Ishrae Variable Volume Pumping System
Ishrae Variable Volume Pumping System
By Kenneth R. Luther
Manager Engineering Services,
TT Fluid Handling,
Morton Grove, III
It is the objective of the HVAC engineer to design the most cost-effective
pumping system while meeting the clients' needs. Primary-secondary pumping is
a tool HVAC engineers have been using for nearly 50 years to accomplish this
objective.'
ASHRAE/IES Standard 90.1- 1989 - Energy Efficient Design of New
Buildings Except Low-Rise Residential Buildings requires "all pumping systems
2
with modulating or step open and closed valves which have total pump system
horsepower greater than 10 must be capable to flow at 50 percent of design value
or less." The standard 90.1 - 1989 User's Manual "highly recommends" primary-
3
secondary pumping for "systems with large, high pressure drop distribution
systems such as those serving campuses and airports."
Primary-secondary pumping (Fig. 1) provides the means for the constant
volume pumping of the low horsepower primary pumps through the chiller.
These pumps are lower horsepower than the secondary pumps because they only
haves to overcome the friction loss associated with the chiller, pipes, and valves
in the primary loop. The chiller pumps are balanced to the design flow rate.
Pump impellers should be trimmed discharge of the pump. This is an important
energy saving measure.
The secondary pumps are higher horsepower because they must overcome
the friction loss associated with the secondary loop-the distribution piping,
fittings, valves, coils, etc. These pumps operate in the energy saving variable
volume mode. Depending on the return on investment, the secondary pumps
either remain constant speed and ride their characteristic head-capacity curve, or
the designer can incorporate adjustable frequency drivers to saves additional
pumping energy (Fig. 2)
There are three critical design areas that must be considered for any variable
volume pumping system:
• The common pipe
• Chiller sequencing
• Control valves and actuators
[top]
When piped with a common, the flow through the chillers is a constant. In
our example, the two steps are either 50 percent flow (1500 gpm) or 100 percent
flow (3000 gpm). The secondary flow is very close to a "linear function." As the
two-way valves modulate in response to a varying load, the flow follows directly.
The more chillers in the plant, the smaller the steps. If we incorporate chillers in
a variety of sizes, the incremental steps are smaller. The additional chillers and
variety of chiller sizes can produce a curve that is nearly linear. When the chiller
plant is designed to produce a near-linear flow function, the supply temperature
rises, the secondary is minimized, and the increased supply waters temperature
lasts for a shorter duration. This is a very critical factor in design regions where
humidity control is a concern.
Chiller sequencing can be as simple as manually turning on and off a second
chiller. It can also become complex when multiple chillers of different sizes,
types, and efficiency are installed. The chiller manufacturer is usually best suited
to provide the information and instrumentation to effectively stage and destage
its product.
[top]
Conceptually, the designer needs to determine the best combination of
chillers that will meet the flow demand. This is often done by calculating the Btuh
consumed (Fig 7). Instrumentation must be provided to determine:
Secondary supply water temperature, T . S.S
Secondary flow, F S
rate of 20 percent of the best efficiency point flow rate. To limit the radial and
axial loads and shaft deflection, our recommendation is to maintain a minimum
flow rate of 25 percent of the best efficiency point flow rate.
The Hydraulic Institute and ITT Fluid Handling also recommend limiting the
temperature rise of the fluid flowing through the pump to 15F. (This is not to be
confused with the system temperature rise.) When a pump is operating in a low
flow condition, the temperature rise occurs in a small volume of water. If an
insufficient volume of water flows through a pump, the inefficiency of the pump
is converted to heat. In time, the heat build-up can cause the fluid to vaporize and
eventually result in cavitation.
To calculate the flow rate for a 15F temperature rise use the following
equation :
Where:
Q = Minimum flow rate, gpm
P = Input power at the minimum flow rate, hp. Assume that the shutoff hp is
approximately equal to the minimum flow rate hp
2.95 = Constant, (hp - lb - min - F) /(Btu.gal)
C = Specific heat, Btu/(lb.F)
P
S = Specific gravity
When careful attention is given to these fundamentals, energy savings will be
achieved and design system ∆T will be achieved. As system characteristics change
due to load changes, the aging of the piping and coils, or even as coils get dirty,
system ∆T may suffer. There is no substitute for knowledgeable operators and
proper thermostats and the lowering of supply air temperatures will only add to
the inefficiency. Unless problems are cured only patches can be applied to treat
symptoms. "Fixes" consume additional energy. The only way to keep a properly
designed HVAC system operating efficiently is to maintain it in the appropriate
manner.
[top]
Conclusion
To optimize system performance and design flexibility, the designer must
select the type of distribution piping and pumping configuration that will best
meet the needs of the client. The following are the four basic types of pump0ing
systems in use today.
• Primary-secondary
• Primary-secondary-tertiary
• Primary-secondary zone
• Primary variable speed
These pumping methods will be discussed in a second article in this series.
References
1. Primary-Secondary Pumping Application Manual, ITT Fluid Technology
Corp., Morton Grove, III., 1968
2. ASHRAE/IES Standard 90.1-1989-Energy Efficient Design of New
Buildings Except Low-Rise Residential Buildings, Section 9.5.5, AHSRAE,
Atlanta, Ga., 1993
3. ASHRAE/IES Standard 90.1-1989-User's Manual, pp 9-59, ASHRAE,
Atlanta, Ga., 1993
4. American National Standard for Centrifugal Pumps for Nomenclature,
Definitions, Application, and Operation, ANSI/HI 1.1-1.5-1994, Section
1.3.3.2.4.2, pp 83-84, Hydraulic Institute, Parsippany, N.J., 1994
Biblography
1. ASHRAE Handbooks: 1995 HVAC Applications; 1996 HVAC Systems and
Equipment; 1997 Fundamentals, Atlanta, Ga.
2. Bell & Gossett Large Chilled Water System Design Manual, ITT Fluid
Handling Corp., Morton Grove, III., 1965.
3. Bell & Gossett Large Chilled Water System Design Manual, ITT Fluid
Handling Corp., Morton Grove, III., 1996.