Functions ............................................................................................................. 18
3.3 Controller Panel Description ................................................................................................. 19
3.4 Setting Values and Protective Features of Controller ........................................................... 21
3.5 Working Power Supply of Controller ................................................................................... 28
2019.11.27
3.6 Introduction of Controller 试制
Functions .................................................................................... 29
3.7 Protection Characteristic Curve ............................................................................................ 29

Internal & confidential file Page 16 of 117


NDT2920213 Document Version: 3

Controller 3
Controller is one of the main components of the circuit breaker, which can provide the function of protecting
the overload, short circuit, grounding, current unbalance, overvoltage, undervoltage, voltage unbalance,
overfrequency, underfrequency, reverse power and other failures, and realize reasonable operation of the power grid
through the load monitoring, required value protection, regional interlocking and other functions. Controller has the
function of measuring the current, voltage, power, frequency, electric energy, required value, harmonic and other
power grid parameters; and the function of recording the fault, alarm, operation, maximum historical current,
contact wear and other operating maintenance parameters. When the power network is carrying on communication
network, the controller can realize the remote sensing, remote communication, remote control and remote regulating
at the remote terminal of the electric power automation network.
3.1 Controller Types
NWK22 /NWK32

Model NWK21/NWK31 NWK21(V)/NWK31(V) NWK22(V)/NWK32(V)


NWK22(P)/NWK32(P)

Controller
Controller Controller

Fault Alarm Fault Alarm

Controller Communication Normal Fault/alarm


Reset

Pictures

Setup Query Test Storage Setup Query Test Storage

Up Up

Function Function
Select
Exit
Select
Exit

Measurement Setting Protection Information

Down Down 2019.11.27


Up Down Exit Select
试制

NWK31 and NWK32 are applied to NDW3-1600,NWK21 and NWK22 are applied to NDW3-2500、NDW3-4000
and NDW3-6300

Internal & confidential file Page 17 of 117


NDT2920213 Document Version: 3

3.2 Controller Functions


NWK21 NWK21/V NWK22 NWK22/V NWK22/P
Functional items
NWK31 NWK31/V NWK32 NWK32/V NWK32/P
Digital tube numbers and symbols display √ √ — — —
Display
LCD panel symbols and graphics display in
interface — — √ √ √
Chinese
Overload long-time delay protection √ √ √ √ √
Overload thermal memory √ √ √ √ √
Overload pre-alarm/alarm output √/▲ √/▲ √/▲ √/▲ √/▲
Short circuit short-time delay protection √ √ √ √ √
Short-time delay thermal memory √ √ √ √ √
Short circuit instantaneous protection
2019.11.27 √ √ √ √ √
Ground protection (differential
试制type) √ √ √ √ √
Grounding alarm/alarm output √/▲ √/▲ √/▲ √/▲ √/▲
Current leakage protection/alarm/alarm output — — √/√/▲ √/√/▲ √/√/▲
Neutral wire protection √ √ √ √ √
Protection Current unbalance protection/alarm/alarm output √/—/— √/—/— √/√/▲ √/√/▲ √/√/▲
function MCR √ √ √ √ √
Load monitoring/alarm/alarm output ▲ ▲ √ √ √
Undervoltage protection/alarm/alarm output — — — √/√/▲ √/√/▲
Overvoltage protection/alarm/alarm output — — — √/√/▲ √/√/▲
Voltage unbalance protection/alarm/alarm output — — — √/√/▲ √/√/▲
Phase sequence protection/alarm/alarm output — — — √/√/▲ √/√/▲
Underfrequency protection/alarm/alarm output — — — √/√/▲ √/√/▲
Overfrequency protection/alarm/alarm output — — — √/√/▲ √/√/▲
Current required value protection/alarm/alarm
— — — √/√/▲ √/√/▲
output
Reverse power protection/alarm/alarm output — — — — √/√/▲
Current measurement (phase pole, N-pole,
√ √ √ √ √
grounding)
Voltage (phase voltage, circuit voltage, voltage
— √ — √ √
unbalance rate)
Phase sequence detection — — — √ √
Frequency measurement — √ — √ √
Required value measurement (current) — — — √ √
Measuring
Required value measurement (power) — — — — √
function
Power measurement (active power, reactive
— √/—/— — — √
power, apparent power)
Power factor measurement — √ — — √
Electric energy measurement (active electric
energy, reactive electric energy, apparent electric — — — — √
energy)
Harmonics measurement — — — — √
LED fault status indication √ √ √ √ √
Fault record (8 times) and query √ √ √ √ √
Historic peak current record — — √ √ √
Alarm history query — — √ √ √
Maintenance Fault tripping signal output √ √ √ √ √
function Self-diagnostic function √ √ √ √ √
Simulating tripping test function √ √ √ √ √
Contact wear equivalent (alarm) query ▲ ▲ √ √ √
Query of number of operations ▲ ▲ √ √ √
Clock function — — √ √ √
DC controllers (DC220V, DC110V) ▲ ▲ ▲ ▲ ▲
Remote reset of controller ▲ ▲ ▲ ▲ ▲
Others
Signal element ▲ ▲ ▲ ▲ ▲
Communication — — ▲ ▲ ▲
SMS function — — ▲ ▲ ▲
Note: 1. “√” represents this function is available, “▲” represents optional functions for users, and “—” represents this function is not
available
2. For NWK21/V, NWK31/V, NWK22/V, NWK32/V, NWK22/P and NWK32/P controllers, when the rated voltage of main
circuit is over AC800V, voltage module P2 must be chosen;
3. "V" and "P" functions are addtional types of normal controller.

Internal & confidential file Page 18 of 117


NDT2920213 Document Version: 3

3.3 Controller Panel Description


■ NWK21/NWK31 Type Controller

Panel Display of NWK21/NWK31 Type Controller


1. Rated current sign

2. N-phase and A, B, C phases voltage indicators in order


Controller
3. Three-phase voltage and frequency value display screen

4. Three-phase current, N-phase current indicators


Fault Alarm
5. Three-phase electric current display screen

6. Load monitoring signals 1 and 2 operation indicators


7. Long time delay and short time delay protection operation

indicators
8. Setup, query indicators

9. 5 operation buttons
10. Unused temporarily

11. Test interface


12. Test, storage indicators

13. Instantaneous, N-phase current or self-diagnosis operation


indicators

14. Unbalance, ground current protection operation indicators


15. %, current, time and I2t (inverse time limit) indicators in order

16. Frequency, power, voltage and power factor indicators in


Setup Query Test Storage
Up order

17. Communication Rx, Tx, fault and alarm indicators in order


Select

Function
Exit

Down

Note: 1. The double-point underline frame displays a controller with the voltage display function, while this display isn’t available
without the optional voltage function;
2019.11.27
2. Tx,Rx is only used for internal testing in the company. 试制

Internal & confidential file Page 19 of 117


NDT2920213 Document Version: 3

■ NWK22/NWK32 Type Controller

Panel Display of NWK22/ NWK32 Type Controller


1. LCD interface display
2. “Normal” indicator (LED): The green LED always flashes as
Controller long as the controller is turned on and works properly.
3. ‘Communication’ indicator (LED): It flashes during the
communication connection.
2019.11.27 4. ‘Fault/Alarm’ indicator (LED): During normal operation, LED
试制
is not on; in case of fault tripping, the red LED flashes quickly; in
case of an alarm, the red LED is always on.
5. Protection indicator (LED): The corresponding LED flashes
respectively from left to right to indicate the fault type in case of
fault disconnection; for the protection parameter settings, the
LED is always on to indicate the currently selected items.
6. “Setting” button: Switch to the topic menu of parameter
settings.
7. “Measurement” button: Switch to the default topic menu of
measurement.
8.“Up” button: Move the menu content up on the current option,
Communication Normal Fault/alarm
or incrementally change the parameters.
Reset
9.“Down” button: Move the menu content down on the current
option, or decrementally change the parameters.
10.“Exit” button: Exit the current option to the previous menu, or
cancel the current parameter settings
11. TEST test interface: Plugged into the portable power box or
test unit.
12. “Select” button: Go to the next menu pointed by the specified
item,
Measurement Setting Protection Information or select and store parameters.
13. “Information function” button: Switch to the topic menu of
history and maintenance.
Up Down Exit Select
14. “Protection function” button: Switch to the topic menu of
protection parameter settings.
15. Fault and alarm reset buttons.
16. Rated current sign.

Internal & confidential file Page 20 of 117


NDT2920213 Document Version: 3

3.4 Setting Values and Protective Features of Controller


Setting Values and Protective Features of Controller
Overload long time-delay protection NWK21/NWK31 &NWK22/NWK32
Note
(0.4~1.0 or 1.25 ) In or OFF (OFF-Function off)
Current setting value IR
Note: 1.0In in case of the power distribution protection; 1.25In in case of the generation protection.
1) Standard power distribution protection I2t: t= 2.25 TR / N2 (factory default)
Standard generator protection I t (F): t= 2.25 TR / N2
2

2) Express inverse time limit (power distribution protection) EI(G): t= 1.25 TR /(N2-1)
3) Express inverse time limit (motor protection) EI(M): t= 1.3974 TR ×ln[N2/(N2-1.15)]
4 types of protection curve 4) High-voltage fuse compatible HV: t = 4.0625 TR /(N4-1)
N= I/ Ir I—Fault current t—Long time-delay action time Ir—Long time-delay setting
current TR—Long time-delay setting time
Description: NWK21/NWK31 controller has only standard power distribution protection I2t;
NWK22/NWK32 controller provides 4 types of protection curves.
1) Standard power distribution NWK21/NWK31: 15s, 30s, 60s, 120s, 240s, 480s
protection I2t
Time setting valve tR (1.5 Ir) NWK22/NWK32: 15s, 30s, 60s, 120s, 240s, 360s, 480s, 600s, 720s, 840s, 960s
1.5Ir 15 30 60 120 240 360 480 600 720 840 960
Tripping time t
(s) 2.0 Ir 8.44 16.88 33.75 67.5 135 202.5 270 337.5 405 472.5 540
(Accuracy of 6.0 Ir 0.94 1.88 3.75 7.5 15 22.5 30 37.5 45 52.5 60
±10%)
7.2 Ir 0.65 1.30 2.60 5.21 10.4 15.6 20.8 26 31.3 36.5 41.7
NWK22/NWK32: See the table below for the overload long-time delay protection action delay
2)~4) Protection curve type
time of C1~C16
Current (I/Ir) Tripping time
1.05 > 2h Inaction
Protective features (accuracy of 1.3 (power distribution
< 1h Action
±10%) protection)
1.2 (generator protection) < 1h Action
The action time is calculated according to four types of
≥1.2 Ir
protection formula or curve queried
NWK21/NWK31: 30min (ON) or OFF
NWK22/NWK32: Instantaneous, 10min, 20 min, 30 min, 45 min, 1h, 2h, 3h or OFF
Thermal memory time Description: 1. The auxiliary power supply of controller features the thermal memory function;
turn off the auxiliary power supply to clear the thermal memory;
2. Setting OFF, it is possible to turn off the thermal memory function.
Overload pre-alarm NWK21/NWK31 &NWK22/NWK32

Current setting value IP OFF+(0.75~1.05) Ir


The signal output is required to add a signal unit.
Overload pre-alarm output
Without signal output, observe the controller display screen or read from the display indicator.
Short circuit short-time delay protection NWK21/NWK31 &NWK22/NWK32
Current setting value Isd
(1.5~15) Ir or OFF (OFF-Function off)
(accuracy of ±10%)
tsd1 inverse
Time setting
time limit NWK21/NWK31: 0.1, 0.2, 0.3, 0.4
value Tsd
tsd2 definite NWK22/NWK32: 0.1~1.0
(s)
time limit
Current
Tripping time
(I/Isd)
2019.11.27
≤0.9 Inaction 试制
Protective features (accuracy of NWK21/NWK31: Isd≤I≤8Ir: t=(8Ir)2×Tsd1/I2 inverse time-limit
±10%) characteristic
I2t-ON
≥ 1.1 NWK22/NWK32: t =(1.5/N)2×Tsd1/10 inverse time-limit
characteristic
I2t-OFF I>8 Ir (or I≥Isd): 0.1s, 0.2s, 0.3s, 0.4s definite time limit
NWK21/NWK31: 15min ON or OFF (OFF-Function off)
Thermal memory time
NWK22/NWK32: Instantaneous, 10min, 20 min, 30 min, 45min, 1h, 2h, 3h or OFF

Internal & confidential file Page 21 of 117


NDT2920213 Document Version: 3

Continued: Setting Values and Protective Features of Controller


Short-circuit instantaneous protection NWK21/NWK31 &NWK22/NWK32
Current setting value Ii
(accuracy of ±10%) (1.0~20) In or OFF (OFF-Function off)
Current (I/Ii) Tripping time
Protective features (accuracy of ≤0.85 Inaction
±10%) ≥ 1.15 <40ms Action
I>IMCR Break action time<30ms
MCR protection NWK21/NWK31 &NWK22/NWK32
Current setting value IMCR (1.0~20) In (factory default as 10In)
2019.11.27
试制
Current (I/I MCR) Tripping time
Protective features (accuracy of
≤0.8 Inaction
±10%)
≥ 1.1 <100ms Action
Ground protection/alarm NWK21/NWK31
Protection type Differential type (T), ground current type (W), with the latter as the optional function
Current setting value Ig (0.2~1.0) In or OFF (OFF-Function off)
Time setting value Tg (s) 0.1~0.4 definite time limit

Protective features (accuracy of Current (I/Ig) Tripping time


±10%) ≤0.8 Inaction (no alarm)
Inherent absolute error: ±40ms≥ 1.0 For action (or alarm), see the time setting value
The signal output is required to add a signal unit.
Grounding alarm output
Without signal output, observe the controller display screen or read from the display indicator.
Ground protection/alarm NWK22/NWK32
Current setting value Igh (0.2~1.0) In or OFF (OFF-Function off)
Action /alarm time setting
0.1~1.0
value Tg (s)
Alarm return current setting
(0.2~1.0)×In
value Only when the execution mode is “alarm”, this setting
Alarm return time setting value is available
0.1~1.0
(s)
Current (I/Ig) Tripping time
Protective/alarm features
≤0.9 Inaction (no alarm)
(accuracy of ±10%)
Inherent absolute error: ±40ms For action (or alarm), see the action time as the
≥ 1.0
inverse or definite time limitNote
Returnable features (accuracy of ≥ 1.0 Non-return
±10%)
Inherent absolute error: ±40ms ≤0.9 For alarm, see the alarm return time setting value
The signal output is required to add a signal unit; set one DO of the signal unit as “Grounding
Grounding alarm output alarm”.
Without signal output, observe the controller display screen or read from the display indicator.
Note: For details of the reverse and definite time limit, see the User Manual of NWK22 and NWK32 Controller, with the
definite time limit as Tg
Neutral line protection NWK21/NWK31 &NWK22/NWK32
NWK21/NWK31 controller: 50%In, 100%In or OFF;
Neutral wire protection setting
NWK21/NWK31 controller: 50%In, 100%In, 160%In, 200%In or OFF.
value
OFF— Turn off N-phase protection function
Same-phase pole overload long time-delay protection, short-circuit short time-delay protection,
Protective features
short-circuit instantaneous protection, ground protection

Internal & confidential file Page 22 of 117


NDT2920213 Document Version: 3

Continued: Setting Values and Protective Features of Controller


Current leakage protection/alarm (namely the residual current protection, applicable for the shell frame level 2500A and below)
NWK22/NWK32
Current setting value I△n (A) 0.5~30.0 or OFF (OFF-Function off)
Action delay time T△n (s) Instantaneous, 0.06, 0.08, 0.17, 0.25, 0.33, 0.42, 0.5, 0.58, 0.67, 0.75 0.83
Alarm delay time T△nb (s) 0.1~1.0
Alarm return current setting value 0.5~30.0
(A)
Alarm return delay time (s) 0.1~1.0
Current (I/I△n) Tripping time
Protective action/alarm features
(accuracy of ±10%) <0.8 Inaction (no alarm)
Inherent absolute error: ±40ms ≥ 1.0 Action (see the data below) or alarm (see the alarm delay
time)
Alarm return features (accuracy of ≥ 1.0 Non-return
±10%)
≤0.9 For alarm, see the alarm return delay time
Inherent absolute error: ±40ms
Instan
Setting
taneo 0.06 0.08 0.17 0.25 0.33 0.42 0.5 0.58 0.67 0.75 0.83
time
us
Tripping time t
(s) I△n 0.36 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 0.36
(Accuracy of 2I△n 0.18 0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5 0.04
±10%)
5I△n
0.072 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0.04
10I△n
The signal output is required to add a signal unit; set one DO of the signal unit as
“Current leakage alarm”.
Current leakage alarm output
Without signal output, observe the controller display screen or read from the display
indicator.
Current unbalance protection/alarm NWK21/NWK31 &NWK22/NWK32
Current unbalance setting (40%~100%)+OFF (OFF-Function off)
NWK21/NWK31 value δ
Action delay time t δ (s) 0.1~1.0
Protection/alarm start
5%~60%
setting value
Action/alarm delay time
0.1~40.0
NWK22/NWK32 (s)
Alarm action return setting Only when the execution mode
5%~start value
value is "alarm", this setting is
Alarm return delay time (s) 10~200 available
Actual current unbalance
Tripping time
Protective features (accuracy of rate/setting value
±10%) ≤0.9 Inaction (no alarm)
Inherent absolute error: ±40ms Acts (or gives an alarm) according to the set delay
≥ 1.1
time
Actual current unbalance
Protective return features (accuracy Tripping time
rate/setting value
of ±10%)
≥ 1.1 Non-return
Inherent absolute error: ±40ms
≤0.9 Returns according to the alarm return delay time
The signal output is required to add a signal unit; set one DO of the signal unit as “I
Current unbalance protection alarm unbalanced alarm”.
DO output Without signal output, observe the controller display screen or read from the display
2019.11.27
indicator.
试制
Execution mode Alarm/tripping/close

Internal & confidential file Page 23 of 117


NDT2920213 Document Version: 3

Continued: Setting Values and Protective Features of Controller


Required current value protection/alarm NWK22/NWK32
Protection/alarm start setting value (0.2~1.0) In
Protection action delay time setting value
15~1500
(s)
Alarm action return setting value 0.2In~start value
Alarm return delay time (s) 15~1500
Multiple of current (I/setting
Tripping time
value)
Protective features (accuracy of ±10%)
≤0.9 Inaction (no alarm)
Inherent absolute error: ±40ms
Acts (or gives an alarm) according to the
≥ 1.1
2019.11.27 set delay time
试制
Multiple of current (I/setting
Tripping time
Return features (accuracy of ±10%) value)
Inherent absolute error: ±40ms ≥ 1.1 Non-return
≤0.9 Returns according to the set delay time
The signal output is required to add a signal unit; set one DO of the signal unit as
Required current value protection alarm “Required value fault”.
DO output Without signal output, observe the controller display screen or read from the display
indicator.
Protection execution mode Alarm/tripping/close
Load monitoring function NWK21/NWK31 &NWK22/NWK32
Operation mode Current setting Time setting
Ic 1 Tc1
Current way 1 15s, 30s, 60s,
Ic 2 Tc2
NWK21/NWK31 (0.2~1.0) In+OFF 120s, 240s, 480s
Ic 1 Tc1
Current way 2
Ic 2 Tc2 60s, 120s, 240, 480s
Thermal memory 15min (ON), OFF
Operation mode Current/power setting Time setting
Un Current way 1 0.2~1.0Ir 20~80%TR
loa Current way 2
d Power way 1
200kW~10000kW 10s~3600s
NWK22/NWK32 Ⅰ Power way 2
Un Current way 1 0.2~1.0Ir 20~80%TR
loa Current way 2 0.2Ir~unload Ⅰ 10s~600s
d Power way 1 200kW~10000kW
Ⅱ Power way 2 10s~3600s
100kW~unload Ⅰ
The signal output is required to add a signal unit; set one DO of the signal unit as “load
monitoring 1”, another as “load monitoring 2”.
Load monitoring alarm DO output
Without signal output, observe the controller display screen or read from the display
indicator.
Undervoltage protection/alarm NWK22/NWK32
Protection/alarm start setting value V 100~return value
Protection action delay time setting value
0.2~6
(s)
Alarm action return setting value V Start value~600
Alarm return delay time (s) 0.2~60

Internal & confidential file Page 24 of 117


NDT2920213 Document Version: 3

Continued: Setting Values and Protective Features of Controller


Undervoltage protection/alarm NWK22/NWK32
Undervoltage protection action /alarm Umin/action setting value Tripping time
features >1.1 Inaction (no alarm)
(Accuracy of ±10%) inherent absolute Acts (or gives an alarm) according to the set
error: ±40 ms ≤0.9
delay time
Alarm return features of undervoltage Umin/return setting value Tripping time
protection <0.9 Non-return
(Accuracy of ±10%) inherent absolute
error: ±40 ms ≥ 1.1 Returns according to the set delay time
The signal output is required to add a signal unit; set one DO of the signal unit as
Undervoltage protection alarm DO “Undervoltage fault”.
output Without signal output, observe the controller display screen or read from the display
indicator.
Execution mode Alarm/tripping/close
Overvoltage protection/alarm NWK22/NWK32
Protection/alarm start setting value V Return value~1200
Protection action delay time setting value
0.2~60
(s)
Alarm return setting value V 100~start value
Alarm return delay time (s) 0.2~60
Overvoltage protection/alarm action Umax/action setting value Tripping time
features ≤0.9 Inaction (no alarm)
(Accuracy of ±10%) Acts (or gives an alarm) according to the set
Inherent absolute error: ±40ms ≥ 1.1
delay time
Overvoltage alarm return features Umax/return setting value Tripping time
(Accuracy of ±10%) inherent absolute ≥ 1.1 Non-return
error: ±40 ms ≤0.9 Returns according to the set delay time
The signal output is required to add a signal unit; set one DO of the signal unit as
Overvoltage protection alarm DO “Overvoltage fault”.
output Without signal output, observe the controller display screen or read from the display
indicator.
Protection execution mode Alarm/tripping/close
Voltage unbalance protection/alarm NWK22/NWK32
Protection/alarm start setting value 2%~30%
Protection action delay time setting
0.2~60
value (s)
Protection action return setting value 2%~start value
Protection return delay time (s) 0.2~60
Actual voltage unbalance
Action features of voltage unbalance Tripping time
rate/setting value
protection/alarm ≤0.9 Inaction (no alarm)
(Accuracy of ±10%) inherent absolute
error: ±40 ms Acts (or gives an alarm) according to the set
≥ 1.1
delay time
Alarm action features of voltage Actual voltage unbalance
Tripping time
unbalance protection rate/setting value
(Accuracy of ±10%) inherent absolute ≥ 1.1 Non-return
error: ±40 ms ≤0.9 2019.11.27
Returns according to the set delay time
试制
The signal output is required to add a signal unit; set one DO of the signal unit as “U
Voltage unbalance protection alarm DO unbalanced alarm” output.
output Without signal output, observe the controller display screen or read from the display
indicator.
Execution mode Alarm/tripping/close

Internal & confidential file Page 25 of 117


NDT2920213 Document Version: 3

Continued: Setting Values and Protective Features of Controller


Underfrequency, overfrequency protection/alarm NWK22/NWK32
Protection/alarm start
45.0~return value
setting value (Hz)
Action delay time setting
0.2~5.0
Underfre value (s)
quency Alarm action return setting
Start value~65.0
value (Hz)
Alarm return delay time
0.2~36.0 (the return value must be greater than or equal to the start value)
(s)
Protection/alarm start
Return value~65.0
setting (Hz) 2019.11.27
Action delay time setting 试制
0.2~5.0
Overfreq value (s)
uency Alarm return setting value
45.0~start value
(Hz)
Alarm return delay time
0.2~36.0 (the return value must be less than or equal to the start value)
(s)
The signal output is required to add a signal unit; set one DO of the signal unit as
Underfrequency, overfrequency “Underfrequency fault” or “Overfrequency fault” output.
protection alarm DO output Without signal output, observe the controller display screen or read from the display
indicator.
Execution mode Alarm/tripping/close
Reverse power protection/alarm NWK22/NWK32
Protection/alarm start setting value (kW) 5~500
Protection action delay time setting value
0.2~20
(s)
Alarm return setting value (kW) 5~start value
Alarm return delay time (s) 1.0~360 (the return value must be greater than or equal to the start value)
Reverse power value/Setting
Reverse power protection Tripping time
value
action/alarm features
≤0.9 Inaction (no alarm)
(Accuracy of ±10%) inherent absolute
Acts (or gives an alarm) according to the set
error: ±40 ms ≥ 1.1
delay time
Reverse power protection/alarm return Reverse power value/Setting value Tripping time
features ≥ 1.1 Non-return
(Accuracy of ±10%) inherent absolute
≤0.9 Returns according to the set delay time
error: ±40 ms
The signal output is required to add a signal unit; set one DO of the signal unit as
Reverse power protection alarm DO “Reverse power fault” output.
output Without signal output, observe the controller display screen or read from the display
indicator.
Execution mode Alarm/tripping/close
Phase sequence protection/alarm NWK22/NWK32
Setting range of action phase sequence Δφ: A, B, C / Δφ: A, C, B
The signal output is required to add a signal unit; set one DO of the signal unit as
Phase sequence protection alarm DO “Phase sequence fault”.
output Without signal output, observe the controller display screen or read from the display
indicator.
Execution mode Alarm/tripping/close
Signal unit NWK21/NWK31 &NWK22/NWK32
Optional Load
DO output General Functions
Monitoring Functions
DO1 Overload pre-alarm output Load monitoring 1
DO2 Grounding pre-alarm output Load monitoring 1
NWK21/NWK31
DO3 Fault tripping output Fault tripping output
Short circuit
Short circuit instantaneous
DO4 instantaneous action
action output
output

Internal & confidential file Page 26 of 117


NDT2920213 Document Version: 3

Continued: Setting Values and Protective Features of Controller


Signal unit NWK21/NWK31 &NWK22/NWK32
Type of signal
Rated current Field of Application
unit
S1 4DO (4 output contacts) Without regional interlocking
3DO (3 output contacts) 1DI (1 input Regional interlocking between air circuit
S2
contact) breakers
2DO (2 output contacts) 2DI (2 input Regional interlocking between air circuit
S3
contacts) breakers
Function Alarm, tripping, regional interlocking, general, grounding interlocking, short circuit
D setting interlocking
I Input form Normally opened Normally closed
Function
See the table below, “Parameter Settings of Switch Output (DO)”
setting
D Execution Normally opened Normally closed Normally opened Normally closed
O mode level level impulse impulse
Impulse time None 1~360s
NWK22/NWK32 Parameter Settings of Switch Output (DO)
Self-diagnosis
General Alarm Fault tripping Load monitoring 1
alarm
Short time delay
Load monitoring 2 Overload pre-alarm Overload fault Transient fault
fault
Grounding/current Grounding/ current Current unbalance
Middle-phase fault Undervoltage fault
leakage fault leakage alarm fault
Voltage unbalance Underfrequency Required value
Overvoltage fault Overfrequency fault
fault fault fault
Regional
Reverse power fault On Off Phase order fault
interlocking
Grounding Short circuit A-phase required B-phase required
MCR fault
interlocking interlocking value fault value fault
C-phase required N-phase required Required value Alarm of operation
Contact wear alarm
value fault value fault out-of-limit times
Remote reset — — — —
See the table below for the overload long-time delay protection action delay setting time and the corresponding
multiple of current time
Curve Fault Delay time (s)
type current C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 C13 C14 C15 C16
1.5×IR 15.00 30.00 60.00 120.00 240.00 360.00 480.00 600.00 720.00 840.00 960.00
2×IR 8.44 16.88 33.75 67.50 135.00 202.0 270.00 337.50 405.00 472.50 540.00
I2t
6×IR 0.94 1.88 3.75 7.50 15.00 22.50 30.00 37.50 45.00 52.50 60.00
7.2×IR 0.65 1.30 2.60 5.21 10.42 15.63 20.83 26.04 31.25 36.46 41.67
1.5×IR 8.00 12.80 19.20 32.00 48.00 64.00 80.00 108.0 144.00 224.00 320.00 480.00 640.00 800.00 960.00 1120.00
2×IR 3.33 5.33 8.00 13.33 20.00 26.67 33.33 45.00 60.00 93.33 133.33 200.0 266.67 333.33 400.00 466.67
EI (G)
6×IR 0.29 0.46 0.69 1.14 1.71 2.29 2.86 3.86 5.14 8.00 11.43 17.14 22.86 28.57 34.29 40.00
7.2×IR 0.20 0.31 0.47 0.79 1.18 1.57 1.97 2.26 3.54 5.51 7.87 11.80 15.74 19.67 23.60 27.54
1.5×IR 6.22 9.96 14.90 24.90 37.30 49.80 62.20 84.00 112.00 174.00 249.00 373.00 498.00 622.00 747.00 871.00
2×IR 2.95 4.72 7.06 11.79 17.67 23.59 29.46 39.79 53.05 82.42 117.95 176.68 235.89 294.63 353.84 412.58
EI (M)
6×IR 0.28 0.45 0.68 1.13 1.69 2.26 2.82 3.81 5.08 7.89 11.30 16.92 22.59 28.22 33.89 39.52
7.2×IR 0.19 0.31 0.47 0.78 1.17 1.56 1.95 2.63 3.51 5.45 7.81 11.69 15.61 19.50 23.42 27.30
1.5×IR 2.46 3.94 5.90 9.85 14.80 19.70 24.60 33.20 44.30 68.90 98.502019.11.27
147.00 197.00 246.00 295.00 344.00
2×IR 0.67 1.07 1.60 2.67 4.01 5.34 6.66 8.99 12.00 18.66 试制
26.68 39.81 53.35 66.63 79.90 93.17
HV
6×IR 0.01 0.01 0.02 0.03 0.05 0.06 0.08 0.10 0.14 0.22 0.31 0.46 0.62 0.77 0.93 1.08
7.2×IR 0.00 0.01 0.01 0.01 0.02 0.03 0.04 0.05 0.07 0.10 0.15 0.22 0.30 0.37 0.45 0.52

Internal & confidential file Page 27 of 117


NDT2920213 Document Version: 3

Controller factory setting


Protective features Setting current Setting time Remarks

Overload long-time delay protection 1.0In 60s Thermal memory ON

Short circuit short-time delay protection 8IR 0.2s Definite time limit, I2t-ON

Short circuit instantaneous 10In - -

Neutral wire protection 100%In - -

3P products usually close this fucti


2019.11.27 on as a default, and 4P open it as a
试制
Ground protection 0.5In 0.2s default; Clients of 3P products ca
n open the function according to t
heir requirements
Current unbalance protection OFF - Users can open it as needed

3.5 Working Power Supply of Controller


■ The working power supply of controller is provided by the transformer and auxiliary power supply. To
ensure reliable operation and breaking of small current in case of failure, please adopt the power supply mode of 1)
and 2), with the mode as follows:
1) To be powered by the power supply CT
Normal operating conditions of the controller: the primary current single-phase and three-phase are no less than
0.4In and 0.2In respectively. When the rated current is ≤400A, the primary current single-phase and three-phase of
the main circuit are no less than 1.0In and 0.6In respectively. Otherwise, it must be powered by the auxiliary power
supply.
2) To be powered by the auxiliary power supply
Normal operating conditions of the controller: (85%~110%) Us.
AC power voltage (50/60Hz): AC230V, AC400V, with an allowable error of ±15%
DC power voltage: DC220V, DC110V, DC24V, with an allowable error of ±5%
NDW3-1600 frame controller input voltage of port 1 and 2 can only be DC24V, when clients require
AC230V/AC400V/DC110V/DC220V, we must switch it to DC24V by external DC power source module, and it has
been installed in factory;2500 frame and above controllers have been transformed internally, and therefore there is
no need in transforming. There is DC power source module transformation in internal controllers of NDW3-2500
and above frames. See Chapter 7 Electrical Wiring Diagram.
3) To be powered by the test port
Rated voltage: DC24V, with an allowable error of ±5%. The panel power supply is used for separately testing
the controller, rather than the working power supply.
■ Rated power consumption of controller
Rated power consumption: <7W.
■ Contact capacity of controller
DO signal alarm output, contact capacity: AC250V/3A;
Fault tripping contact output, contact capacity: AC250V/16A;

Internal & confidential file Page 28 of 117


NDT2920213 Document Version: 3

Auxiliary contact output of the circuit breaker status, contact capacity: AC250V/16A

3.6 Introduction of Controller Functions


For introduction of controller functions, see the User Manual of NWK21 and NWK31 Controller and User
Manual of NWK22 and NWK32 Controller
3.7 Protection Characteristic Curve
Overlaod long time delay protection, short-circuit short time delay protection, short-circuit instantaneous protection
and grounding protection curves are seen in the following diagram.

Overload long delay time


adjustable

Overload long-time
delay protection

Overload long-time delay current adjustable

Short-circuit short time-delay


Ground setting current adjustable
current
adjustable

Short circuit short-time


delay inverse time-limit
protection
Short-circuit short
time-delay setting time Short circuit short-time delay
adjustable fixed time-limit protection

Short circuit instantaneous


protection
Ground
(Current adjustable)
protection

2019.11.27
试制

For each protection characteristic curve of controller, see the User Manual of NWK21 and NWK31 Controller and
User Manual of NWK22 and NWK 32 Controller

Internal & confidential file Page 29 of 117


NDT2920213 Document Version: 3

Chapter 4 Accessories
4.1 Accessories list ...................................................................................................................... 31
4.2 Electrical Control Accessories .............................................................................................. 32
4.3 Signal Output Accessories .................................................................................................... 35
4.4 Related Accessories of Controller ......................................................................................... 37
4.5 Safety Accessories................................................................................................................. 50
2019.11.27
4.6 Lock and interlocking device
试制................................................................................................ 51

4.7 Power Supply Conversion System ........................................................................................ 54


4.8 Communication System ........................................................................................................ 60

Internal & confidential file Page 30 of 117


NDT2920213 Document Version: 3

Accessories 4
4.1 Accessories list
Accessory Type of the installation
Accessory name Configuration Remarks
category structure
Standard
Closed electromagnet Fixed type/drawout type
configuration
Standard
Shunt release Fixed type/drawout type
configuration
Electrical control Standard
Motor operating mechanism Fixed type/drawout type
accessories configuration
Undervoltage release Optional Fixed type/drawout type
Undervoltage release (loss of voltage Either
Optional Fixed type/drawout type
protection)
Remote reset electromagnet Optional Fixed type/drawout type
Standard
Auxiliary switch Fixed type/drawout type
configuration
Closing ready signal output device Optional Fixed type/drawout type
Signal output
Three-position status signal output
accessories Optional Drawout type
device of the drawer seat
Standard
Secondary terminal Fixed type/drawout type
configuration
External N-pole transformer
Optional Fixed type/drawout type
(rectangular, flexible type)
Shell frame level
External current leakage transformer Optional Fixed type/drawout type
≤4000A
Power supply module NWDF1 Optional Fixed type/drawout type
To be used with
Relay module NWDF1-RM Optional Fixed type/drawout type the power supply
module
Communication adapter
Optional Fixed type/drawout type
NWDF1-MD/MP
Related accessories
Message notification module
of controller Optional Fixed type/drawout type
NWDF1-SMS
Temperature alarm protection device Optional Fixed type/drawout type
Remote intelligent I/O module
Optional Fixed type/drawout type
NWDF1-C8/S12/SC64/SCM423
6-channel programmable output module
Optional Fixed type/drawout type
NWDF1-C6
Accessory monitoring unit NWDF1-AM Optional Fixed type/drawout type
Energy-storing signal communication
Optional Fixed type/drawout type
module NWDF1-S1
Voltage conversion module NWDF1-P2 Optional Fixed type/drawout type
Standard
Phase partition Fixed type/drawout type
configuration
Safety accessories Counter Optional Drawout type
Door frame Optional Fixed type/drawout type
Dust cover Optional Drawout type
Off-position key lock Optional Fixed type/drawout type
Lock and
Button lock Optional Fixed type/drawout type
interlocking device
Door interlock Optional Drawout type
Mechanical interlocking Optional 2019.11.27 type
Fixed type/drawout
Power supply 试制
For the two-way
conversion system Power automatic switching device (ATS) Optional Fixed type/drawout type
power supply

Internal & confidential file Page 31 of 117


NDT2920213 Document Version: 3

4.2 Electrical Control Accessories


4.2.1 Closed electromagnet
Closed electromagnet is mainly composed of coil, iron core component and electronic
parts. In the condition of mechanism energy storage, as long as the closed electromagnet is
energized, the circuit breaker can be closed.
◆ Action features of the closed electromagnet.
1) When the power supply voltage of the closed electromagnet maintains at 85%~110%
2019.11.27
of the rated control supply voltage Us, operation of the closed electromagnet can make
试制
reliable closing of the circuit breaker;
2) Closed electromagnet is the short-time duty-type;
3) Power-on time >200ms.
◆ Technical Parameters of Closed Electromagnet
Power Consumption Table of Closed Electromagnet
Rated insulation Instantaneous power
Rated control supply voltage (Us)
voltage (Ui) NDW3-1600 NDW3-2500, 4000, 6300

AC380V/AC400V 50/60Hz 380 VA 620VA

AC220V/AC230V 50/60Hz 330 VA 500VA

400V DC220V 330W 500W

DC110V 270W 400W

DC24V 156W 135W

4.2.2 Shunt release


Shunt release is mainly composed of coil, iron core component and electronic parts,
and can disconnect the circuit breaker by remote operation.
◆ Action features of the shunt release
1) When the power supply voltage of the shunt release maintains at 70%~110% of the
rated control supply voltage, operation of the shunt release can make the circuit breaker
disconnect;
2) Shunt release is the short-time duty-type;
3) Power-on time >200ms.
◆ Technical Parameters of Shunt Release
Power Consumption Table of Shunt Release
Rated insulation Instantaneous power
Rated control supply voltage (Us)
voltage (Ui) NDW3-1600 NDW3-2500, 4000, 6300

AC380V/AC400V 50/60Hz 380 VA 620VA

AC220V/AC230V 50/60Hz 330 VA 500VA

400V DC220V 330W 500W

DC110V 270W 400W

DC24V 156W 135W

Internal & confidential file Page 32 of 117


NDT2920213 Document Version: 3

4.2.3 Motor operating mechanism


The circuit breaker can only be closed after the motor operating mechanism make
the circuit breaker to store energy in advance.
◆ Operation features
1) If the rated supply voltage of the motor operating mechanism is between
85%~110% , energy storage of the circuit breaker can be made in place.
2) The motor will close the power supply automatically and stop operation after it
stores energy in place.
3) The motor operating mechanism can realize the automatic pre-energy storing.
◆ Technical Parameters of Motor Operating Mechanism
Power Consumption Table of Motor Operating Mechanism
Rated Rated control Power consumption
Energy storage
insulation supply voltage
time NDW3-1600 NDW3-2500 NDW3-4000 NDW3-6300
voltage (Ui) (Us)
AC220V/AC230V
AC380V/AC400V 90 VA 110VA 150 VA 180 VA
400V 3s~5s
(50/60Hz)
DC220V/DC110V 90W 110W 150W 180W

4.2.4 Undervoltage release


◆ Action features of the undervoltage release
1) When the applied voltage drops, even slowly drops to 70%~35% of the
rated operational voltage,
the undervoltage release will work to disconnect the circuit breaker;
2) When the applied voltage is less than 35% of the rated operational voltage
of the undervoltage release, the undervoltage release will make the circuit breaker cannot be closed;
3) When the applied voltage is 85%~110% of the rated operational voltage of the undervoltage release, the
undervoltage release can be closed reliably to guarantee the reliable closing of the circuit breaker.
◆ Undervoltage release can be divided into two types (instantaneous release and delayed release), which is
mainly composed of coil, iron core component and electronic parts.
◆ Undervoltage delayed release
The undervoltage delayed release sets the delay time of the release action through toggling the toggle switch
on the undervoltage delayed device. The delay time is set as 1 s, 3 s, 5 s as required, and the factory default is 1 s.
◆ See the table below for the power consumption of undervoltage release.
Power Consumption Table of Undervoltage Release
2019.11.27
Rated insulation voltage Operating
试制 power
Rated operational voltage (Ue)
(Ui) NDW3-1600 NDW3-2500, 4000, 6300

AC220V/AC230V 50/60Hz 0.8 VA 3.9VA

AC380V/AC400V 50/60Hz 0.8 VA 5.2VA

400V DC220V 0.8W 3.9W

DC110V 0.8W 3.9W

DC24V 1.9W 1.55W

Internal & confidential file Page 33 of 117


NDT2920213 Document Version: 3

4.2.5 Undervoltage release (loss of voltage protection), loss of voltage release for short
◆ Action features of the loss of voltage release
1) When the applied voltage suddenly drops to 0~30% of the rated
operational voltage, the loss of voltage release will work to disconnect the circuit
breaker;
2) When the applied voltage is less than 30% of the rated operational voltage
of the loss of voltage release, the loss of voltage release will make the circuit breaker cannot be closed;
3) When the applied voltage is 85%~110%
2019.11.27 of the rated operational voltage of the loss of voltage release, the
试制
loss of voltage release can guarantee the reliable closing of the circuit breaker.
4) When the applied voltage drops no less than 35% of the rated operational voltage, the loss of voltage
release can be closed to guarantee the reliable closing of the circuit breaker.
◆ The loss of voltage release can be divided into instantaneous release and delayed release, which is
mainly composed of coil, iron core component and electronic parts.
◆ Loss of voltage delayed release
The loss of voltage delayed release sets the delay time of the release action through toggling the toggle
switch on the loss of voltage delayed device. Delay time: NDW3-1600/6300:0s~10s adjustable for
clients(factory default setting value is 3s), and its step length is 1s; NDW3-2500/4000:1s、3s、5s.
◆ See the table below for the power consumption of loss of voltage release.
Power Consumption Table of Loss of Voltage Release
Operating power
Rated insulation voltage (Ui) Rated operational voltage (Ue)
NDW3-1600 NDW3-2500、4000、6300
AC220V(AC230V) 50Hz/60Hz 0.8VA 4VA
400V
AC380V(AC400V) 50Hz/60Hz 0.8VA 8VA
4.2.6 Remote reset electromagnet
This accessory is installed in the controller base. In case of fault tripping and
troubleshooting of controller, the remote reset electromagnet can reset the reset
button of the circuit breaker for the normal closing/opening operation of the
circuit breaker
◆ Action features of remote reset electromagnet
1) When the power supply voltage of the remote reset electromagnet
maintains at 85%~110% of the rated control supply voltage, operation of the shunt release can make the
circuit breaker disconnect;
2) Remote reset electromagnet is the short-time duty-type;
3) Power-on time >200ms.
◆ Technical Parameters of Remote Reset Electromagnet
Power Consumption Table of Remote Reset Electromagnet

Rated insulation voltage (Ui) Rated control supply voltage (Us) Instantaneous power

AC220V/AC230V 50/60Hz
55VA
DC220V
400V
DC110V
50W
DC24V

Internal & confidential file Page 34 of 117


NDT2920213 Document Version: 3

4.3 Signal Output Accessories


4.3.1 Auxiliary switch
◆ The conventional thermal current of the auxiliary switch is 6 A;
◆ Auxiliary contact form: Four groups switch, six groups switch, four normally
opened and four normally closed, five normally opened and five normally closed, six
normally opened and six normally closed.
◆ Technical Parameters of Auxiliary Contact
Applicable shell frame NDW3-1600 NDW3-4000 NDW3-2500/6300

■ Four normally opened


Conventional ■ Four groups switch ■ Four groups switch
and four normally closed

Auxiliary contact ■ Five normally opened


■ Four normally opened
form and five normally closed
Special ■ Six groups switch and four normally closed
■ Six normally opened and
■ Six groups switch
six normally closed

Agreed thermal current Ith 6A

Minimum load 2mA/DC15V

DC-13 5A/250V
Breaking capacity
AC-15 16A/380V

4.3.2 Closing ready signal output device


Closing ready signal output device of the circuit breaker is the output signal
device that reflects the operating mechanism to achieve the closed state. It can output
signals if it meets the following mechanical states. See the table below for technical
parameters.
Circuit breaker off state;
Energy storage in place;
No disconnection instruction;
Undervoltage release closing in place;
Controller fault tripping reset.
Table of Technical Parameters
Applicable shell frame NDW3-1600, NDW3-2500, NDW3-4000, NDW3-6300

250V 3A
Breaking capacity AC
125V 5A
2019.11.27
试制
4.3.3 Position status signal output device of the drawer seat (on the drawer seat)
When the drawer-seat circuit breaker body is in the "Separation", "Test" and
“Connection" positions of the drawer seat(Pop-up the red reset button in front of the
drawer seat), the triolocation electric indication device can output the electrical status
signal corresponding to the three positions with the signal output terminal located on
the left side of the drawer seat. See the table below for technical parameters

Internal & confidential file Page 35 of 117


NDT2920213 Document Version: 3

Table of Technical Parameters


Applicable shell frame NDW3-1600, NDW3-2500, NDW3-4000, NDW3-6300

DC 125V 0.4A
Breaking capacity
AC 250V 16A

4.3.4 Secondary wiring terminal


■ For the number of secondary wiring terminal, there is a total of 62
groups (identical for the fixed type and drawout type); see Chapter 8 for the
2019.11.27
试制
definition and its electrical wiring diagram of each terminal number.
■ See the table below for parameters of the secondary wiring terminal
Item Parameter

Connection mode Clamping

Flame retardant rating, according to UL 94 V0

Pollution level 3

Voltage category III

Material group IIIa

Applicable connection standards GB/T 14048.7-2006

Maximum load current 10A

Rated current 10A

Rated Voltage 500V

Minimum cross section area of the rigid (flexible) 0.2mm2

conductor

Maximum cross section area of the rigid (flexible) 1.5mm2

conductor

Recommended striping length 10mm

Minimum test pull-force after the conductor 10N

connection

Internal & confidential file Page 36 of 117


NDT2920213 Document Version: 3

4.4 Related Accessories of Controller


4.4.1 External N-pole transformer
Ground type
The 3P+N system can be formed by using a 3P circuit breaker and an external N-phase transformer. It can
measure data on the grounding cable via an external N-pole transformer to realize the ground protection of the
differential type (T) or the ground current type (W). The electric circuit diagram is shown as below:
1) Electric circuit diagram of differential type (T)

Intelligent
controller
Intelligent
controller Intelligent
controller
External N-phase
transformer

3P 4P (3P+N)T

2) Electric circuit diagram of ground current type (W)

Intelligent
controller
PE or
PEN

◆ Transformer type
For rectangular and flexible-type transformers, users can select the shell frame current (or N-pole current)
and dimensions.
1) Rectangular transformer
★ Rectangular transformer code
Transformer code Hole dimensions mm Applicable shell frame

N1 62×21 1600

N2 102×32.5 1600

N3 122×52 2500, 4000, 6300


2019.11.27
N4 262×102 2500, 4000,
试制 6300

★ See the figure below for outline and installation dimensions of the rectangular transformer.
★ pay attention to the direction for use:the current flows from P1 to P2.

Internal & confidential file Page 37 of 117


NDT2920213 Document Version: 3

N1 external transformer N2 external transformer

2019.11.27
试制
N3 external transformer N4 external transformer

Outline and Installation Dimension


Diagram of the N-pole Transformer
★ With conductors to be supplied by customers, it is recommended to use the shielded twisted pair (with
the metal shield layer, 0.2~0.3mm²,namely the AWG24/AWG22 conductor). The recommended conductor length
is no more than 3 meters for connection of Y-type terminals at the wire end, with a tightening torque of 1.2N.m.
2) Flexible transformer
★ Flexible transformer code
Transformer code Circumference of soft connection coil Applicable current range

NR1 280mm 200A-800A

NR2 370mm 1000A-2000A

NR3 450mm 1000A-6300A

★ See the figure below for outline and installation dimensions of the flexible transformer.
★ pay attention to the direction for use:the inlet wire direction is shown in the picture.

Internal & confidential file Page 38 of 117


NDT2920213 Document Version: 3

★ Install the flexible transformer on the busbar as shown in the figure, and connect the transformer
conduction to the secondary circuit: Red to No. 25 and green to No. 26. Standard configuration of the
conductor is 3m.
4.4.2 External current leakage transformer
◆ When the grounding protection mode is residual current protection (E) type, an external current
leakage transformer is required. The controller judges action via the output signal of the external current
leakage transformer.
◆ See the figure below for the current leakage protection schematic (3P and 4P system).
External current External current
leakage transformer leakage transformer

N
PE
R Intelligent
controller Intelligent
controller

Schematic Diagram of Current Leakage Protection


◆ NDW3-1600 mode can pass through busbar while the NDW3-1600 and 2500 modes can pass through
cable.
◆ With conductors to be supplied by customers, it is recommended to use the shielded twisted pair (with
the metal shield layer, 0.2~0.3mm²,namely the AWG24/AWG22 conductor). The recommended conductor
length is no more than 3 meters for connection of Y-type terminals at the wire end, with a tightening torque of
1.2N.m.
2019.11.27
◆ See the figure below for outline and installation dimensions of the external current
试制 leakage

transformer

Internal & confidential file Page 39 of 117


NDT2920213 Document Version: 3

◆ When install the circumscribed electric leakage mutual inductor, there is no need in distinguishing
directedns.

2019.11.27
试制

Outline and Installation Dimension Diagram of the External Current Leakage Transformer

4.4.3 Power supply module NWDF1


◆ Role: As the power source of relay module NWDF1-RM, the output
voltage is DC24V;
◆ Type: See the table below

NWDF1-P1 NWDF1-P3 NWDF1-P5


Nominal 400/230VAC 220/110VDC
24 VDC
voltage
Allowable 180VAC-430VAC 85VDC-265VDC
Working 12-36 VDC
input range
power
Isolation 1500Vrms 1500Vrms
supply 1500Vrms
voltage
Reverse Without polarity effects With polarity effects
With polarity effects
polarity effects
Protection IP20 IP20
IP20
class
Dimensions 90 x 54 x 58.5mm 90×72×58.5 90×72×58.5
1. With a 35mm standard guide rail 1. With a 35mm standard guide
Installation Installed with a 35mm
2. Screw installation rail
mode standard guide rail
2. Screw installation

◆ Supply mode: Optional ordering by customers;


Users indicate the rated operational voltage and carry out installation by themselves. Pay attention to “+”
and “-” polarities of wiring, which cannot be wrongly wired.

Internal & confidential file Page 40 of 117


NDT2920213 Document Version: 3

◆ See the figure below for outline and installation dimensions.

Outline and Installation Dimension Diagram of Power Supply Outline and Installation Dimension Diagram of Power Supply
Module NWDF1-P1 Module NWDF1-P3/P5
4.4.4 Relay module NWDF1-RM
◆ Function: Signal unit of controller is commonly used in fault alarm or
indication, etc. When the circuit breaker is opened, closed or when the load
capacity is larger, the control should be carried out after conversion through
this module. Match with the power supply module NWDF1 to achieve the
"four remotes" function;
◆ Contact capacity: AC250V, 10 A; DC24V, 10 A;
◆ Appearance and installation: To be used with the controller power supply
module ST-IV, see the installation diagram of relay module.

Installation Diagram of Relay Module 2019.11.27


试制

4.4.5 Communication adapters NWDF1-MD, NWDF1-MP, NWDF1-ME and NWDF1-MC


 The communication adapter can be divided into the following types: NWDF1-MD and NWDF1-MP.
It connects with the intelligent communication products with our ModBus RTU standard protocol
interface to realize conversion of different protocols, thus making the intelligent communication

Internal & confidential file Page 41 of 117


NDT2920213 Document Version: 3

products to achieve the remote communication, remote regulating, remote control and remote sensing
functions on DeviceNet and ProfiBus DP.
1) NWDF1-MD(MDC-225) communication adapter realizes conversion from the ModBus-RTU protocol to
the DeviceNet protocol;
2) NWDF1-MP(PM-127) communication adapter realizes conversion from the ModBus-RTU protocol to
the Profibus DP protocol;
3) NWDF1-ME(ES-301A) communication
2019.11.27
adapter realizes conversion from the ModBus-RTU protocol to
试制
the Ethernet protocol;
4) NWDF1-MC(NT50-CO-RS) communication adapter realizes conversion from the ModBus-RTU
protocol to the CAN protocol;
5) See the attached manual of each accessory for the communication protocol.
6) NWDF1-MD and NWDF1-MP only support communication for a single device.
◆ Appearance and function indication Power
Communica

1. Button
RS485
PROFIBUS DP
interface
address setting
4. Devicenet
2. Module status address shows
indicator MS
LED

3. Network status PROFIBUS DP

indicator NS interface

NWDF1-MD NWDF1-MP

◆ See the figure below for outline and installation dimensions.

Install the
guide rail here

Unit: mm

NWDF1-MD Outline and Installation Dimension Diagram NWDF1-MP Outline and Installation Dimension Diagram

Internal & confidential file Page 42 of 117


NDT2920213 Document Version: 3

NWDF1-ME Outline and Installation Dimension Diagram

NWDF1-MC Outline and Installation Dimension Diagram

4.4.6 Message notification module NWDF1-SMS(JYC311A6)


 The message notification module directly connects one communication circuit breaker via the
standard RS485 communication mode.
When a fault tripping event occurs to the circuit breaker, send a message to one or up to 5 phones via the GSM
network so as to prompt the user for timely treatment. The message content includes tripping type, fault current,
2019.11.27
试制
delay time, tripping time (year/month/day/hour/minute/second); users can add their own mobile phone users
via the framework controller (enter the phone number). Note: Users shall buy their own mobile phone SIM
card with China mobile number. Other network is not supported and shall be guaranteed to be in the renewal
state. The message center number setting must be correct at the same time; otherwise the message can’t be sent
normally. See the figure below for outline and installation dimensions.

Internal & confidential file Page 43 of 117


NDT2920213 Document Version: 3

2019.11.27
试制

4.4.7 Remote intelligent I/O module NWDF1-C8/S12/SC64/SCM423


The remote intelligent I/O module is a simple, practical and reliable monitoring communication module
(installed with a 35mm standard guide rail), which enables the remote communication, remote control and remote
measurement of the system via the standard RS485 interface and ModBus-RTU protocol. When using a
non-communication circuit breaker, users can monitor the corresponding power distribution circuit via the module.
Users can remotely monitor the circuit current, circuit breaker on-off status, fault status and other important
information.
After the module is energized, the power/status indicator will flash quickly (0.5s on/0.5s off) while the rest
indicators will be constantly on for 1s and then enter into the working state. During this period, any input, output
and communication are invalid. After normal startup, this module can realize the following functions: Setting the
communication parameters by pressing the key (communication initialization button); detecting the current input,
i.e. the analog input; detecting the digital input, i.e. the passive dry contact input; controlling the digital output,
that is, self-holding output/pulse output.
NWDF1-SCM423 features 4 common-side switch inputs, 2 relay outputs and 3 5A current inputs. Users
can know the 3-phase current and 4-channel switch of the feeder line (such as: switch on-off status, fault status,
etc.) via it combined with inputs & outputs of the circuit breaker and the standard current transformer in the line
.
NWDF1-S12 features 12 common-side switch inputs. Users can learn the on-off status up to 12 circuit
breakers or the on-off status and fault status of 6 circuit breakers.
 NWDF1-C8 has 4 groups of 8 relay outputs, for controlling the on-off status of 4 circuit breakers.
 NWDF1-SC64 features 6 switch inputs and 4 relay outputs, for monitoring its important status while
controlling the circuit breaker.
 See the table below for general parameters

Nominal voltage 24VDC


Working power
Allowable input range 18V~36VDC
supply
Isolation voltage 1000Vrms

Internal & confidential file Page 44 of 117


NDT2920213 Document Version: 3

Reverse polarity effects Does not work, but does not damage the module
Voltage above 40VDC may cause the permanent damage of
Voltage mismatch
the module
Voltage sag Sag for 10ms can still work without interruption
interface Standard RS485, 2-wire, Modbus RTU
Optional Modbus address 1~247
Baud rate 1200/2400/4800/9600/19200/38400bps
Communication Parity bit CRC check, without support for parity
Isolation voltage 1000Vrms
Maximum number of
32
modules for a single bus
Protection class IP20
Dimensions 91.6 x 54 x 58.5mm
Installation
Installed with two 35mm standard guide rails
mode

 See the figure below for outline and installation dimensions.

Outline and Installation Dimension Diagram of the Remote Intelligent I/O Module

4.4.8 6-channel programmable output moduleNWDF1-C6


 For the NDWF1-C6 programmable output module (installed with a
35mm standard guide rail),
For the programmable content details, see the NWDF1-C6 6-channel
programmable expansion output module part in the NDT2920191 “Operation
2019.11.27
试制
Manual of NWDF1 Series Frame Electrical Accessories”.
 For the communication protocol details of the programmable module,
see the NWDF1-C6 6-channel programmable expansion output module part in the NDT2920191
“Operation Manual of NWDF1 Series Frame Electrical Accessories”.

Internal & confidential file Page 45 of 117


NDT2920213 Document Version: 3

Function Table of Wiring Mode and Terminal Definition


Model Terminal code Connection position Input/output Remarks
Power-supply AC220V Power-supply AC220V input, including
AC230V Input
input end neutral wire, live wire
B RS485 communication AB RS485 communication ports, do not
Input/output
A ports reverse
1 Relay output 1 NC contact Output Relay output 1 NC contact
2 Relay output 1 NO contact Output Relay output 1 NO contact
2019.11.27
Relay output 1 public
3 试制 Input Relay output 1 public contact
contact
4 Relay output 2 NC contact Output Relay output 2 NC contact
5 Relay output 2 NO contact Output Relay output 2 NO contact
Relay output 2 public
6 Input Relay output 2 public contact
contact
7 Relay output 3 NC contact Output Relay output 3 NC contact
8 Relay output 3 NO contact Output Relay output 3 NO contact
NWDF1-C6
Relay output 3 public
9 Input Relay output 3 public contact
contact
10 Relay output 4 NC contact Output Relay output 4 NC contact
11 Relay output 4 NO contact Output Relay output 4 NO contact
Relay output 4 public
12 Input Relay output 4 public contact
contact
13 Relay output 5 NC contact Output Relay output 5 NC contact
14 Relay output 5 NO contact Output Relay output 5 NO contact
Relay output 5 public
15 Input Relay output 5 public contact
contact
16 Relay output 6 NC contact Output Relay output 6 NC contact
17 Relay output 6 NO contact Output Relay output 6 NO contact
Relay output 6 public
18 Input Relay output 6 public contact
contact

Programmable Output Module Contact Type Table


Non-locking contact In case the alarm triggered by fault isn't eliminated, the contact holds action
Locking contact The contact holds action until reset (reset menu)
Time delay contact The contact holds action within the adjustable time delay or is reset (reset menu)

Time Setting Table of the Time Delayed Contact


Item Scope Step Accuracy
Delay time of the delay time contact 1s-360s 1s ±10%

Electric Parameters Table of the Programmable Module Relay Output


Rated working voltage Ue/V Agreed thermal current Ith/A Rated working current Ie/A Rated control capacity
5 AC-15: 5(2-channel 1200VA (2-channel
AC 230
(2-channel programmable programmable output module programmable

Internal & confidential file Page 46 of 117


NDT2920213 Document Version: 3

output module is 1A) is 1A) output module is 230VA)


400 AC-15: 3 1200 VA
220 DC-13: 0.15
DC 50W
110 DC-13: 0.4

 See the figure for outline and installation dimensions of 6-channel programmable output module.

Outline and Installation Dimension Diagram of 6-channel Programmable Output Module

4.4.9 Accessory monitoring unit NWDF1-AM


 After installed with the accessory monitoring unit, the circuit breaker can perform the online monitoring
of coil break for the shunt release, closing electromagnet, undervoltage release and energy storage motor,
to ensure normal operation of the circuit breaker.
 For the communication protocol details, see the NWDF1-AM accessory monitoring module part in the
NDT2920191 “Operation Manual of NWDF1 Series Frame Electrical Accessories”.
 See the table below for technical parameters

Nominal voltage 230VAC


Allowable input range 180V~270VAC
Isolation voltage 1000Vrms
Working power
Reverse polarity effects Without polarity effects
supply 2019.11.27
试制cause the permanent damage
Voltage above 260VAC may
Voltage mismatch
of the module
Voltage sag Sag for 10ms can still work without interruption
interface Standard RS485, 2-wire; Modbus RTU
Optional modbus address 2~127
Communication Baud rate 9600
Parity bit CRC check, without support for parity
Isolation voltage 1000Vrms

Internal & confidential file Page 47 of 117


NDT2920213 Document Version: 3

Number of modules for a


32
single bus
Protection class IP20
Dimensions 90 x 72 x 58.5mm
Installation mode Installed with a 35mm standard guide rail

 Function Table of Wiring Mode and Terminal Definition

Model Terminal code Connection position Port notes Remarks


L
2019.11.27 Without positive and
Power
试制 supply 230V Power supply
negative polarities
N
The terminal code is
A RS485 A Communication port consistent with that of the
communication module
The terminal code is
B RS485 B Communication port consistent with that of the
communication module
COM COM Communication shied earthing No wiring required
The terminal code is the
Motor detection
29 Motor coil break monitoring definition number of the
line
body secondary terminal
The terminal code is the
Motor detection
NWDF1-AM 30 Motor coil break monitoring definition number of the
line
Accessory body secondary terminal
monitoring The terminal code is the
Motor detection
module 31 Motor coil break monitoring definition number of the
line
body secondary terminal
The terminal code is the
Motor detection
32 Motor coil break monitoring definition number of the
line
body secondary terminal
The terminal code is the
16 Shunt+ Shunt coil break monitoring definition number of the
body secondary terminal
The terminal code is the
17 Shunt- Shunt coil break monitoring definition number of the
body secondary terminal
The terminal code is the
18 Closing+ Closing coil break monitoring definition number of the
body secondary terminal
The terminal code is the
19 Closing- Closing coil break monitoring definition number of the
body secondary terminal
The terminal code is the
20 Pull-in+ Pull-in coil break monitoring definition number of the
body secondary terminal
The terminal code is the
21 Pull-in- Pull-in coil break monitoring definition number of the
body secondary terminal
The terminal code is the
22 Hold+ Hold coil break monitoring definition number of the
body secondary terminal
The terminal code is the
23 Hold- Hold coil break monitoring definition number of the
body secondary terminal

 See the figure below for outline and installation dimensions.

Internal & confidential file Page 48 of 117


NDT2920213 Document Version: 3

NWDF1-AM Outline and Installation Dimension Diagram

4.4.10 Energy-storing signal communication module NWDF1-S1


 Energy-storing signal communication module components can obtain the “Energy
storage” or “Energy release” status information of the electric operating mechanism
of the circuit breaker via the upper computer.
Outline and installation dimensions are the same with the outline and installation dimension
diagram of the remote intelligent I/O module.

4.4.11 Voltage conversion module NWDF1-P2


 As the maximum rated input of the frame controller is AC400V in case of voltage detection, a
voltage conversion module is required to reduce the voltage below AC400V when the input is greater
than AC400V.
 See the table below for technical parameters:
Input voltage 690VAC~1200VAC
Working power supply
Allowable input range 690VAC~1200VAC
Protection class IP20
Dimensions 90 x 54 x 58.5mm/90×72×58.5
Installation mode Installed with a 35mm standard guide rail

 See the figure below for outline and installation dimensions.

2019.11.27
试制

NWDF1-P2 Outline and Installation


Dimension Diagram

Internal & confidential file Page 49 of 117


NDT2920213 Document Version: 3

4.5 Safety Accessories


4.5.1 Phase partition
Divided into fixed type and drawout type, the phase partition is installed in the groove between all the phase
bus bars, used to increase the insulation strength between phases of the main circuit so as to prevent the short
circuit in case of the insulation breakdown and improve the power reliability.
◆ Conventional phase partition

2019.11.27
试制

Fixed type appropriative holder Phase Partition

◆ HU Type Circuit Breaker Phase Partition


The phase partition is divided into fixed type and drawer type, and is installed in the grooves between all
phase bus-bars. It is used to strengthen the dielectric insulation between phase and phase, input lines and output
lines of main circuits, to prevent short-circuit caused by insulation breakdown, and therefore increase reliability of
power supply.

Fixed type appropriative holder Phase Partition Input and output line partition
NDW3-2500HU

Fixed type appropriative holder Phase Partition Input and output line partition
NDW3-4000HU

Internal & confidential file Page 50 of 117


NDT2920213 Document Version: 3

Note:When installing, NDW3-4000HU input and output line partition side with N, A, B and C should be
installed upturned.
4.5.2 Counter
Counter is used to record the number of the "close-open" operation of the circuit
breaker.

4.5.3 Doorframe
Divided into fixed type and drawout type, it is mainly placed on the door of the cubicle for sealing effect, and can
make the protection level of the circuit breaker reaches IP40. It is beautiful and practical.

Fixed type
Drawout type

4.5.4 Dust cover


Installed on the beam of the wiring terminal, it can prevent dust and other debris falling into the terminal of the
wiring terminal, leading to poor contact. It is an optional accessory.

4.6 Lock and interlocking device


4.6.1 Off-position key lock (on the circuit breaker)
This key lock is locked on the manually disconnected position of the circuit
breaker. When the key is anticlockwise locked and pulled out,
2019.11.27
The circuit breaker cannot carry out closed operation, so as to prevent irregular 试制
operation. Model and type are shown in the table below.
Model and Type Table of Off-position Key Lock

Model Name Number of circuit breakers Number of keys

SF11 One lock one key 1 1

SF21 Two locks one key 2 1

SF31 Three locks one key 3 1

Internal & confidential file Page 51 of 117


NDT2920213 Document Version: 3

SF32 Three locks two keys 3 2

SF53 Five locks three keys 5 3

When the off-position lock is optionally selected, this accessory is sent to the user after being assembled
with the circuit breaker. As the off-position lock protrudes out of the circuit breaker mask, the installer shall pay
attention to the protruding dimension when opening the power distribution cabinet door. This dimension diagram
and data are as follows.
2019.11.27
试制

Mounting plate of the circuit Mask centerline of the Mounting plate of the circuit
breaker cabinet circuit breaker breaker cabinet

Drawer seat off position

Mounting plate of the Mask centerline of the Mounting plate of the


circuit breaker cabinet circuit breaker cabinet Drawer seat connection
circuit breaker position
Drawout type

Unit: mm
a b c d
Model Fixed Drawout Fixed Drawout Fixed Drawout Fixed Drawout
type type type type type type type type
NDW3-1600 17 220 134 114 42
NDW3-2500 27 247 125 163 45

Internal & confidential file Page 52 of 117


NDT2920213 Document Version: 3

NDW3-4000
NDW3-6300
4.6.2 Button lock
◆ To be used with a padlock, it is used to prevent non-staff from illegally
operating the opening/closing button (padlock should be prepared by
users).
◆ When the off-position lock is optionally selected, this accessory is sent
to the user after being assembled with the circuit breaker. As the
off-position lock protrudes out of the circuit breaker cover, the installer shall pay attention to the
protruding dimension when opening the power distribution cabinet door.
This dimension diagram and data are as follows.

Mounting plate of the Mask centerline of the


Mounting plate of the
circuit breaker cabinet circuit breaker
circuit breaker cabinet

Fixed

Drawer seat off position

2019.11.27
试制

Mounting plate of the Mask centerline of the Mounting plate of the Drawer seat connection
circuit breaker cabinet circuit breaker circuit breaker cabinet position

Drawo

Unit: mm

Internal & confidential file Page 53 of 117


NDT2920213 Document Version: 3

a b c d
Model Fixed Drawout Fixed Drawout Fixed Drawout Fixed Drawout
type type type type type type type type
NDW3-1600 18 155 187.5 91.7 108.2 26.4
NDW3-2500
27 204 243.7 106 143.8 26.4
NDW3-4000
NDW3-6300 27 204 243.7 106 104.4 26.4

4.6.3 Door interlock (on the drawer seat)


2019.11.27
Installed on the right or the left side of the
试制drawer seat. When the drawout type circuit breaker is in the separation

position, it can avoid opening of the cubicle door.

4.7 Power Supply Conversion System


4.7.1 Mechanical interlocking
 Mechanical interlocking mechanism can be used for interlocking of the drawout circuit breaker and the
fixed circuit breaker;
 Interlocking mechanism shall be installed by users. First, demount the nut for connecting the rear part of
the interlocking device with four combination screws; then, fix the interlocking mechanism on the right-side plate
of the circuit breaker with four combination screws;
 Interlocking pattern selection is shown in the table below

Selection Number of circuit


Code Type
mode breakers
Two sets of cables, one for
1 SR11 2
closing and one for opening
Three sets of cables, one for
2 SR12 3
closing and two for opening
Three sets of cables, two for
3 SR21 3
closing and one for opening
Two sets of hard rods, one for
4 SY11 2
closing and one for opening
Three sets of hard rods, one
5 SY12 for closing and two for 3
opening

Internal & confidential file Page 54 of 117


NDT2920213 Document Version: 3

 Circuit breaker can be applicable to the following power supply state interlocking
1) Two circuit breakers (one for closing and one for opening)
Usage mode is shown in the figure below, while interlocking action state is shown in the figure below.

Status Table of Two Circuit Breaks


U1 U2
Close Open
Open Close
Open Open

2) Three circuit breakers (one for closing and two for opening)
Usage mode is shown in the figure below, while interlocking action state is shown in the figure below.

Status Table of Three Circuit Breakers (One for Closing


and Two for Opening)
U1 U2 U3
Close Open Open
Open Close Open
Open Open Close
Open Open Open
3) Three circuit breakers (two for closing and one for opening)
Usage mode is shown in the figure below, while interlocking action state is shown in Table 64.
Status Table of Three Circuit Breakers (One for Closing
and Two for Opening)
U1 U2 U3
Open Open Open
Close Close Open
Close Open Close
Open Close Close
 Type description
1) Two interlocking cables (one for closing and one for opening)
Installation schematic diagram:
2m (max)
2019.11.27
试制

Circuit breaker Circuit breaker


Internal & confidential1 file Page 55 of 117 2
NDT2920213 Document Version: 3

2019.11.27
试制

Adjustment schematic diagram:

Adjusted to the hole position II

2) Three interlocking cables


Installation schematic diagram:
2m (max) 2m (max)

Circuit breaker 1 Circuit breaker 2 Circuit breaker 3

Adjustment schematic diagram: One for closing and two for opening

Internal & confidential file Page 56 of 117


NDT2920213 Document Version: 3

Adjusted to the hole position II

Adjustment schematic diagram: Two for closing and one for opening

Adjusted to the
hole position I

3) Two interlocking hard rods


Installation schematic diagram: (One for closing and one for opening)

2019.11.27
试制

Internal & confidential file Page 57 of 117


NDT2920213 Document Version: 3

Circuit breaker 1

Cabinet

2019.11.27 Mounting hole of the


Cabinet 试制
Mounting hole of the circuit breaker
circuit breaker

900 (max)

Circuit breaker 2

Mounting hole of the


circuit breaker

4) Three interlocking hard rods


Installation schematic diagram: (One for closing and two for opening)

Internal & confidential file Page 58 of 117


NDT2920213 Document Version: 3

Circuit breaker 1
Mounting hole of the
circuit breaker

Cabinet Mounting hole of the


circuit breaker Cabinet

600 (max)

Circuit breaker 2

Mounting hole of the


circuit breaker

Mounting hole of the Cabinet


Cabinet
circuit breaker

600 (max)

Circuit breaker 3

Mounting hole of the


circuit breaker

Note: During the process of assembly adjustment, the overlong part of the connecting rod can be appropriately eliminated.
Adjustment schematic diagram:

Adjusted to the
hole position II

2019.11.27
试制

4.7.2 Power automatic switching device

Internal & confidential file Page 59 of 117


NDT2920213 Document Version: 3

Four-position switch state Automatic operation


★ Automatic switching; ★ Monitor the "common" power supply and
★ Forced with "common" power supply; automatic switching;
★ Forced with "standby" power2019.11.27
supply; ★ Generator set start control;
试制
★ Double-open state (both "common" ★ Generator set close control;
power supply and "standby" power ★ Unloading and restoring the non-priority load;
supply are disconnected). ★ Alarm control in case of abnormality of the
"standby" power supply.
Indication state Function
★ Display the power supply state of the ★ Closing delay and opening delay can be
power supply system; adjustable by section;
★ Display the closing and opening state ★ Overvoltage and undervoltage protection can be
of the universal circuit breaker; adjustable by section;
★ Display the energy storage state of the ★ Mode of the control function is optional (R, S,
universal circuit breaker mechanism; F);
★ Manual control and automatic control is
adjustable.
Selection of power supply Threshold value
★ Rated control supply voltage Us: ★ Undervoltage: 0.35Us≤voltage≤0.7Us;
220V~240V 50/60Hz; ★ Default phase: 0.5Us≤voltage≤0.7Us;
★ Rated current In: 400A~6300A ★ Voltage return value: 5V±2V.
optional.
◆ See the figure below for outline and installation dimensions

Hole dimensions

Note: Due to the power automatic switching control device has overvoltage and undervoltage protection functions, in order to
guarantee the consistency and reliability of the system protection, the universal circuit breaker used for power supply automatic
switching control device can't install undervoltage release, and the power automatic switching control device and the mechanical
interlocking (two interlocking) shall be used together.

4.8 Communication System


The controller with the communication function can realize four remotes data transmission function, i.e.,
“remote metering, remote control, remote adjustment and remote communication”, through the communication
port according to the stipulated agreement requirements. Communication port output uses photoelectric isolation,
and is suitable for strong electrical interference environment. The Modbus communication protocol is built in the
controller, and does not need additional conversion module.
■ Computer communication network

Internal & confidential file Page 60 of 117


NDT2920213 Document Version: 3

Modbu DeviceNe Profibus-D Message


module

SIM

AC230

DC24V DC24V

Accessory Remote I/O Energy-storing Energy-storing


monitoring module information information
unit communicatio communication module
RS485 n module

Status
(control)

Note: 1. The red line represents the RS485 communication line, which is connected from the communication interface of controller;
the black line represents the power supply line; the blue line represents the signal output line of the circuit breaker secondary terminal
to output the circuit breaker status or control signal.
2. The message notification module needs to use a SIM card, which shall be prepared by users.

With the Modbus-RTU mode, connect to the computer system via the conversion interface of RS485/RS232
and twisted shielded wire line from the controller RS485 interface, or connect the RS485 signal interface of circuit
breaker via the serial port server or communication manager, and then connect with computer via the Ethernet
interface (RJ45 interface). Related communication parameters of Modbus-RTU are shown in the table below.
Communication protocol Modbus 2019.11.27
试制
Communication address 0~255

Baud rate (bit/s) 9.6k, 19.2k, 38.4k, 115.2k

Distance (to be extended with a repeater) 1200m

With the communication network, the same line can connect up to 32 communication circuit
breakers (16 drawout circuit breakers) at the same time.

Internal & confidential file Page 61 of 117


NDT2920213 Document Version: 3

Chapter 5 Field of Application


5.1 Working Environment ........................................................................................................... 63
5.2 Installation Conditions .......................................................................................................... 65
5.3 Main Circuit Wiring of the Circuit Breaker .......................................................................... 65
5.4 The power loss of the incoming and outgoing lines of the circuit breaker (ambient
temperature +40℃) ..................................................................................................................... 66
2019.11.27
试制

Internal & confidential file Page 62 of 117


NDT2920213 Document Version: 3

The NDW3 series of universal circuit breakers (hereinafter referred to as circuit breakers) can be applied to
the distribution network with AC of 50 Hz / 60 Hz, rated current of 200A ~ 6300A, rated insulation voltage of
1140V, rated operational voltage of AC220/230/240V, AC380/400/415V, AC440/480V, AC660/690V , AC800V,
AC1000V and AC1140Vfor distribution of electrical energy and protecting circuit and power equipment from
overload, under-voltage, short circuit, single phase grounding and harm of other faults. It also has an isolating
function at the same time. The circuit breaker has multiple protection functions. It can avoid unnecessary sudden
power failure while realizing highly accurate selective protection, and improve the reliability and security of the
power supply system.

5.1 Working Environment


5.1.1 Ambient temperature
Applicable ambient temperature is -25℃~+70℃; the average within 24 h shall not be more than +35℃.
The circuit breaker with the ambient temperature below -25℃~-40℃ can be specially customized. If the
ambient temperature is higher than +40℃, the user needs to reduce the capacity, and the reduced capacity
coefficient is shown in Table 3.
Table 3
Ambient temperature +40℃ +45℃ +50℃ +55℃ +60℃ +70℃
200A 200A 200A 200A 200A 200A 200A
400A 400A 400A 400A 400A 400A 400A
630A 630A 630A 630A 630A 630A 630A
NDW3-1600 800A 800A 800A 800A 800A 800A 800A
1000A 1000A 1000A 1000A 1000A 1000A 1000A
1250A 1250A 1250A 1250A 1250A 1250A 1250A
1600A 1600A 1600A 1600A 1600A 1600A 1520A
630A 630A 630A 630A 630A 630A 630A
800A 800A 800A 800A 800A 800A 800A
1000A 1000A 1000A 1000A 1000A 1000A 1000A
NDW3-2500 1250A 1250A 1250A 1250A 1250A 1250A 1250A
1600A 1600A 1600A 1600A 1600A 1600A 1600A
2000A 2000A 2000A 2000A 2000A 1950A 1825A
2500A 2500A 2375A 2225A 2125A 1950A 1825A
800A 800A 800A 800A 800A 800A 800A
1000A 1000A 1000A 1000A 1000A 1000A 1000A
1250A 1250A 1250A 1250A 1250A 1250A 1250A
1600A 1600A 1600A 1600A 1600A 1600A 1600A
NDW3-4000
2000A 2000A 2000A 2000A 2000A 2000A 2000A
2500A 2500A 2500A 2500A 2500A 2500A 2500A
3200A 3200A 3200A 3200A 3200A 3120A 2920A
4000A 4000A 3800A 3560A 3400A 3120A 2920A
4000A 4000A 4000A 4000A 4000A 4000A 4000A
NDW3-6300 5000A 5000A 5000A 5000A 5000A 4914A 4599A
6300A 6300A 5985A 5607A 5355A 4914A 4599A
Note: The above data is calculated according to the test and theory. The data represent only guidelines and recommendations.
2019.11.27
5.1.2 Atmospheric environment conditions 试制
When the ambient air temperature is +40℃, the relative humidity of atmosphere shall not be more than
50%. At low temperature, a higher relative humidity is allowed; for example, in case of +25℃, the relative
humidity of atmosphere can be 90%. For condensation due to temperature change, dehumidification or
corresponding measures should be taken.
5.1.3 Altitude
Altitude of the installation site shall not exceed 2,000 m.

Internal & confidential file Page 63 of 117


NDT2920213 Document Version: 3

If the altitude of the installation site is between 2,000 m to 5,000 m, it can be specially customized. For the
working performance, refer to the correction value in the following table.
Rated working current Altitude
Type Rated current(A) 2000m 3000m 4000m 5000m
200~630 1.0In 1.0In 1.0In 1.0In
NDW3-1600 800~1000 1.0In 1.0In 1In 1In
1250~1600 1.0In 1.0In 0.97In 0.87In
630~1600 1.0In 1.0In 1.0In 1.0In
NDW3-2500
2000~2500 1.0In 0.93In 0.88In 0.85In
2019.11.27
800~2500 试制 1.0In 1.0In 1.0In 1.0In
NDW3-4000 3200 1.0In 1.0In 1.0In 1.0In
4000 1.0In 0.93In 0.88In 0.82In
4000、5000 1.0In 1.0In 1.0In 1.0In
NDW3-6300
6300 1.0In 0.93In 0.88In 0.82In

Altitude m 2000 3000 4000 5000

Impulse withstand voltage Uimp (kV) 12 11 10 8

Rated insulation voltage Ui (V) 1140 900 800 700

690 690 620 550


Rated working voltage (V)
1140 900 800 700

Power frequency withstand voltage (V) 3500 3150 2500 2500

Annotation:NDW3-1600 is not included in this table, the correction value of NDW3-1600 refer to the following
table.
Altitude m 2000 3000 4000 5000

Impulse withstand voltage Uimp (kV) 12 11 10 8

Rated insulation voltage Ui (V) 1000 900 800 700

Rated working voltage (V) 690 690 620 550

Power frequency withstand voltage (V) 3500 3150 2500 2500

5.1.4 Anti-corrosion Level


Salt mist: Severe Level 3
5.1.5 Pollution level
Pollution level: Level 3
5.1.6 Shockproof requirements
◆ The circuit breaker can ensure resistance to electromagnetic or mechanical shock, and has passed the
IEC 60721-3-3 standard test;
◆ Amplitude:±1mm (2 Hz -9Hz);
◆ Constant acceleration: 5m/s2 (9 Hz -200Hz);
◆ Super strong shock may result in damage to the parts, and impact the reliable action of the circuit
breaker.
5.1.7 Electromagnetic interference

Internal & confidential file Page 64 of 117


NDT2920213 Document Version: 3

1) The circuit breaker can resist the following electromagnetic interference


◆ Overvoltage caused by electromagnetic interference;
◆ Overvoltage due to aging of the distribution system or environmental interference;
◆ Radio wave;
◆ Electrostatic discharge.
2) The circuit breaker has passed the electromagnetic compatibility (EMC) test stipulated by following
standards
◆ GB/T 14048.2-2008 Low-voltage Switchgear and Control Equipment - Part 2: Circuit Breaker -
Appendix F;
◆ GB/T 14048.2-2008 Low-voltage Switchgear and Control Equipment - Part 2: Circuit Breaker -
Appendix N.
The above tests can ensure that the circuit breaker won't wrongly occur tripping.

5.2 Installation Conditions


With the vertical gradient no more than 5°, the circuit breaker shall be installed under the environment
condition without explosion danger, conductive dust or the possibility of corroding metal and damaging the
insulation.
5.2.1 Installation category
The circuit breaker's main circuit and undervoltage release coils, power transformer primary coil
installation category is IV; the rest auxiliary circuit and control circuit installation category is III.
5.2.2 Protection class
IP30 and IP40 (installed in a cubicle and equipped with a protective door frame).
5.2.3 Utilization category
Category B.
5.3 Main Circuit Wiring of the Circuit Breaker
Main Circuit Wiring of the Circuit Breaker
Copper bar specification
Rated current of frame Inm (A) Rated operating current In(A) 40℃
Dimension (mm) Number
200 20×5 1
400 50×5 1
630 40×5 2
1600 800 50×5 2
1000 40×5 3
1250 40×5 4
1600 50×10 2
630 80×5 1
800, 1000 80×5 2019.11.27 2
试制
2500 1250 80×5 3
1600 80×5 3
2000 80×10 2
2500 80×10 3
800~1600 80×5 3
2000 80×10 2
4000
2500 80×10 3
3200, 4000 100×10 5
4000 100×10 5
6300
5000, 6300 100×10 6

Internal & confidential file Page 65 of 117


NDT2920213 Document Version: 3

Note: 1. The table indicates the copper bar specifications adopted when the circuit breaker is under the ambient temperature of 40℃
and the open wide installation under the heating condition meets the stipulation in GB/T14048.2. If the temperature is higher than
40℃, the quantity of copper bar should be increased, or the capacity should be reduced.
2. The above data is calculated according to the test and theory, and for reference only.
3. The maximum permissible temperature of the copper bar is no more than +110℃.
4. The electrical gap of copper bar is ≥15mm with the altitude more than 5, 000m and relative humidity more than 90%; the
electrical gap shall be adjusted according to the table 1 of 7.1.1in the sdandard GB/T 20645.

5.4 The power loss of the incoming and outgoing lines of the circuit breaker (ambient
temperature +40℃)
The power loss2019.11.27
of the incoming and outgoing lines of the circuit breaker
试制
Model Power loss of the fixed type Power loss of the drawout type

NDW3-1600 ≤123.5 W ≤331.5 W

NDW3-2500 ≤356.8W ≤823.4 W

NDW3-4000 ≤486.7W ≤856.8 W

NDW3-6300 ≤787 W ≤1145W

Internal & confidential file Page 66 of 117


NDT2920213 Document Version: 3

Chapter 6 Outline and Installation Dimensions


6.1 NDW3-1600 .......................................................................................................................... 68
6.2 NDW3-2500 .......................................................................................................................... 72
6.3 NDW3-4000 .......................................................................................................................... 78
6.4 NDW3-6300 .......................................................................................................................... 84
6.5 The Circuit Breaker Cabinet Door Open Hole and the Installation Pitch ............................. 90
6.6 Circuit Breaker Installation Notes......................................................................................... 91

2019.11.27
试制

Internal & confidential file Page 67 of 117


NDT2920213 Document Version: 3

6.1 NDW3-1600
NDW3-1600 fixed type (unit: mm)
Dimensions Fixed Details

cabinet door

2019.11.27
试制

Horizontal Wiring Detail

Vertical Wiring Detail

Note: For the 3-pole circuit breaker, X and Y are the Rated current Size of busbar a (mm)
symmetric axes of the front panel; 200A, 400A, 630A 10

800A, 1000A, 1200A, 1600A 15

Internal & confidential file Page 68 of 117


NDT2920213 Document Version: 3

Mixed Wiring (Upper Horizontal, Lower Vertical) Detail

Mixed Wiring (Upper Vertical, Lower Horizontal) Detail

Note: For the 3-pole circuit breaker, X and Y are the Rated current Size of busbar a (mm)
symmetric axes of the front panel; 200A, 400A, 630A 10

800A, 1000A, 1200A, 1600A 15

2019.11.27
试制

Internal & confidential file Page 69 of 117


NDT2920213 Document Version: 3

NDW3-1600 drawout type (unit: mm)


Dimensions Fixed Details

cabinet door

2019.11.27
试制

Horizontal Wiring Detail

Vertical Wiring Detail

Note: For the 3-pole circuit breaker, X and Y are the Rated current Size of busbar a (mm)
symmetric axes of the front panel; 200A, 400A, 630A 10

800A, 1000A, 1200A, 1600A 15

Internal & confidential file Page 70 of 117


NDT2920213 Document Version: 3

Mixed Wiring (Upper Horizontal, Lower Vertical) Detail

Mixed Wiring (Upper Vertical, Lower Horizontal) Detail

Note: For the 3-pole circuit breaker, X and Y are the Rated current Size of busbar a (mm)
symmetric axes of the front panel; 200A, 400A, 630A 10

800A, 1000A, 1200A, 1600A 15

2019.11.27
试制

Internal & confidential file Page 71 of 117


NDT2920213 Document Version: 3

6.2 NDW3-2500
NDW3-2500 fixed type (unit: mm)
Dimensions Fixed Details

cabinet door

2019.11.27
试制

Horizontal Wiring Detail

Vertical Wiring Detail

Note: For the circuit breaker, X and Y are the symmetric axes Size of busbar a
Rated current
of the front cover; (mm)

630A, 800A, 1000A, 1250A 15

1600A, 2000A, 2500A 20

Internal & confidential file Page 72 of 117


NDT2920213 Document Version: 3

Mixed Wiring (Upper Horizontal, Lower Vertical) Detail

Mixed Wiring (Upper Vertical, Lower Horizontal) Detail

Horizontal Extended Wiring Detail

2019.11.27
Note: For the circuit breaker, X and Y are the symmetric axes Rated current 试制 Size of busbar a (mm)
of the front cover; 630A, 800A, 1000A, 1250A 15

1600A, 2000A, 2500A 20

Internal & confidential file Page 73 of 117


NDT2920213 Document Version: 3

Vertical Extended Wiring Detail

2019.11.27
试制

Mixed Wiring (Upper Horizontal, Lower Vertical) Detail

Mixed Wiring (Upper Vertical, Lower Horizontal) Detail

Note: For the circuit breaker, X and Y are the symmetric axes Rated current Size of busbar a (mm)
of the front cover; 630A, 800A, 1000A, 1250A 15

1600A, 2000A, 2500A 20

Internal & confidential file Page 74 of 117


NDT2920213 Document Version: 3

NDW3-2500 drawout type (unit: mm)


Dimensions Fixed Details

cabinet door

50 min.

Horizontal Wiring Detail

Vertical Wiring Detail

2019.11.27
Note: For the circuit breaker, X and Y are the symmetric axes Rated current 试制 Size of busbar a (mm)
of the front cover; 630A, 800A, 1000A, 1250A 15

1600A, 2000A, 2500A 20

Internal & confidential file Page 75 of 117


NDT2920213 Document Version: 3

Mixed Wiring (Upper Horizontal, Lower Vertical) Detail

2019.11.27
试制

Mixed Wiring (Upper Vertical, Lower Horizontal) Detail

Horizontal Extended Wiring Detail

Note: For the circuit breaker, X and Y are the symmetric axes Rated current Size of busbar a (mm)
of the front cover; 630A, 800A, 1000A, 1250A 15

1600A, 2000A, 2500A 20

Internal & confidential file Page 76 of 117


NDT2920213 Document Version: 3

Vertical Extended Wiring Detail

Mixed Wiring (Upper Horizontal, Lower Vertical) Detail

Mixed Wiring (Upper Vertical, Lower Horizontal) Detail

Note: For the circuit breaker, X and Y are the symmetric axes Rated current Size of busbar a (mm)
of the front cover; 630A, 800A, 1000A, 1250A 15

1600A, 2000A, 2500A 20

2019.11.27
试制

Internal & confidential file Page 77 of 117


NDT2920213 Document Version: 3

6.3 NDW3-4000
NDW3-4000 fixed type (unit: mm)
Dimensions Fixed Details

Direction A

cabinet door

2019.11.27
试制

800A-2500A Horizontal and Vertical Wiring Detail

Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;

Internal & confidential file Page 78 of 117


NDT2920213 Document Version: 3

800A-2500A Horizontal Extended and Vertical Extended Wiring Detail

3200A-4000A Horizontal Wiring Detail

2019.11.27
试制

Note: X and Y axes are the symmetric axes of the front mask;

Internal & confidential file Page 79 of 117


NDT2920213 Document Version: 3

3200A-4000A Vertical Wiring Detail

2019.11.27
试制

3200A-4000A Horizontal Extended and Vertical Extended Wiring Detail

Note: X and Y axes are the symmetric axes of the front mask;

Internal & confidential file Page 80 of 117


NDT2920213 Document Version: 3

NDW3-4000 drawout type (unit: mm)


Dimensions Fixed Details
Direction A

cabinet door

50 min.

800A-2500A Horizontal and Vertical Wiring Detail

2019.11.27
试制

Internal & confidential file Page 81 of 117


NDT2920213 Document Version: 3

800A-2500A Horizontal Extended and Vertical Extended Wiring Detail

2019.11.27
试制

3200A-4000A Horizontal Wiring Detail

Note: X and Y axes are the symmetric axes of the front mask;

Internal & confidential file Page 82 of 117


NDT2920213 Document Version: 3

3200A-4000A Vertical Wiring Detail

3200A-4000A Horizontal Extended and Vertical Extended Wiring Detail

2019.11.27
试制

Note: X and Y axes are the symmetric axes of the front mask;

Internal & confidential file Page 83 of 117


NDT2920213 Document Version: 3

6.4 NDW3-6300
NDW3-6300 fixed type (unit: mm)
Dimensions Fixed Details
Direction A

Direction A

cabinet door

2019.11.27
试制

4000A-5000A Horizontal, Vertical and Mixed Wiring


Horizontal Wiring Detail

Vertical Wiring Detail

Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;

Mixed Wiring (Upper Horizontal, Lower Vertical) Detail

Mixed Wiring (Upper Vertical, Lower Horizontal) Detail

Internal & confidential file Page 84 of 117


NDT2920213 Document Version: 3

4000A-5000A Horizontal Extended, Vertical Extended and Mixed Extended Wiring


Horizontal Extended Wiring Detail

Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;

Vertical Extended Wiring Detail

Mixed Wiring (Upper Horizontal, Lower Vertical) Detail

Mixed Wiring (Upper Vertical, Lower Horizontal) Detail

2019.11.27
试制

Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;

Internal & confidential file Page 85 of 117


NDT2920213 Document Version: 3

6300A Vertical Wiring Detail

Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;
2019.11.27
试制

6300A Vertical Wiring Detail

Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;

Internal & confidential file Page 86 of 117


NDT2920213 Document Version: 3

NDW3-6300 drawout type (unit: mm)


Dimensions Fixed Details
Direction A
Direction A
cabinet door

50 min.
Direction A

4000A-5000A Horizontal, Vertical and Mixed Wiring


Horizontal Wiring Detail

Vertical Wiring Detail

Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;

2019.11.27
试制

Internal & confidential file Page 87 of 117


NDT2920213 Document Version: 3

Mixed Wiring (Upper Horizontal, Lower Vertical) Detail

Mixed Wiring (Upper Vertical, Lower Horizontal)


2019.11.27 Detail
试制

4000A-5000A Horizontal Extended, Vertical Extended and Mixed Extended Wiring


Extended Horizontal Wiring Detail

Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;

Extended Vertical Wiring Detail

Internal & confidential file Page 88 of 117


NDT2920213 Document Version: 3

Mixed Wiring (Upper Horizontal, Lower Vertical) Detail

Mixed Wiring (Upper Vertical, Lower Horizontal) Detail

Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;

6300A Vertical Wiring Detail

Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;

6300A Extended Vertical Wiring Detail

Note: For the circuit breaker, X and Y are the symmetric axes of the front cover;

2019.11.27
试制

Internal & confidential file Page 89 of 117


NDT2920213 Document Version: 3

6.5 The Circuit Breaker Cabinet Door Open Hole and the Installation Pitch
Hole dimensions of NDW3-1600 door frame (unit: mm)

2019.11.27
Mask center Mask center
试制

Circuit breaker undersurface


Fixed type Drawout type

Hole dimensions of NDW3-2500 door frame (unit: mm)

Mask center
Mask center

Circuit breaker undersurface


Fixed type
Drawout type

Hole dimensions of NDW3-4000 door frame (unit: mm)

Internal & confidential file Page 90 of 117


NDT2920213 Document Version: 3

Mask center
Mask center

Circuit breaker undersurface

Fixed type Drawout type


Hole dimensions of NDW3-6300 door frame (unit: mm)

Mask center

Mask center

Circuit breaker undersurface


Fixed type Drawout type

6.6 Circuit Breaker Installation Notes


To ensure the safety of you and the electric equipment, before put the circuit breaker into operation, users
must:
★ Carefully read the Operation Manual before installation and use of the circuit breaker.
★ Check whether the specification of the circuit breaker is in line with the requirements before
installation.
★ Install the circuit breaker under the environment condition without explosion danger, conductive dust
or the possibility of corroding metal and damaging the insulation. 2019.11.27
试制
★ Measure the insulation resistance of the circuit breaker with a 1000V megohmmeter before
installation of the circuit breaker. When the surrounding medium temperature is 20℃±5℃, the
relative humidity 50%-70% should not be less than 20 mge; otherwise it needs to be dried, and it can
be used until the insulation resistance meets the requirements.
★ Prevent foreign matters from falling into the circuit breaker when installing the circuit breaker.
★ Ensure the circuit breaker is flat without additional mechanical stress when installing the conductive
busbar.

Internal & confidential file Page 91 of 117


NDT2920213 Document Version: 3

★ Conduct reliable grounding protection when installing the circuit breaker. The grounding place of the
circuit breaker has an obvious grounding symbol.
★ Carry out wiring of the control circuit according to the wiring diagram when installing the circuit
breaker; check whether the working voltage of the undervoltage, shunt, closed electromagnet, motor,
controller and related parts conforms to the actual voltage, and then carry out the secondary circuit
energizing. In case of drawout circuit breaker, the circuit breaker should be shaken into the test
position, then the undervoltage release will close and then the circuit breaker can be closed.
★ Pressing (or powering on) the closing button after the energy storage of the motor, the circuit breaker
will close.
★ Pressing (or powering on) the
2019.11.27
opening button, the circuit breaker will open.
试制
★ For manual storage of energy, pull the handle on the front panel up and down, when a "click" sound
can be heard after seven times; the panel shows "storage of energy", and the storage of energy ends.
At this point, if there's undervoltage tripping, power on it (no need if without undervoltage tripping),
then carry out closing operation.
★ Installation screws of the circuit breaker is shown in the table below
Installation Screws of the Circuit Breaker
Circuit breaker Connection conditions between bus and terminal
NDW3-1600 M10 bolt, level 8.8, with contact washer, tightening torque 45N.m
NDW3-2500 M12 bolt, level 8.8, with contact washer, tightening torque 60N.m
800-2500A M12 bolt, level 8.8, with contact washer, tightening torque 60N.m
NDW3-4000
3200-4000A M14 bolt, level 8.8, with contact washer, tightening torque 97N.m
Extended vertical wiring M12 bolt, level 8.8, with contact washer, tightening torque 60N.m
NDW3-6300
Other wiring modes M14 bolt, level 8.8, with contact washer, tightening torque 97N.m
The circuit breaker is installed in the cabinet, the safe distance between the circuit breaker and the
cabinet
When users install the circuit breaker into the cabinet, the safe distance between the circuit breaker and
the cabinet is shown in the figure below, and the installation dimensions are shown in the table below.

Drawout circuit breaker Fixed circuit breaker


Unit: mm
Installation mode of the To the insulator To the grounded metallic body To the live part
circuit breaker A B A B A B
Drawout type 0 0 0 0 60 60
Fixed type 0 0 0 0 60 60
Note: 1. 150 mm space needed for removing the arc-extinguishing chamber should be considered for the safe spacing of the fixed
type circuit breaker;
2. If dust cover is added, height space of 70 mm for installation and rotating of the dust cover should be considered.

Internal & confidential file Page 92 of 117


NDT2920213 Document Version: 3

Chapter 7 Electrical Wiring Diagram


7.1 NDW3-1600 Electrical Wiring Diagram and Terminal Number Definition ......................... 94
7.2 NDW3-2500/6300 Electrical Wiring Diagram and Terminal Number Definition................ 98
7.3 NDW3-4000 Electrical Wiring Diagram and Terminal Number Definition ....................... 102
7.4 Electrical Wiring Diagram of Check-for-voltage Closing Device ...................................... 106
7.5 Wiring Diagram of the Power Automatic Switching Device (ATS) ................................... 106

2019.11.27
试制

Internal & confidential file Page 93 of 117


NDT2920213 Document Version: 3

7.1 NDW3-1600 Electrical Wiring Diagram and Terminal Number Definition


The following diagram is the NDW3-1600 full-function wiring diagram

2019.11.27
试制

Internal & confidential file Page 94 of 117


NDT2920213 Document Version: 3

The following diagram is the input/output interface of NDW3-1600 controller

2019.11.27
试制

Internal & confidential file Page 95 of 117


Wiring terminal line number
备注
Function 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 45~62
Users only need to
connect the power supply
Working power supply to the input end of the
power supply module.
Contact capacity of
Fault tripping
7# public end:
indication contac
AC250V/16A
Contact capacity of

Internal & confidential file


Opening and closing
4# public end:
indication contact
AC250V/16A
Closing ready electric indicator
Four groups of optional
signal unit outputs
Shunt output with
试制

break monitoring
2019.11.27

Closing output with


break monitoring
Grounding wire of controller
Three-phase three-wire
Voltage signal input ends
system: 21#23# shall be
(N, A, B, C) short connected to U2
NDT2920213

Under-voltage release break


monitoring output
N-pole transformer

Page 96 of 117
output (3P+N)
Current leakage transformer
output end
Remote reset function
input end
Definition table of NDW3-1600 terminal number is shown in the following table

Energy-storing signal
unit output
Communication interface
Electric energy storage and
energy storage indicators
Undervoltage release
Loss of voltage release
Shunt release
Closed electromagnet
Document Version: 3

Connecting terminals of
auxiliary switch
NDT2920213 Document Version: 3

Note:

1. The current state of the circuit breaker is de-energized, disconnected, connected, no energy stored;
2. The dashed part shall be wired by users;
3. When the power supply of Q, F, B, M, controllers is not the same, they shall be powered on respectively;

4. Each terminal number can only be used once;


5. The secondary terminal wiring is only suitable for the 0.5-1.5mm2 multi-strand soft wire or hard wire with the soft wire

recommended; pay attention to adopt the appropriate conductor.


6. Terminal number 39~45 - user-defined.

7. All the signal units are passive signals. Users can choose S1, S2, S3 modes as required.

SB1 - Shunt button (to be prepared by users); SB2 - Close button (to be prepared by users);
SB3 - Remote reset button (to be prepared by users); SA1 - Motor travel switch;

SA2 - Closing ready travel switch; SA4 - Fault tripping travel switch;
SA5 - Opening and closing indicating travel switch;

XT - Secondary terminal; F - Shunt release;


B - Closed electromagnet; Q - Undervoltage release or loss of voltage release (instantaneous or delayed);

YF - Remote reset; Fu - Fuse (to be prepared by users);

M - Energy storage motor.


Appendix: NDW3-1600 Auxiliary Wiring Diagram

Four-group switch contacts Six-group switch contacts


2019.11.27
试制

Internal & confidential file Page 97 of 117


Configuration of additional communication functions

ST power
ST power
supply supply module
module IV IV

Device-net protocol

Internal & confidential file


To be wired at the user Profibus-DP protocol
side
Message notification
ST201 relay
module module
Modbus protocol

试制
2019.11.27

Motor Energy
energy storage Undervoltage Electric Electric Closing ready Remote reset
Main power supply Controller storage indicator off opening closing Auxiliary switch

Green

Fault Open Close


NDT2920213

Page 98 of 117
Optional function
Power supply
The following diagram is the NDW3-2500 and NDW3-6300 full-function wiring diagram

Red
Document Version: 3

7.2 NDW3-2500/6300 Electrical Wiring Diagram and Terminal Number Definition


NDT2920213 Document Version: 3

The following diagram is the input/output interface of NDW3-2500 and NDW3-6300 controller

Connected to the power inlet side

Working power supply


Voltage measurement
input end

Controller

Communication
interface Signal unit

N-phase external
transformer

12、13——signal contactor 1,contactor capacity:AC250V/5A;DC110V/0.5A,additional function;We cannot choose both

it and check-for-voltage closing device.

14、15——signal contactor 1,contactor capacity:AC250V/5A;DC110V/0.5A,additional function;We cannot choose both

it and check-for-voltage closing device.

2019.11.27
试制

Internal & confidential file Page 99 of 117


NDT2920213 Document Version: 3

Definition table of NDW3-2500 and NDW3-6300 terminal number is shown in the following table

2019.11.27
试制

Internal & confidential file Page 100 of 117


NDT2920213 Document Version: 3

Note:
1. The current state of the circuit breaker is de-energized, disconnected, connected, no energy stored;

2. The dashed part shall be wired by users;


3. When the power supply of Q, F, B, M, controllers is not the same, they shall be powered on respectively;

4. Each terminal number can only be used once;


5. The secondary terminal wiring is only suitable for the 0.5-1.5mm2 multi-strand soft wire or hard wire with the soft wire

recommended; pay attention to adopt the appropriate conductor.


6. All the signal units are passive signals. Users can choose S1, S2, S3 modes as required.

7. To realize “four-remote” functions, clients should choose signal unit, and add power source module and relay module.
8. When choose check-for-voltage closing device, electrical wiring diagram of closed electromagnet and under-voltage trip

controlled by check-for-voltage is seen in the check-for-voltage electrical wiring diagram of appendix.


9. Check-for-voltage closing device is an appropriative accessory of NDW3-2500.

SB1 - Shunt button (to be prepared by users); SB2 - Close button (to be prepared by users); SB3 - Remote reset button (to be
prepared by users);

SA1 - Motor travel switch; SA2 - Closing ready travel switch; SA4 - Fault tripping travel switch;
SA5 - Opening and closing indicating travel switch;

XT - Secondary terminal; F - Shunt release; B - Closed electromagnet;


Q - Undervoltage release or loss of voltage release (instantaneous or delayed);

YF - Remote reset; Fu - Fuse (to be prepared by users); M - Energy storage motor.

Appendix: NDW3-2500/6300 Auxiliary Wiring Diagram

Four normally opened and Five normally opened and 2019.11.27


Six normally opened and six
four normally closed five normally closed 试制closed
normally

Internal & confidential file Page 101 of 117


Configuration of additional communication functions

ST power
supply module
IV
ST power
supply module
IV

Device-net protocol

Internal & confidential file


To be wired at the user Profibus-DP protocol
side
Message notification
module
ST201 relay module

Modbus protocol

试制
2019.11.27

Motor Energy Undervoltage Electric Electric Remote


Main power supply energy storage Closing ready
Controller storage indicator off opening closing reset Auxiliary switch

Green

Fault Open Close


NDT2920213

Page 102 of 117


The following diagram is the NDW3-4000 full-function wiring diagram

Optional function
Power supply

Red
7.3 NDW3-4000 Electrical Wiring Diagram and Terminal Number Definition
Document Version: 3
NDT2920213 Document Version: 3

The following diagram is the input/output interface of NDW3-4000 controller


Connected to the power inlet side

Remote reset

Working power supply


Voltage measurement
input end

Controller

Communication
interface Signal unit

N-phase external
transformer

2019.11.27
试制

Internal & confidential file Page 103 of 117


Wiring terminal line number
备注
Function 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 45~62
Working power supply
Users only need to
connect the power
Fault tripping
supply to the input end
indication contac of the power supply
module.
Contact capacity of
Opening and closing
7# public end:
indication contact

Internal & confidential file


AC250V/16A
Closing ready electric indicator
Four groups of optional
signal unit outputs
Shunt output with
break monitoring
试制

Closing output with


2019.11.27

break monitoring
Grounding wire of controller
Three-phase three-wire
Voltage signal input ends
system: 21#23# shall be
(N, A, B, C) short connected to U2
NDT2920213

Under-voltage release break


monitoring output
N-pole transformer
output (3P+N)

Page 104 of 117


Current leakage transformer
output end
Remote reset function
input end
Energy-storing signal
unit output
Definition table of NDW3-4000 terminal number is shown in the following table

Communication interface
Electric energy storage and
energy storage indicators
Undervoltage release
Loss of voltage release
Shunt release
Closed electromagnet
Document Version: 3

Connecting terminals of
auxiliary switch
NDT2920213 Document Version: 3

Note:
1. The current state of the circuit breaker is de-energized, disconnected, connected, no energy stored.

2. The dashed part shall be wired by users.


3. Power supply - when Q, F, B, M, controllers power supply is not the same, they shall be powered on respectively.

4. Each wiring terminal number can only be used once.


5. The secondary terminal wiring is only suitable for the 0.5-1.5mm2 multi-strand soft wire or hard wire with the soft wire

recommended; pay attention to adopt the appropriate conductor.


6. Terminal number 41~44 - user-defined.

7. All the signal units are passive signals. Users can choose S1, S2, S3 modes as required.

SB2 - Undervoltage button (to be prepared by users); SB5 - Remote reset button (to be prepared by users);
SA1 - Motor travel switch; SA2 - Closing ready travel switch; SA2 - Closing ready travel switch;

SA3 - Undervoltage indicating travel switch; SA4 - Fault tripping travel switch;
SA5 - Opening and closing indicating travel switch; XT - Secondary terminal; F - Shunt release;

B - Closed electromagnet; Q - Undervoltage release or loss of voltage release (instantaneous or delayed); YF - Remote reset;
T - Auxiliary contact of the circuit breaker (see attached figure); Fu - Fuse (to be prepared by users); M - Energy

storage motor.

Appendix: NDW3-4000 Auxiliary Wiring Diagram

Four-group switch contacts Four normally opened and Six-group switch contacts
four normally closed

2019.11.27
试制

Internal & confidential file Page 105 of 117


NDT2920213 Document Version: 3

7.4 Electrical Wiring Diagram of Check-for-voltage Closing Device


Power Power
Source Source

Secondary
Terminals of
Circuit Breaker

Check-for-voltage Closing Device


2019.11.27
试制

Check-for-voltage
Wiring Harness
(Optional)

1)6、7——The check-for-voltage closing device need to monitor the state of circuit breaker, and clients should
make a choice between it and circuit open contactors output function.
Note: Check-for voltage module’s 6 and 7terminals should be connected to without-power normally closed
contactors;
2)12、13 和 14、15——Choose one of appropriative under-voltage trip controlled by check-for-voltage closing
device, PV appropriative under-voltage (voltage-loss) trip (adjustable from 0~10s) and signal unit function;
3)33、34——Check-for-voltage closing device power source is the same to common under-voltage trip power
source, and clients can wire according to practical requirements, and only AC220V/230V、AC380V/AC400V
power source can be allowed to connect.
4)37、38——When choose check-for-voltage closing device function, the closed electromagnet will be 37 and 38,
and turn closing voltage rotary button of check-for-voltage closing device to non-off state, the closed
electromagnet will be controlled by check-for-voltage closing device automatically, and a to b wires are suggested
not to be connected.
5)If only take controlling closed electromagnet manually, we should turn off closing voltage rotary button of
check-for-voltage closing device module, and connect a to b wires including SB2.
6)If clients do not choose check-for-voltage closing device, and the closed electromagnet is still 37 and 38, then
they should wire according to general electrical wiring diagram of ACB.
7)6, 7, 12, 13, 14, 15, 38 should be connected to corresponding secondary terminals by wiring harness.
8)The imaginary line is wiring of clients, and real line is internal wiring of products.

Internal & confidential file Page 106 of 117


NDT2920213 Document Version: 3

7.5 Wiring Diagram of the Power Automatic Switching Device (ATS)


7.5.1 Wiring diagram of the power automatic switching device (ATS) of
NDW3-1600

2019.11.27
试制

Internal & confidential file Page 107 of 117


NDT2920213 Document Version: 3

7.5.2 Wiring diagram of the power automatic switching device (ATS) of


NDW3-2500 & NDW3-4000& NDW3-6300

2019.11.27
试制

Internal & confidential file Page 108 of 117


NDT2920213 Document Version: 3

Chapter 8 Ordering Type Selection Specification


8.1 NDW3 Series of Circuit Breaker Model Explanation and Encoding Rules错误!未定义书签。
8.2 Order Specifications ................................................................................. 错误!未定义书签。

2019.11.27
试制

Internal & confidential file Page 109 of 117


NDT2920213 Document Version: 3

Ordering Type Selection Specification 8


8.1 NDW3 Series of Circuit Breaker Model Explanation and Encoding Rules
ND W 3- □ □/□ □/□/□ □ /□ □ □/□ □ □ □/□/□/□/□/□
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
SN Name Specification, type code Description

Enterprise
1 brand low-voltage electrical appliance
code
2019.11.27
2 Product code Air circuit breaker 试制

3 Design SN 3

Shell frame
4 16-1600, 25-2500, 40-4000, 63-6300
level

NDW3-1600 is only

available with one


5 Breaking type S-Conventional breaking level, H-High breaking level, HU-High voltage level
breaking type, which is

not to write in default

02-200A, 04-400A, 06-630A, 08-800A, 10-1000A, 12-1250A, 16-1600A,


6 Rated current
20-2000A, 25-2500A, 32-3200A, 40-4000A, 50-5000A, 63-6300A

Installation
7 Non-marked - fixed type, C - drawout type
structure

Number of 3P+N: 3P products are


8 3-3 poles, 4-4 poles, 5-3P+N
poles added with N-phase

KM1-NWK21/NWK31 (AC380V/AC400V), external transformers

KM2-NWK21/NWK31 (AC220V/AC230V),

KM3-NWK21/NWK31 (DC220V), NWK31 and NWK32 are


KM4-NWK21/NWK31 (DC110V), applicable to
KM5-NWK21/NWK31 (DC24V) NDW3-1600 controllers
9 Controller
KY1-NWK22/NWK32 (AC380V/AC400V), while NWK21 and

KY2-NWK22/NWK32 (AC220V/AC230V), NWK22 are applicable

KY3-NWK22/NWK32 (DC220V), to the rest

KY4-NWK22/NWK32 (DC110V),

KY5-NWK22/NWK32 (DC24V)

Internal & confidential file Page 110 of 117


NDT2920213 Document Version: 3

Continued:
Protection type: Not-standard - conventional type, V - voltage measurement and
protection, P - harmonic measurement and protection
Communication function: H (Modbus protocol) MP (Profibus-DP protocol) 1. This shall be
MD (Devicenet protocol) DXX-Message notification module omitted
Signal unit: S1- 4DO S2- 3DO, 1DI S3-2DO, 2DI if the controller has

Remote reset function: Z1(AC380V/AC400V), Z2(AC220V/AC230V), no optional function;

Z3(DC220V), Z4(DC110V), Z5DC(24V) NWK21/NWK31


controller only has
3P+N grounding mode (optional for the external N-pole transformer): T -
S1-4DO;
Differential type (not to write in default) W - Ground current type
2. Z1 is not available
N1 - External N-phase transformer
Applicable to NDW3-1600 with the
(62*21)
NDW3-1600 remote
N2 - External N-phase transformer
Controller Applicable to NDW3-1600/2500 reset function;
(102*32.5)
10 Optional 3. Choose one from
N3 - External N-phase transformer
function Applicable to NDW3-2500/4000/6300 the communication
(122*52)
functions of “H”,
N4 - External N-phase transformer
Applicable to NDW3-2500/4000/6300 “MP”, “MD” and
(262*102)
“DXX”;
NR1 - External flexible transformer
Applicable to 200A-800A 4. For the controller
(280mm)
with “V” and
NR2 - External flexible transformer
Applicable to 1000A-2000A “P”functions, the
(370mm)
voltage module P2 is
NR3 - External flexible transformer
Applicable to 1000A-6300A optional for the main
(450mm)
circuit rated voltage
Protection form of current leakage: E-type (including the external current leakage above AC800V.
transformer)
Contact wear equivalent, operation times query (NWK21/31 optional): J
Electric energy
D1-AC380V/AC400V, D2-AC220V/AC230V,
11 storage
D3-DC220V, D4-DC110V, D5-DC24V
mechanism
F1-AC380V/AC400V, F2-AC220V/AC230V,
12 Shunt release
F3-DC220V, F4-DC110V, F5-DC24V
Closed B1-AC380V/AC400V, B2-AC220V/AC230V,
13
electromagnet B3-DC220V, B4-DC110V, B5-DC24V
1. One out three of the
Under-voltage release: Q1-AC380V/AC400V, Q2-AC220V/AC230V,
under-voltage release,
Q3-DC220V, Q4-DC110V, Q5-DC24V
Under-voltage loss of voltage release
release/loss of and voltage-check
voltage Loss of voltage release: S1-AC380V/AC400V, S2-AC220V/AC230V closing device
14
release/voltage- 2. To be selected
2019.11.27
check closing 试制 during ordering; this
device shall be omitted if
Voltage-check release: J1-AC380V/AC400V, J2-AC220V/AC230V without this
accessory
3. The special
under-voltage
release and closed
electromagnet
controlled by the
voltage-check
Internal & confidential file Page 111 of 117
closing device are
internal accessories,
while the
NDT2920213 Document Version: 3

Continued:
3. The special
under-voltage
Conventional undervoltage delay: 0-Instantaneous, 1-1s delay, 3-3s delay, 5-5s delay
release and closed
electromagnet
controlled by the
Under-voltage NDW3-1600/6300 loss of voltage: 0s~10s adjustable by users (the factory default voltage-check
release/loss of setting value is 3s), with a step of 1s; closing device are
voltage release
15 internal accessories,
Delay
2019.11.27 while the
time/voltage-ch 试制
NDW3-2500/4000 loss of voltage delay: 1-1s delay, 3-3s delay, 5-5s delay voltage-check
eck harness
closing controller
module is the
external accessory
0- Without harness, 1 - With harness
(applicable to
NDW3-2500)
Applicable to
Not-marked - four groups conversion, A6 - six groups conversion
NDW3-1600
Applicable to
Auxiliary Not marked - Four opened and four closed, A55 - Five opened and five closed, A66 -
16 NDW3-2500
contact Six opened and six closed
and NDW3-6300
Not-marked - Four groups conversion, A6 - Six groups conversion, A44 - Four Applicable to
opened and four closed NDW3-4000

BX - Closing ready signal output unit

JS - Counter functional unit This shall be omitted


Internal
17 CM1 - Drawout type (with the right side of the door interlock); CM2 - Drawout type if without this
Accessories
(with the left side of the door interlock) accessory

CX - Drawer seat three-position signal output

Internal & confidential file Page 112 of 117


NDT2920213 Document Version: 3

Continued:
1. Power supply module,
M - Doorframe
relay module, external
current leakage
transformer,
F - Dust cover
programmable output
module, message
R - Relay module module, communication
adapter and N-pole
external transformer
P - Power supply module (in line with the controller voltage in default)
should be used with the
controller;
2. Carry out the
S - Button lock
sequence arrangement
according to the table,
External BC - Programmable output module (6-channel) with “/” for separation;
18
accessories 3. The accessory
IO1 - Remote I/O module C8 monitoring unit can’t be
selected with the
IO2 - Remote I/O module S12
communication function,
signal unit and controller
IO3 - Remote I/O module SC64
with “V” and “P”
IO4 - Remote I/O module SCM423 functions
simultaneously;
AM - Accessory monitoring unit 4. The energy-storing
signal communication
module component can’t
P2 - Voltage conversion module
be selected with the
controller with “V” and
“P” functions
TC - Energy-storing signal communication module component
simultaneously.

Not marked - Horizontal wiring, J1 - Horizontal extended wiring, J3 Vertical NDW3-6300 with the
wiring, J4 - Vertical extended wiring rated current of 6300A
J5 - Mixed wiring (upper horizontal, lower vertical), J6 - Mixed wiring (upper only has two wiring
19 Wiring mode
vertical, lower horizontal) modes: Vertical wiring
J7 - Mixed extended wiring (upper horizontal and lower vertical), J8 - Mixed
2019.11.27
and vertical extended
extended wiring (upper vertical and lower horizontal) 试制 wiring.
Product usage
20 Not-marked - Conventional, TH - Thermal and humidity
type
21 Special notes Customer’s special requirements
Rated working Not-marked - AC690V and below, KV4-AC800V, KV5-AC1000V,
22
voltage KV6-AC1140V

Internal & confidential file Page 113 of 117


NDT2920213 Document Version: 3

Interlocking Accessory Model Explanation and Encoding Rules

SF11 - key lock device (one lock and one key), SF21 - key lock device (two locks and one
key),
Key lock SF31 - key lock device (three locks and one key), SF32 - key lock device (three locks and 1. Select one from five
two keys), key locks;
SF53 - key lock device (five locks and three keys) 2. Select one from five
SR11 - Mechanical interlocking device (two sets of steel cables, one for closing and one for mechanical interlocks;
opening) 3. SR21 and SR12 are
2019.11.27
SR12 - Mechanical interlocking试制
device (three sets of steel cables, one for closing and two only applicable to the
for opening) NDW3-2500 frame and
Mechanical SR21 - Mechanical interlocking device (three sets of steel cables, two for closing and one above;
interlocking for opening) 4. NDW3-1600 fixed type
SY11 - Mechanical interlocking device (two sets of hard rods, one for closing and one for is not provided with a
opening) mechanical interlock.
SY12 - Mechanical interlocking device (three sets of hard rods, one for closing and two for
opening)
1. It is standard with a
mechanical interlock
Power
with the type selected by
automatic ATS-R/S/F (R: Auto switch and auto recover; S: Auto switch and non-auto recover; F:
customers;
switching Mains - Generator)
2. NDW3-1600 fixed
device
type is not provided with
this accessory.

Internal & confidential file Page 114 of 117


NDT2920213 Document Version: 3

8.2 Order Specifications


(Please fill in numbers in_____, and check √ in □. Related contents can be found in the Manual)

Number of units
User unit Date of ordering:
ordered:
Shell frame □ NDW3-1600 □ NDW3-2500 □ NDW3-4000 □ NDW3-6300
level
Installation
□ Fixed type □ C - Drawout type
structure
NDW3-1600: □200 □400 □630 □800 □1000 □1250 □1600
Rated current NDW3-2500: □630 □800 □1000 □1250 □1600 □2000 □2500
(A) NDW3-4000: □800 □1000 □1250 □1600 □2000 □2500 □3200 □4000
NDW3-6300: □4000 □5000 □6300
□ S-Conventional breaking (AC690V and below) □ H-High breaking (AC690V and below)
□ HU-High voltage breaking (AC800V) □ HU-High voltage breaking (AC1000V)
Breaking type
□ HU-High voltage breaking (AC1140V)

Ba Note: These options are not distinguished with NDW3-1600, no selection required

sic Number of
□ 3 (3 poles) □ 4 (4 poles) □ 5(3P+N)
par poles
a □ Horizontal wiring (standard configuration) □ J3 - Vertical wiring
me NDW3-1600 □ J5 - Mixed wiring (upper horizontal and lower vertical) □ J6 - Mixed wiring
ters (upper vertical and lower horizontal)
□ Horizontal wiring (standard configuration) □ J1 - Horizontal extended wiring □ J3 -
NDW3-2500 Vertical wiring □ J4 - Vertical extended wiring □ J5 - Mixed wiring (upper
horizontal, lower vertical) □ J6 - Mixed wiring (upper vertical, lower horizontal)
Wiring mode □ Horizontal wiring (standard configuration) □ J1 - Horizontal extended wiring □ J3 -
NDW3-4000
Vertical wiring □ J4 - Vertical extended wiring
□ Horizontal wiring (standard configuration) □ J1 - Horizontal extended wiring □ J3 -
Vertical wiring □ J4 - Vertical extended wiring □ J5 - Mixed wiring (upper
NDW3-6300 horizontal, lower vertical) □ J6 - Mixed wiring (upper vertical, lower horizontal)
□ J7 - Mixed extended wiring (upper horizontal and lower vertical) □ J8 - Mixed
extended wiring (upper vertical and lower horizontal)
Product type □ Not-marked - Conventional (standard configuration) TH - Thermal and humidity

Controller NDW3-1600 □ KM-NWK31 (digital screen) □ KY-NWK32 (LCD)


model NDW3-2500/4000/6300 □ KM-NWK21 (digital screen) □ KY-NWK22 (LCD)
Co
Controller
n □ 1(AC380V/400V) □ 2(AC220V/AC230V) □ 3(DC220V) □ 4(DC110V) □ 5(DC24V)
voltage
trol 2019.11.27
□ Conventional type (standard configuration) 试制 and protection type
□ V - Voltage measurement □ P -
l
Harmonic measurement and protection type
er
Note: 1. The NWK22/32 LCD type is only optional for P, while V and P can’t be selected with the accessory
par Protection type
monitoring unit simultaneously
a
2. For the AC800V and above, select the V - voltage measurement and protection type while the P2-voltage
me
conversion module is optional
ters
Communicatio □ Modbus □ Profibus □ DeviceNet
n functions Note: It can’t be selected with the accessory monitoring unit simultaneously

Internal & confidential file Page 115 of 117


NDT2920213 Document Version: 3

□ S1-4DO □ S2-3DO, 1DI □ S3-2DO, 2DI


Signal element
Note: It can’t be selected with the accessory monitoring unit simultaneously
□ Z1(AC380V/AC400V) □ Z2(AC220V/AC230V) □ Z3(DC220V) □ Z4(DC110V) □ Z5(DC24V)
Remote reset
Note: Z1 is not available with NDW3-1600
External 3P+N required: □ N1 □ N2 □ N3 □ N4
E type: □ E
transformer □ NR1 □ NR2 □ NR3
Grounding □ T type (default) □ W type Note: 3P+N needs to be added with an
□ E type
mode external transformer
Contact wear
□ J - Contact wear2019.11.27
equivalent Note: NWK21/31 is optional
equivalent 试制
Re Electric
qui operating □ D1(AC380V/AC400V) □ D2(AC220V/AC230V) □ D3(DC220V) □ D4(DC110V)
red mechanism
acc Shunt release □ F1(AC380V/AC400V) □ F2(AC220V/AC230V) □ F3(DC220V) □ F4(DC110V) □ F5(DC24V)
ess
ori Closed
□ B1(AC380V/AC400V) □ B2(AC220V/AC230V) □ B3(DC220V) □ B4(DC110V) □ B5(DC24V)
es electromagnet

Voltage
□ Q1(AC380V/AC400V) □ Q2(AC220V/AC230V)
specificat
Under-voltage □ Q3(DC220V) □ Q4(DC110V) □ Q5(DC24V)
ions
release
delay
□ 0-Instantaneous (0s) Delay: □ 1 (1s delay) □ 3 (3s delay) □ 5 (5s delay)
time
Voltage
Specificat □ S1(AC380V/AC400V) □ S2(AC220V/AC230V)
Loss of ions
voltage release 0s-10s adjustable by users Note: The factory default setting is 3s,
delay NDW3-1600/6300
with a step of 1s
time
NDW3-2500/4000 □ 1 (1s delay) □ 3 (3s delay) □ 5 (5s delay)
Op Voltage-check □ J1(AC380V/AC400V) □ J2(AC220V/AC230V) Note: Applicable to NDW3-2500
tio closing device Included harness or not: □ 0(without harness) □ 1 (with harness)
nal NDW3-1600 □ Four-group conversion (standard configuration) □ A6 - Six-group conversion
acc NDW3-2500/6300 □ Four normally opened and four normally closed (standard configuration) □ A55 - five
ess Auxiliary normally opened and five normally closed □ A66 - six normally opened and six
ori contact normally closed
es NDW3-4000 □ Four-group conversion(standard configuration) □ A6 - six-group conversion
□ A44 - four normally opened and four normally closed
Closing ready □ BX - Closing ready signal output unit
Counter □ JS - Counter
Drawer seat
□ CM1 - Right side of the door interlock □ CM2 - Left side of the door interlock
door interlock
Position
□ CX - Drawer seat three-position signal output
indicator
Door frame □ M Door frame
Dust cover □ F Dust cover
Relay module □ R Relay module
Power supply □ P Power supply module (in line with the operating voltage of controller in default)

Internal & confidential file Page 116 of 117


NDT2920213 Document Version: 3

module
Button lock □ S Button lock
Programmable
□ BC Programmable output module (6-channel)
module
□ IO1 remote I/O module C8 □ IO2 remote I/O module S12 □ IO3 remote I/O module SC64 □ IO4 remote
Remote I/O
I/O module SCM423
module
Note: To be used with the optional power supply module
Accessory □ AM - Accessory monitoring unit
monitoring Note: It can’t be selected with the communication function, signal unit and controller with “V” and “P”
unit functions simultaneously
Voltage
conversion □ P2 - Voltage conversion module
module
Energy-storing
□ TC - Energy-storing signal communication module component
signal
Note: It can’t be selected with the controller with “V” and “P” functions simultaneously
communication
Off-position □ SF11-One lock one key □ SF21-Two locks one key □ SF31-Three locks one key
lock □ SF32-Three locks two keys □ SF53-Five locks three keys
□ SR11 - Two groups, one for closing and one for opening Note: SR21 and SR12 are only
Cable
Inter □ SR12 - Three groups, one for closing and two for opening applicable to the NDW3-2500
type
lock Mechanical □ SR21 - Three groups, two for closing and one for opening frame and above, while the
ing interlocking NDW3-1600 fixed type is not
Hard rod □ SY11 - Two groups, one for closing and one for opening
acce provided with a mechanical
type □ SY12 - Three groups, one for closing and two for opening
ssori interlock.
es Power supply □ ATS-R type □ ATS-S type □ ATS-F type
automatic Note: 1. Please select a type if mechanical interlocking is standard,; 2. There's no need to select undervoltage
switching release if undervoltage protection is included; 3. The electrical accessories must select the working voltage of
device AC220V; 4. NDW3-1600 fixed type is not provided with this accessory.
Factory setting of the special requirements:
Overload long time-delay current____A time_____s; short-circuit short time-delay current____A
Special requirements time_____s
short circuit transient current____A; ground fault current ____A time____s
Other requirements:
Note: 1. In case of no special requirements, the current and time setting value of controller shall be set according to the factory setting;
2. If you have special requirements, please indicate in the special requirements column.

2019.11.27
试制

Internal & confidential file Page 117 of 117