Pre-Commissioning Check List (SAMSUNG DVMS)
Pre-Commissioning Check List (SAMSUNG DVMS)
LIST
Remarks:_________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
SAMSUNG HVAC 776 Henrietta Creek Road Suite 100, Roanoke, TX 76262 • 888-699-6067 www.samsunghvac.com
ASSISTED START-UP POLICY PRE-CHECK
LIST
CONDENSING UNIT
Description Check
You must have in your possession a copy of the “As-Designed” DVM PRO piping tree diagram. BEFORE ANY FIELD
PIPE SIZE OR LENGTH CHANGES ARE MADE, PROPOSED CHANGES MUST BE FORWARDED TO THE DESIGN
ENGINEER SO THAT THEY CAN INPUT THE CHANGES INTO DVM Pro and RE-ISSUE A NEW PIPING TREE DIAGRAM.
Condensing unit is properly installed and meets all guidelines
Correct supply voltage to the condensing unit(s) has been connected.
All COM1 (F1/F2, OF1/OF2) communication wires have been connected (16 AWG X 2 Shielded)
COM1 shielded cable bare wire is grounded at the outdoor unit on a separate terminal than the main service ground connection
All central control communication wires (R1/R2) have been connected R1/R2 terminals in MAIN outdoor unit(s)
(Required for projects where central control options are being installed. 16 AWG X 2 shielded)
INDOOR UNITS
Description Check
1-way and Mini 4-way cassette units are 60" minimum from nearby walls and obstructions on all sides ( 1-way on all
sides excluding return air side of unit) Minimum 10' between installed 4-way and mini 4-way cassettes.
Wall mounted units have sufficient space in front of them to the nearest wall or
obstruction (Wall mounted units are 6' minimum from the ground)
All refrigerant pipe insulation is installed, sealed and supported.
All COM1 (F1/F2) and COM2 (F3/F4) wire is 16 AWG X 2, shielded cable and communication wires are connected.
Shield and bare wire in COM1 (F1/F2) wire is not touching indoor unit PCB's or other communication or voltage connections.
Condensate pump overflow relay is connected to break CN83 external contact connection (requires indoor unit option
setting to function) Option 14 - set to 2 (system must be wired and power must be applied) (For Wall Mountunits only)
Ducted indoor unit option setting has been adjust for use of internal Samsung condensate pumps.
Option 8 - set to 1 for pump use, set to 2 for pump use with 3 minute off-delay (system must be wired and power must
be applied) (For ducted units that have optional Samsung Pump field installed)
Ducted unit duct connections are complete and sealed and filters are in place.
Remarks:_________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
©2016. Samsung HVAC - All rights reserved. ASSISTED DVMS START UP PRE-CHECK LIST P2
SAMSUNG HVAC 776 Henrietta Creek Road Suite 100, Roanoke, TX 76262 • 888-699-6067 www.samsunghvac.com
ASSISTED START-UP POLICY PRE-CHECK
LIST
CONTROLLERS
Description Check
All COM2 (F3/F4) wire is 16 AWG X 2, shielded cable throughout the building
Central control wires have been run from the MAIN outdoor unit (R1/R2) to the installation location of central
controller(s) For projects with central control options. 16 AWG X 2 shielded cable
Optional remote temp. sensor MRW-TA has been connected to indoor unit(s) indoor unit option setting has been adjusted
for external sensor use. Option 4 - Set to 1 when using MRW-TA sensor (system must be wired and power must be applied)
Remarks:_________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
_________________________________________________________________________________________________
Prepared by Installer/Contractor:
Witnessed By Client:
Checked By:
©2016. Samsung HVAC - All rights reserved. ASSISTED DVMS START UP PRE-CHECK LIST P3