Week 4-5 Electrical Distribution Systems in Hospital
Week 4-5 Electrical Distribution Systems in Hospital
SYSTEMS IN HOSPITAL
• Electric Power is needed in health-care facilities not only for medical devices
but also for any other electrical equipment like lightning, air condition,
telephone, television etc.
• BUT
Medical devices underlie special safety regulations as they might stay in special
contact to and with patients, applicants and third persons
1. Overvoltage protection
2. Special ground
• Example
A lightning causes an overvoltage at the public power supply. The overvoltage is
transferred directly to the patients heart by applied ECG-Electrodes.
=> Over voltage protection
Distribution of Electrical Power
(230 V)
(230 V)
Emergency system
• The emergency system must be in full operation within 10 s after a
fault in general power supply.
• This system serves the life safety branch, the critical branch, and life
support branch
– Life safety branch : supplies power to the equipment necessary for
patient and personal safety such as hallway and stairway lighting, exit
signs and directional signs , smoke detectors, alarm systems.
– Critical branch: Serves the patient care areas as well as areas related
to patient care such as nursing stations and pharmacy. Also supplies
power to isolation transformer in anesthetizing locations.
– Life support branch: Provide power to those areas where electrical
power is essential for patient survival. Such as respirator and heart
lung machines.
Electrical Hazards in Hospital
Macroshock hazards
“The undesirable effect of a current greater than 5 mA at 60
cycles applied to the surface of the body”
Electrical Hazards in Hospital-
Protection Against Macroshock
1. Separate ground wire is used in hospital wiring systems.
Local codes for home wiring do not require this separate grounding
when metal conduit may serve as the ground return path.
Hospital require the use of separate ground wire to keep the ground
resistance as low as possible and to prevent breaks in ground path due
to corrosion, which can happen with conduit.
Hospital wiring
Home wiring
Protection Against Macroshock
Protection Against Macroshock
MICROSHOCK HAZARDS
“Define as a effect where a low level current (μA)
passes directly through the heart via a needle or
catheter in artery or vein”
V = IR
= (100 μA) (1Ω)
= 100 μV
Electrical Hazards in Hospital-
Microshock Hazards
If a catheterized patient, who is also grounded, comes in
contact on the medical device, the chassis-to-ground voltage
will be applied across the patient.
Microshock
Threshold of ventricular
fibrillation and pump failure
versus catheter area in dogs.
From O.Z. Roy, J.R.Scott, and
G.C. Park, “Ventricular
Fibrillation and Pump Failure
Threshold Versus Electrode
Area,” IEEE Transaction of
Biomedical
Engineering,1976,23,45-48.)
Electrical Safety Codes &
Standards
Code – document that contains only mandatory
documents
Standard –also a document that contain mandatory
requirement, but compliance tends to be voluntary,
and more detailed notes and explanations are given.
Manual or guide- is a document that is informative
and tutorial but does not contain requirements.
Electrical Safety Codes &
Standards
History:
The process of development, adoption and use of
standards and codes for electrical safety in health-care
facilities began following tragic explosion and fire
resulting from electric ignition of flammable
anaesthetics such as ether.
Lead to adoption of National Fire Protection
Association NFPA 99-1894 and ANSI/AAMI ESI \-
1985 standards.
Electrical Safety Codes &
Standards
NFPA 99-Standard for Health Care Facilities – 1996 has
evolved from 12 NFPA documents that were combined in a984
and revosed every 3 years.
Current edition: 2015
In addition to electric equipment, this standard also described
gas, vacuum, and environmental systems and materials.
The primary document that describes the requirements for
patient-care-related electric appliances used for diagnostic,
therapeutic, or monitoring purposes in a patient-care area.
Electrical Safety Codes &
Standards
The Association for the Advancement of Medical
Instrumentation (AAMI) developed an American National
Standard on “Safe Current Limits for Electromedical
Apparatus,” ANSI/AAMI ESI -1993.
This standard concern limits on chassis and patient-lead
leakage currents, which are fixed from dc to 1 kHz and
increase from 1kHz to 100 kHz.
Protection
against shock
1. Method Protection 1 : Power Distribution
• Grounding System
• Isolated Power distribution
• Ground fault circuit interrupters (GFCI)
2. Method Protection 2: Equipment design
3. Electrical-Safety Analyzers
Basic Approaches to
Shock Protection
Not grounded !
• Normally, when there is a ground-fault from hot wire to ground, a large current is drawn causing a
potential hazard, as the device will stop functioning when the circuit breakers open !
• This can be prevented by using the isolated system, which separates ground from neutral, making
neutral and hot electrically identical. A single ground-fault will not cause large currents, as long as
both hot conductors are initially isolated from ground!
Isolated Power Distribution
Not grounded !
• In fact, in such an isolated system, if a single ground-fault occurs, the system simply reverts back to
the normal ground-referenced system.
•A line isolation monitor is used with such system that continuously monitors for the first ground
fault, during which case it simply informs the operators to fix the problem. The single ground fault
does NOT constitute a hazard!
Ground – Fault
Circuit Interrupters (GFCI)
Disconnects source of electric current when a ground fault greater than about 6 mA occurs!
When there is no fault, Ihot=Ineutral. The GFCI detects the difference between these two
currents. If the difference is above a threshold, that means the rest of the current must be
flowing through elsewhere, either the chassis or the patient !!!.
The detection is done through the monitoring the voltage induced by the two coils (hot and
neutral) in the differential transformer!
GFCI
~
Input common CM ISO
ISO Output
common
o = SIG ± ± Gain
CMRR IMRR
(a)
*IMRR in v/v
FB
AD202
Signal
In - - Demod Hi
In + Mod
+ ±
5V ±5V
SIG F.S. o
F.S. Lo
In com
+ISO Power
Out Rect and
+ 7.5 V filter Oscillator + 15 V DC
-ISO
Out - 7.5 V 25 kHz
25 kHz Power
return
(b)
Optical Isolation Amplifier
Isolation barrier
i i2
i
1 2
+V
+o
RG
- -
AI i2 AII
+ i1 + i3 + +
~ i o
-
-V -
Input
RK Output
control o = i
RG control
(c)
Electrical Safety Analyzers
Wiring / Receptacle Testing
Circuitry
Internal
surface or if none, then 10 by
120 V N 20 cm metal foil in contact
N (white) with the exposed surface
G