This document provides the specifications for an AL59 conductor to be used for a 220kV transmission line from a 320MW solar power plant to a substation. It lists 16 items that describe the conductor's: [1] type as AL59 made of 61 strands of 3.5mm wire; [2] weight as 1618kg/km; and [3] electrical and mechanical properties including resistance, tensile strength, and coefficient of expansion. Drum details are also provided specifying steel drums of 1850x650x1000mm in size.

Uploaded by

RAJESH SHARMA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
6K views2 pages

GTP OF Al59 Conductor (61 - 3.5mm, 1618 KG - KM)

This document provides the specifications for an AL59 conductor to be used for a 220kV transmission line from a 320MW solar power plant to a substation. It lists 16 items that describe the conductor's: [1] type as AL59 made of 61 strands of 3.5mm wire; [2] weight as 1618kg/km; and [3] electrical and mechanical properties including resistance, tensile strength, and coefficient of expansion. Drum details are also provided specifying steel drums of 1850x650x1000mm in size.

Uploaded by

RAJESH SHARMA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

TERMS OF REFERENCE FOR THE AWARD OF TURNKEY OFFER

FOR 220KV SC TRANSMISSION LINE FROM M/s AEPL 320MW


SOLAR POWER PLANT TO PGCIL’s BHADLA II SUBSTATION

ANNEXURE-B: GTP OF Al59 Conductor (61/3.5mm, 1618 Kg/Km)

S.NO Description Conductor Details


1. Conductor type AL59
2. Standard according to which the conductor SS 4240814
will be manufactured and tested SS 4240813
3. Number of strands and wire diameter in mm 61/3.50
4. Number of Strands –(Nos.) 61
5. Diameter of Strand (mm)
Nominal 3.50
Maximum 3.53
Minimum 3.47

Overall Diameter of Conductor (mm) 31.50


6. Cross Sectional Area of – (sq. mm)
Whole Conductor 587
Each Strand 9.62
7. Laying of Strands – (Nos.)
a) Centre wire 1
b) First Layer 6
c) Second Layer 12
d) Third Layer 18
e) Fourth Layer 24
8. Weight – (Kg / Km.)
Whole Conductor 1618
Strand (At Nominal Dia.) 25.96
9. Calculated D.C. resistance at 20 ⁰C –
(Ohms /Km)
Whole Conductor 0.05070
Strand 3.100
10. Ultimate Tensile Stress – (KN)
Whole Conductor 141.12
Strand
i) Before Stranding 2.31
ii) After Stranding 2.19
11. Modulus of Elasticity –(N/sq.mm) 68000
12. Coefficient of linear expansion – 23.0x10-6
(per deg. C.)
13. Resistivity – (Ohms Sq.mm / m). Max.0.02930
14. Lay Ratios

First Layer
DOC. NO: ASEBR4-AEL-643-TOR-0108-R0 Page 22
TERMS OF REFERENCE FOR THE AWARD OF TURNKEY OFFER
FOR 220KV SC TRANSMISSION LINE FROM M/s AEPL 320MW
SOLAR POWER PLANT TO PGCIL’s BHADLA II SUBSTATION

i) Maximum 17
ii) Minimum 10

Second Layer
i) Maximum 16
ii) Minimum 10

Third Layer
i) Maximum 15
ii) Minimum 10

Fourth Layer
i) Maximum 14
ii) Minimum 10
15. Standard length of conductor in Km 2.0 ± 5%
16. Drum Details Steel 1850x650x1000
Material IS: 15976 & Approved
Size in mm (F x B x T) drum drawing
Standard confirming will be followed

--------------------------------------------------End of Document-----------------------------------------

DOC. NO: ASEBR4-AEL-643-TOR-0108-R0 Page 23