0% found this document useful (0 votes)
110 views18 pages

NAE55/NIE55 Installation Instructions: Application

Uploaded by

tqhunghn
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
110 views18 pages

NAE55/NIE55 Installation Instructions: Application

Uploaded by

tqhunghn
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

NAE55/NIE55 Installation Instructions

MS-NAE55xx-3, MS-NIE55xx-3, MS-NAE5510-2U

(barcode for factory use only)


Part No. 24-10051-43, Rev. N
Software Release 9.0
Issued August 2017
Refer to the QuickLIT website for the most up-to-date version of this document.

Application
The Network Automation Engine (NAE) and Network Integration Engine (NIE) are web-enabled, Ethernet-based,
supervisory devices. Network Automation Engines (NAEs) and Network Integration Engines (NIEs) monitor and
control networks of field-level building automation devices, including HVAC equipment, lighting, security, and fire
safety equipment. Figure 1 shows a typical NAE55 model. Use this document to install the NAE55 or NIE55, hereafter
referred to as the NAE55. For installation instructions on the secure NAE55, refer to the NAE-S Installation Instructions
(Part No. 24-10051-108).

Important: In Metasys® system smoke control applications, use only the NAE5510-2U model that is UL Listed,
UUKL 864 Listed, Smoke Control Equipment. See Repair Information for the UUKL 864 Listed NAE55
model. For Metasys system smoke control applications, you must refer to the Metasys® System UL
864 9th Edition UUKL/ORD-C100-13 UUKLC Smoke Control System Technical Bulletin (LIT-12011252)
for detailed requirements and procedures for installing and operating UUKL 864 Listed Metasys system
devices. Failure to meet the requirements or follow the procedures in the Metasys® System UL 864
9th Edition UUKL/ORD-C100-13 UUKLC Smoke Control System Technical Bulletin (LIT-12011252)
can void the UUKL 864 listing for Smoke Control Equipment.

North American Emissions Compliance


United States
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated
in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area may cause harmful interference, in which case the users will be required to correct the interference
at their own expense.

Canada
This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

Installation
Follow these guidelines when installing an NAE55:
• Transport the NAE55 in the original container to minimize vibration and shock damage to the NAE55.
• Verify that all the parts shipped with the NAE55. The data protection battery and NAE55 ship together but are
packaged separately.
• Do not drop the NAE55 or subject it to physical shock.
• Do not open the NAE55 housing (except the data protection battery compartment). The NAE55 has no
user-serviceable parts inside.

NAE55/NIE55 Installation Instructions 1


Parts Included
• one NAE55
• one data protection battery
• one installation instructions sheet
• one quick start guide

Materials and Special Tools Needed


• four fasteners appropriate for the mounting surface (M4 screws - Europe, #8 screws - North America)
• two 36 cm (14 in.) or longer pieces of 35 mm DIN rail (for DIN rail mount applications only)

Dimensions
Figure 1: NAE55 Showing Dimensions, Physical Features, and Mounting Orientation

Note: The features shown in Figure 1 may or may not be present, depending on the NAE55/NIE55 model. See
Ordering Information for a list of features available on the NAE55/NIE55 models.

Mounting
Location Considerations
Follow these guidelines when mounting an NAE55:

NAE55/NIE55 Installation Instructions 2


• Ensure that the mounting surface can support the NAE55 and any user-supplied enclosure.
• Mount the NAE55 in the proper orientation (Figure 4).
• Mount the NAE55 on an even surface in wall mount applications whenever possible. If you must mount the
NAE55 on an uneven surface, be careful not to crack the wall mount feet or housing when tightening the screws.
Use shims or washers to mount the unit securely on the mounting surface.
• Mount the NAE55 in areas free of corrosive vapors and observe the environmental limitations listed in the
Technical Specifications section.
• Do not mount the NAE55 on surfaces that are prone to vibration, such as duct work, or in areas where
electromagnetic emissions from other devices or wiring can interfere with NAE55 communication.
• Allow sufficient space for running cable and wire, making terminal connections, and accessing battery compartment
(Figure 2).
• Do not mount the power supply below the NAE55.
On panel or enclosure mount applications, observe these additional guidelines:
• Do not install the NAE55 in an airtight enclosure.
• Mount the NAE55 so that the enclosure wall or the transformer does not obstruct ventilation of the NAE55 housing.
Figure 2: NAE55 DIN Rail Mount Dimensions and Mounting Space Requirements, mm (in.)

Each NAE55 application is different, and no general guidelines can be given about the heat dissipating devices that
may be mounted in an enclosure with the NAE55. Monitor the NAE55 processor temperature for each application
to determine the acceptable combinations of devices and proper mounting location for your specific application.

Important: Do not add any devices to an enclosure with an NAE55 that could cause the temperature of the NAE55
processor to exceed 70˚C (158˚F). View the NAE55’s CPU Temperature value on the NAE55’s Diagnostic
tab on the Metasys Site Management Portal. See Technical Specifications for ambient condition
requirements, and refer to the Troubleshooting section of the NAE Commissioning Guide (LIT-1201519)
for additional information.

Mounting the NAE55

Wall Mount Applications


To mount the NAE55 on a vertical surface:
1. Mark the location of the four wall mount feet on the wall using the dimensions in Figure 3 and an orientation
shown in Figure 4, or hold the NAE55 up to the wall and mark the hole locations.

NAE55/NIE55 Installation Instructions 3


Figure 3: Mounting Screw Hole Dimensions, mm (in.)

2. Drill holes in the wall at the marked locations.


3. Insert appropriate wall anchors in all four holes (if necessary) and insert the screws into the top two holes. Leave
enough space between the wall surface and the screw head for the wall mount feet.
4. Hang the NAE55 on the screws with the top wall mount feet for horizontal wall mount applications. Hold the
NAE55 in place for vertical application.
Note: The wall mount feet are designed to make mounting easier. When the NAE55 is wall mounted in the
horizontal orientation, you can hang the NAE55 on the screws with the upper two mount feet (Figure 4).
5. Insert the screws into the lower two wall mount feet and holes and carefully tighten all of the screws.
Important: Do not overtighten the mounting screws. Overtightening the screws can crack the NAE55 wall
mount feet or housing.

DIN Rail Mount Applications


To mount the NAE55 on DIN rails:
1. Mount two DIN rails horizontally, so they are 125 mm (4.9 in.) apart on centers (Figure 2).
2. Snap the DIN clips on the bottom of the NAE55 to the outward position.
3. Hang the NAE55 on the DIN rail hooks on the back of the NAE55.
Press the DIN clips back into position to secure the unit on the DIN rails.
Figure 4: Required Orientations for NAE55 Wall Mount Applications

NAE55/NIE55 Installation Instructions 4


To remove the NAE55 from the DIN rails:
1. Snap the DIN clips on the bottom of the NAE55 to the outward position.
2. Lift the NAE55 off the DIN rails.

Enclosure Mount
To mount the NAE55 in an enclosure:
1. Mount the enclosure in accordance with the manufacturer’s instructions.
2. Mount the NAE55 in the enclosure following the guidelines in the Location Considerations and Mounting the
NAE55 sections of this document.

Wiring
Power Supply, Network, and Communication Connections
See Figure 1 for the location of the power supply terminal, network communication terminals, Ethernet jack, and
modem jack.

Power Supply
Important: Install the data protection battery before applying 24 VAC power to the NAE55. See the Installing the
Data Protection Battery section.
In North America, use a Class 2, 24 VAC power supply with a 50 VA minimum output. Outside North America, use
a 24 VAC safety extra-low voltage (SELV) transformer at the appropriate rating. The minimum input voltage for the
NAE55 to operate properly is 20 VAC. See the Technical Specifications section.
Use a dedicated power supply to the NAE55 only. Do not connect any other loads to the power supply. Additional
loads may cause noise interference.

FC Bus Terminal Block


The two Field Controller (FC) Bus connections on the MS-NAE55xx-x models are 4-pin removable, keyed terminal
blocks labeled FC A and FC B.
Note: MS-NIE55xx-x models (NIE55s) do not have FC Bus terminal blocks or LONWORKS® network terminal blocks.
The FC bus connections are optically isolated RS-485 ports with keyed 4-position terminal blocks that communicate
at 9.6k, 19.2k, 38.4k, or 76.8k baud. Use an FC Bus port to integrate an N2 network or a BACnet®
Master-Slave/Token-Passing (MS/TP) FC Bus trunk into the Metasys system.
Note: N2 and BACnet MS/TP Buses have different protocols and network requirements. Do not connect N2 and
MS/TP devices to the same FC Bus port.
The Shield (SHD) connections on the FC terminal blocks are not connected to any earth ground connection. The
FC A and FC B terminal blocks are not interchangeable.

LONWORKS Network Terminal Block


The LONWORKS TP/FT-10 network connection on the MS-NAE552x-3 models (only) is a 3-wire removable, keyed
terminal block. The SHLD connection (Figure 6) on the LONWORKS network terminal block is an isolated terminal and
is not connected in the NAE552x. Use the LONWORKS terminal block to connect LONWORKS networks to the NAE552x.

NAE55/NIE55 Installation Instructions 5


Computer Serial Ports
The RS-232-C serial ports on the NAE55 are for direct connection using a standard 9-pin female data terminal
equipment (DTE) to 9-pin female DTE null modem cable. The NAE55 serial ports do not support external modems.
The RS-232-C serial ports are labeled RS232C A and RS232C B (Figure 1).
Use the RS232C A port to connect directly to a computer serial port to browse to the NAE55. Use this port only for
establishing a Point-to-Point Protocol (PPP) network connection. Refer to the Metasys System Extended Architecture
Direct Connection and Dial-Up Connection Application Note (LIT-1201639).
Use the RS232C B port to connect with a VT100 terminal or computer using a VT100 terminal emulator because
the RS232C B port outputs the device IP address. Use this port only to obtain the NAE55 IP address at startup.
Refer to the NAE Commissioning Guide (LIT-1201519).

Universal Serial Bus (USB) Ports


The two USB ports labeled USB A and USB B are both configured as masters and are independent of each other.
Use the USB A port to connect an optional external modem. Refer to the NAE Commissioning Guide (LIT-1201519)
for more information on external modems.

Ethernet Port
The Ethernet port, labeled ETHERNET, is an 8-pin RJ-45 network port for connecting the NAE55 to Ethernet
networks. NAE55 engines can connect to Ethernet networks at 10 Mbps, 100 Mbps, or 1 Gbps.
On MS-NIE55xx-x models, use the Ethernet port for migration of N1 communications. Refer to the N1 Migration with
the NIE Technical Bulletin (LIT-1201535).

Optional Internal Modem


MS-NAE55x1-x and MS-NIE55x1-x models have an internal modem and a 6-pin RJ-12 modular jack labeled MODEM.
Connect a standard phone line plug and cable to the to use the internal modem.
For information on commissioning an internal modem, refer to the NAE Commissioning Guide (LIT-1201519).

Wiring the NAE55/NIE55


Mount the NAE55 securely before wiring it. Follow these guidelines when wiring the NAE55:

Important: Do not apply 24 VAC power to the NAE before completing and checking connections. Short circuits or
improperly connected wires may result in permanent damage to the equipment.

Important: Do not apply 24 VAC power to the NAE55 before installing the data protection battery. See the Installing
the Data Protection Battery section in this document.

Important: Use copper conductors only. Make all wiring in accordance with local, national, and regional regulations.

Important: The NAE55 is a low-voltage (<30 VAC) device. Do not exceed the NAE electrical ratings. Applying high
voltage to the NAE may result in permanent damage to the NAE and void any warranties.

Important: Do not remove the terminal block keys. The terminal block plugs and the terminal sockets are keyed
to fit together in the correct configuration only.

NAE55/NIE55 Installation Instructions 6


Important: Prevent any static electric discharge to the NAE. Static electric discharge can damage the NAE and
void any warranties.
• Route the supply power wires and communication cables at least 50 mm (2 in.) away from the vent slots in the
sides of the NAE55 housing.
• Provide slack in the wires and cables. Keep cables routed neatly around the NAE55 to promote good ventilation,
LED visibility, and ease of service.
Note: Ensure that the building automation network wiring meets the specifications, rules, and guidelines in the
Wiring Considerations and Guidelines for Network Integrations section.
To wire the NAE55:
1. Connect the Ethernet cable to the RJ-45, 8-pin Ethernet port shown in Figure 1.
2. Connect the Building Automation System (BAS) network cables to the appropriate ports.
• For N2 or MS/TP networks, connect the 3-wire bus cable to one of the removable 4-terminal plugs labeled
FC A or FC B (Figure 5).
• For LONWORKS compatible networks, connect the 2-wire cable from the LONWORKS network trunk to th removable
3-terminal plug labeled LON (Figure 6).
Note: If an N2 Bus or MS/TP Bus is connected to the NAE55, you must set the NAE55 EOL switches to the
proper positions. See the Setting the End-of-the-Line Switches section.
3. If using a modem, connect a telephone line to the modem port or connect an external modem to the USB A as
necessary.
Figure 5: FC Bus Terminal Block and Wiring Connections

NAE55/NIE55 Installation Instructions 7


Figure 6: LONWORKS Network Terminal Block and Wiring Connections

Figure 7: 24 VAC Supply Power Wiring

4. Make connections to the RS-232 serial ports (if necessary).


5. Connect the 24 VAC supply power wires from the transformer to the removable power terminal block plug (Figure
7).
Power supply wire colors may be different on transformers not manufactured by Johnson Controls. Follow the
transformer manufacturer’s instructions and the project installation drawings.
The 24 VAC power should be connected to all network devices so transformer phasing is uniform across the devices.
Powering network devices with uniform 24 VAC supply power phasing reduces noise, interference, and ground loop
problems.
The NAE55 does not require an earth ground connection.

NAE55/NIE55 Installation Instructions 8


Wiring Considerations and Guidelines for Network Integrations
Table 1: NAE Ethernet Network Rules
Category Rules/Maximums Allowed
1

General Star topology with network hubs/switches


Number of Devices Maximum of 1,000 devices can be connected to one site in the Metasys network.
Line Length and Type 2,000 m (6,600 ft) for plastic/glass fiber optic with external adapter
10/100 BaseT: 100 m (330 ft) CAT5 cable
1000 BaseT: 100 m (330 ft) CAT5E cable
Terminations For 10/100/1000 BaseT, no line terminators allowed.

1 Refer to the N1 Ethernet/IP Network Technical Bulletin (LIT-6360175) for recommended parts and part numbers.

Table 2: Guidelines for BACnet Protocol MS/TP Network Topology


Category Rules/Maximums Allowed
General MS-NAE55xx-x models (only) support up to two MS/TP Bus trunks, daisy chain topology only.
Number of Devices 1
100 devices per Field Controller (FC) Bus with no more than two repeaters between NAE55 and
any device and a maximum of 50 devices between repeaters
2 1
Line Length and Type 1,500 m (5,000 ft) cable without a repeater
4,500 m (15,000 ft) cable from NAE55 to the farthest FC Bus device (three bus segments of 1,500
m [5,000 ft] each, separated by repeaters)
2,000 m (6,600 ft) between two fiber modems
Cable Type Stranded 0.6 mm (22 AWG) 3-wire twisted, shielded cable is recommended.
Stranded 0.6 mm (22 AWG) shielded 4-wire (two twisted-pairs) shielded cable is acceptable.
Note: The + and - bus leads should be a twisted pair. On applications using 4-wire (two
twisted-pairs) cable, isolate and insulate unused conductor. Refer to the MS/TP
Communications Bus Technical Bulletin (LIT-12011034) for more information.
Terminations Two FC devices with end-of-line (EOL) switches in the ON position, one at each end of each FC
Bus segment

1 If TEC Thermostat Controllers or third-party devices are used on the FC Bus, the maximum total number of devices is 64
and the maximum length is 1,219 m (4,000 ft).
2 Refer to the MS/TP Communications Bus Terminal Bulletin (LIT-12011034) for information on cable types and lengths.

Table 3: Guidelines for N2 Network Topology


Category Rules/Maximums Allowed
General MS-NAE55xx-x models (only) support up to two N2 Bus trunks.
Only daisy-chained N2 devices (with maximum stub length of 3 m [10 ft] to any device)
Number of Devices MS-NAE551x-x models (only) support up to 100 N2 devices per N2 Bus, with no more than two repeaters
between NAE55 and any N2 device and a maximum of 50 devices between repeaters.
Line Length and 1,500 m (5,000 ft) twisted pair cable without a repeater
Type
4,500 m (15,000 ft) twisted pair cable from NAE55 and the farthest N2 device (three segments of 1,500
m [5,000 ft] each, separated by repeaters)
2,000 m (6,600 ft) between two fiber modems

NAE55/NIE55 Installation Instructions 9


Table 3: Guidelines for N2 Network Topology
Category Rules/Maximums Allowed
Cable Solid or stranded 1.5 mm (18 AWG) 3-wire is recommended.
Solid or stranded 0.6 mm (24 AWG) larger 3-wire or 4-wire (two twisted-pairs) is acceptable.
Note: The + and - bus leads should be a twisted pair. On applications using 4-wire (two twisted-pairs)
cable, isolate and insulate unused conductor.
Terminations Preferred Termination Configuration: Two N2 devices with EOL switches in the ON position, one at
each end of each N2 Bus segment
Minimally Required Termination Configuration: At least one N2 device with an EOL switch in the ON
position somewhere on each N2 Bus segment

Table 4: Guidelines for LONWORKS Network Bus Topology


Cable Type Maximum Segment Length with Maximum Segment Length with
1 1
FTT10 Devices Only FTT10 and/or LPT10/11 Devices
Belden® 85102 Cable 2,700 m (8,850 ft) 2,200 m (7,200 ft)
Belden 8471 Cable 2,700 m (8,850 ft) 2,200 m (7,200 ft)
Level IV 22 AWG 1,400 m (4,600 ft) 1,150 m (3,770 ft)
JY (St.) Y 2 x 2 x 0.8 900 m (2,950 ft) 750 m (2,460 ft)

1 For the bus topology, the maximum length stub cable is 3 m (10 ft), and the stub lengths must be calculated into the overall
segment length.

Table 5: Guidelines for LONWorks Network Free Topology


Cable Type Maximum Node-to-Node Distance Maximum Segment Length with
FTT10 and/or LPT10/11 Devices
Belden 85102 Cable 500 m (1,640 ft) 500 m (1,640 ft)
Belden 8471 Cable 500 m (1,640 ft) 500 m (1,640 ft)
Level IV 22 AWG 400 m (1,300 ft) 500 m (1,640 ft)
JY (St.) Y 2 x 2 x 0.8 320 m (1,050 ft) 500 m (1,640 ft)

Table 6: Maximum Number of Devices per LONWORKS Network Segment


Device Type Maximum Allowed
FTT10 Nodes Only 64 nodes if repeaters are not used; 255 nodes if repeaters are
used
1 ([FTT10 x 2] + LPT10/11) < 128
Mixed FTT10 and LPT-10/11 Nodes
Physical Layer Repeaters Maximum of 1 per segment
2
Terminators
Bus Topology 2 bus type EOL terminators required (NU-EOL202-0)
Free Topology 1 free topology terminator required (NU-EOL203-0)

1 Each NPT10/11 channel segment (between repeaters) requires its own power supply. Other factors, such as power consumption
of individual LPT10/11 devices, may limit a segment to fewer devices.
2 The MS-NAE552x-x models that support LONWORKS Network trunks do not have an internal network terminator.

NAE55/NIE55 Installation Instructions 10


Setup and Adjustments
Installing the Data Protection Battery
Important: Do not apply 24 VAC power to the NAE55 before installing the data protection battery.
To install the data protection battery:
1. Remove the battery from its packaging. Remove the battery cover on the NAE55 to expose the battery
compartment (Figure 1).
2. Carefully plug the NAE55 battery connector from the battery compartment into the connector on the battery cable
(Figure 9).
3. Place the battery into the compartment (Figure 9).
4. Slide one end of the battery strap into the hole on the opposite side of the strap (Figure 9), and loop the strap
tightly around the battery to minimize battery movement.
5. Replace the cover of the battery compartment.
6. Apply 24 VAC power to the NAE55 immediately.
Important: The data protection battery must maintain a small residual charge. The battery ships from the factory
with a small residual charge. You should connect 24 VAC power to the NAE55 immediately after
connecting the battery to ensure that the battery does not completely lose its charge, which may
damage the battery.
Note: The 24 VAC power to the NAE55 charges the data protection battery. At initial startup, the battery requires
a charging period of at least 2 hours before it supports data protection if power fails. Maximum protection
(up to three consecutive power failures without recharging time) requires a 24-hour charging period.

Setting the End-of-the-Line Switches


The network devices at each end of an FC Bus segment must be set as network terminated devices. The NAE55
has two EOL switches (one for each FC Bus) that enable you to set the NAE55 as a network terminated device on
the bus.
To set an NAE55 as an FC Bus terminated device, position the switch on the EOL switch block to the ON position
(Figure 8).
Figure 8: FC Bus EOL Switch in the Factory Default ON (Up) Position

Note: The NAE55 is shipped with the EOL switches for both FC Buses in the initial factory position, ON (Figure 8).
If the NAE55 is not a terminated device on the FC Bus, reposition the switch on the EOL switch block to the
Off (down) position.
Set the EOL switches appropriately for the FC A and FC B buses. The NAE55 follows the same rules as other
switch-terminating devices listed in the Setting Terminations sections of the N2 Communications Bus Technical
Bulletin (LIT-636018) and the MS/TP Communications Bus Technical Bulletin (LIT-12011034).

Powering on the NAE55


After applying 24 VAC power, the NAE55 requires approximately 3 minutes to start up and become operational. See
the LED Test Sequence at Startup section.
Startup is complete and the NAE55 is operational when the (green) RUN LED is On steady and the (red) GEN
FAULT LED is Off. See Figure 10 for LED locations.

NAE55/NIE55 Installation Instructions 11


Disconnecting Power from the NAE55
Important: The data protection battery must be installed and charged before disconnecting the 24 VAC supply
power.
The 24 VAC supply power is disconnected from the NAE55 by removing the terminal block plug from the power
terminal port on the NAE55 (Figure 7).
When the 24 VAC supply power to the NAE55 is disconnected or lost, the NAE55 is nonoperational. The POWER
LED (Figure 10) remains On, and the data protection battery continues to power the NAE55 for approximately 1 to
3 minutes so that volatile data can be backed up in nonvolatile memory. The POWER LED goes Off when the data
backup is completed.
Figure 9: NAE55 and NAE55 Data Protection Battery

Troubleshooting
LED Status Indicators
The NAE55 has LEDs to indicate power and communication status. See Figure 10 and Table 7.

LED Test Sequence at Startup


During startup, the NAE55 automatically initiates an LED test to verify the operational status of the LEDs. Immediately
after connecting supply power, the following LED lighting sequence occurs:
1. The NAE55 emits one short beep, indicating that the BIOS startup was successful.
2. The PEER COM, RUN, and GENL FAULT LEDs turn on, indicating that the operating system (OS) is booting
up. For NAE55 models, the FC A and FC B LEDs also turn on.
3. The PEER COM, RUN, GENL FAULT LEDs, and the FC A and FC B LEDs (on NAE55 models) shut off. The
RUN LED flashes to indicate that the NAE55 software is loading.
4. The LEDs display the operational status of the NAE55. When the RUN LED goes On Steady, the operating
system and Metasys application are running and the NAE55 is ready.
The total time to start up the NAE55 depends on the size of the database and can take several minutes.

NAE55/NIE55 Installation Instructions 12


Figure 10: NAE55 with LED Designations

Figure 11: NIE55 with LED Designations

System Re-Boot Switch


The System Re-Boot switch (Figure 1) forces a manual restart of the NAE55 processor. All data changes made to
the system since the last time the NAE55 saved data are lost on restart, including alarm, trend, and audit trail data.
Note: Press the System Re-Boot switch only if the NAE55 fails to respond and cannot be accessed by any user
device. Do not press the System Re-Boot switch unless you have tried other reasonable means to fix the
problem.

NAE55/NIE55 Installation Instructions 13


Table 7: NAE55 LEDs Designation, Normal Status, Description, and Other Conditions
LED Normal Descriptions/Other Conditions
POWER (Green) On Steady On Steady = Unit is getting power from either the battery or 24 VAC power. Also
see the 24 VAC LED. Off Steady = Unit is shut down.
ETHERNET (Green) Flicker Flicker = Data is transferring on the Ethernet connection. Ethernet traffic is general
traffic (may not be for the NAE55).
Off Steady = No Ethernet traffic, probably indicates a dead Ethernet network or
bad Ethernet connection.
10/LINK (Green) On Steady On Steady = Ethernet connection is established at 10 Mbps.
100/1000 LINK On Steady On Steady (Green) = Ethernet connection is established at 100 Mbps.
(Green/Yellow)
On Steady (Yellow) = Ethernet connection is established at 1,000 Mbps.
FC A (Green) Flicker On Steady = Controllers are defined to FC A (FC Bus 1 or N2 Trunk 1) in the
NAE55, but none are communicating (NAE55 transmitting only). Flicker = Normal
(NIE55 models do not
communications; FC A port is transmitting and receiving data. Flickers are generally
have FC Bus terminals.)
in sync with data transmission but should not be used to indicate specific
transmission times.
Off Steady = No field controllers are defined to FC A (FC Bus 1 or N2 Trunk 1) in
the NAE55.
FC B (Green) Flicker On Steady = Controllers are defined to FC B (FC Bus 2 or N2 Trunk 2) in the
NAE55, but none are communicating. (NAE55 transmitting only) Flicker = Normal
(NIE55 models do not
communications; FC B port is transmitting and receiving data. Flickers are generally
have FC Bus terminals.)
in sync with data transmission but should not be used to indicate specific
transmission times.
Off Steady = No field controllers are defined to FC B (FC Bus 2 or N2 Trunk 2) in
the NAE55.
PEER COMM (Green) Varies (see next Flicker = Data traffic between NAEs. For an NAE55 that is not a Site Director, this
column) LED indicates regular heartbeat communications with the Site Director. For a Site
Director NAE55, flashes are more frequent and indicate heartbeat communications
from all other NAE devices on the site. For a single NAE55 on a network without
an Application and Data Server (ADS), there is no flicker.
Run (Green) On Steady On Steady = NAE55 software is running.
On 1 second, Off 1 second = NAE55 software is in startup mode.
On 0.5 seconds, Off 0.5 seconds = NAE55 software is shutting down.
Off Steady = Operating system is shutting down or software is not running.
24 VAC (Green) On Steady On Steady = 24 VAC power is present.
Off Steady = Loss of 24 VAC power. In the Off Steady condition, the NAE55 can
be running on battery power. Also see the POWER LED.
BATT FAULT (Red) Off Steady On Steady = Battery fault. Replace the battery. Battery is not connected or cannot
be charged. The BATT FAULT LED may remain On for up to 24 hours after initially
powering on the NAE55. If the BATT FAULT LED remains on longer than 48 hours
after initially powering on the NAE55, check the battery connection or replace the
battery.
GENL FAULT (Red) Off Steady On Steady = General Fault. Fault conditions are user configurable in software.
Preconfigured fault conditions include excessive memory use, excessive flash use,
excessive CPU or printed wire board (PWB) temperature, and Battery Fault. In
normal operation, the GENL FAULT LED stays on steady for the first half of the
startup sequence.

NAE55/NIE55 Installation Instructions 14


Repair Information
If you replace an NAE55 for any reason or add a new NAE55 to a site, you must update the site registration to ensure
that the new NAE55 is recognized and able to communicate. Refer to the Replacing an NAE section in the NAE
Commissioning Guide (LIT-1201519) for information on replacing an NAE and configuring the new NAE to
communicate in a Metasys system site.
Except for replacing the data protection battery, the NAE55 cannot be repaired in the field. If the NAE55 fails to
operate, it must be replaced. If you need to repair the UL 864 9th Edition UUKL/ORD-C100-13 UUKLC listed
MS-NAE5510-2U network engine, please contact the Johnson Controls Repair Center in Louisville, Kentucky, at
1-502-671-7312.
Batteries removed from this device must be recycled or disposed of in accordance with local, national, and regional
regulations. Only trained technicians or qualified building maintenance personnel should service Johnson Controls®
products.

Ordering Information
Table 8: NAE55-2 Ordering Information
Product Code Description
1
Number
MS-NAE55xx-x (Base NAE55 Network Automation Engine: Requires a 24 VAC power supply. Model includes two RS-232-C
Features of NAE55) serial ports, two USB serial ports, two RS-485 ports, one Ethernet port, and one MS-BAT1010-0 Data
Protection Battery. Supports up to 100 devices on each N2 or BACnet MS/TP trunk.
MS-NAE5510-2U Supports two N2 or two BACnet MS/TP (RS-485) trunks (or one N2 trunk and one BACnet MS/TP trunk).
Note: This model is UL 864 9th Edition UUKL/ORD-C100-13 UUKLC Standard for Smoke Control
Equipment. Refer to the NAE55/NIE55 Installation Instructions (Part No. 24-10051-0) and the
Metasys® System UL 864 9th Edition UUKL/ORD-C100-13 UUKLC Smoke Control System
Technical Bulletin (LIT-12011252) for detailed specifications, requirements, and procedures for
installing and operating UUKL 864 Listed Metasys system devices.

Table 9: NAE55-3 Ordering Information


Product Code Description
1
Number
MS-NAE55xx-x (Base NAE55 Network Automation Engines: Require a 24 VAC power supply. Each model includes two RS-232-C
Features of Each serial ports, two USB serial ports, two RS-485 ports, one Ethernet port, and one MS-BAT1010-0 Data
NAE55) Protection Battery. Supports up to 100 devices on each N2 or BACnet MS/TP trunk.
MS-NAE5510-3 Supports two N2 or two BACnet MS/TP (RS-485) trunks (or one N2 trunk and one BACnet MS/TP trunk).
MS-NAE5511-3 Supports two N2 or two BACnet MS/TP (RS-485) trunks (or one N2 trunk and one BACnet MS/TP trunk);
includes an internal modem.
MS-NAE5520-3 Supports a LONWORKS trunk and two N2 trunks or two BACnet MS/TP (RS-485) trunks (or one N2 trunk
and one BACnet MS/TP trunk). Supports up to 255 devices on the LONWORKS trunk.
MS-NAE5521-3 Supports a LONWORKS trunk, and two N2 trunks or two BACnet MS/TP (RS-485) trunks (or one N2 trunk
and one BACnet MS/TP trunk); includes an internal modem. Supports up to 255 devices on the LONWORKS
trunk.
MS-MULTENGSW-6 Contains ToggleTunnel utility for converting an NAE55/NIE55 to an NAE55 model with the N2 Tunneling
features enabled. Not for use with MS-NAE5510-OU or MS-NIE5510-OU.

NAE55/NIE55 Installation Instructions 15


Table 10: NIE55-3 Series Ordering Information
Product Code Description
1
Number
MS-NIE55xx-x (Base NIEs: Require a 24 VAC power supply. Each model includes two RS-232-C serial ports, two USB serial
Features of Each ports, one Ethernet port, and one MS-BAT1010-0 Data Protection Battery.
NIE55)
MS-NIE5510-3 Supports N1 network migrations.
MS-NIE5511-3 Supports N1 network migrations, includes an internal modem.

Table 11: Accessories Ordering Information


Product Code Description
1
Number
MS-BAT1010-0 Replacement data protection battery for NAE55 and NIE models. Rechargeable gel cell battery with a
typical life of 3 to 5 years at 21°C (70°F).
AS-XFR100-1 Power transformer (Class 2, 24 VAC, 92 VA maximum output), with enclosure
AS-XFR010-1 Power transformer (Class 2, 24 VAC, 92 VA maximum output), no enclosure

1 Some models are also available in a Buy American version (add a G after the code number). For the European version, add
an E after the code number. For repair parts, add -702 after the code number.

Technical Specifications
The MS-NAE5510-2U network engine complies with UL 864 9th Edition UUKL/ORD-C100-13 UUKLC Smoke Control
Listing for United States and Canada. Refer to Metasys® System UL 864 9th Edition UUKL/ORD-C100-13 UUKLC
Smoke Control System Technical Bulletin (LIT-12011252) for specific UL 864 UUKL listing guidelines that must be
followed per UL864.
Table 12: MS-NAE5510-2U
Power Requirement Dedicated nominal 24 VAC, Class 2 power supply (North America), SELV power supply
(Europe), at 50/60 Hz (20 VAC minimum to 30 VAC maximum)
Power Consumption 50 VA maximum
Ambient Operating Conditions 0 to 50°C (32 to 122°F); 10 to 90% RH, 30°C (86°F) maximum dew point
Ambient Storage Conditions -40 to 70°C (-40 to 158°F); 5 to 95% RH, 30°C (86°F) maximum dew point
Data Protection Battery Supports data protection on power failure. Rechargeable gel cell battery: 12 V, 1.2 Ah, with
a typical life of 3 to 5 years at 21°C (70°F); Product Code Number: MS-BAT1010-0
Clock Battery Maintains real-time clock through a power failure. Onboard cell; typical life 10 years at 21°C
(70°F)
Processor 1.6 GHz Intel® Atom™ processor
Memory 4 GB flash nonvolatile memory for operating system, configuration data, and operations data
storage and backup.
1 GB synchronous dynamic random access memory (SDRAM) for operations data dynamic
memory for all models
Operating System Johnson Controls OEM Version of Microsoft® Windows® Standard 2009

NAE55/NIE55 Installation Instructions 16


Table 12: MS-NAE5510-2U
Network and Serial Interfaces One Ethernet port; 10/100/1,000 Mbps; 8-pin RJ-45 connector
Two optically isolated RS-485 ports; 9,600, 19.2k, 38.4k, or 76.8k baud; pluggable and keyed
4-position terminal blocks
Two RS-232-C serial ports, with standard 9-pin sub-D connectors, that support all standard
baud rates
Two USB serial ports; standard USB connectors support an optional, user-supplied external
modem
Housing Plastic housing with internal metal shield
Plastic material: ABS + polycarbonate; Protection: IP20 (IEC 60529)
Mounting On flat surface with screws on four mounting feet or on dual 35 mm DIN rail
Dimensions(Height x Width x 226 x 332 x 96.5 mm (8.9 x 13.1 x 3.8 in.) including mounting feet
Depth)
Minimum space for mounting: 303 x 408 x 148 mm (12.0 x 16.1 x 5.8 in.)
Shipping Weight 2.9 kg (6.4 lb)
Compliance United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment,
FCC Compliant to CFR47, Part 15, Subpart B, Class A
Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment,
Industry Canada Compliant, ICES-003
Europe: CE Mark - Johnson Controls, Inc. declares that this product is in compliance with
the essential requirements and other relevant provisions of the EMC Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
BACnet International: BACnet Testing Laboratories™ (BTL) 35-2004 Listed BACnet Building
Controller (B-BC)

The performance specifications are nominal and conform to acceptable industry standard. For application at conditions
beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.
Table 13: NAE55xx-3 and NIE55xx-3
Power Requirement Dedicated nominal 24 VAC, Class 2 power supply (North America), SELV power supply
(Europe), at 50/60 Hz (20 VAC minimum to 30 VAC maximum)
Power Consumption 50 VA maximum
Ambient Operating Conditions 0 to 50°C (32 to 122°F); 10 to 90% RH, 30°C (86°F) maximum dew point
Ambient Storage Conditions -40 to 70°C (-40 to 158°F); 5 to 95% RH, 30°C (86°F) maximum dew point
Data Protection Battery Supports data protection on power failure. Rechargeable gel cell battery: 12 V, 1.2 Ah, with
a typical life of 3 to 5 years at 21°C (70°F); Product Code Number: MS-BAT1010-0
Clock Battery Maintains real-time clock through a power failure. Onboard cell: typical life of 10 years at 21°C
(70°F)
Processor 1.46 GHz Intel Atom® Bay Trail E3815 processor for MS-NAE55xx-3 models
Memory 16 GB flash nonvolatile memory for operating system, configuration data, and operations data
storage and backup for MS-NAE55xx-3 models.
2 GB DDR3 SDRAM for operations data dynamic memory for all models
Operating System Johnson Controls OEM Version of Microsoft Windows Embedded Standard 7 with SP1 (WES7)

NAE55/NIE55 Installation Instructions 17


Table 13: NAE55xx-3 and NIE55xx-3
Network and Serial Interfaces One Ethernet port; 10/100/1,000 Mbps; 8-pin RJ-45 connector
Two optically isolated RS-485 ports; 9,600, 19.2k, 38.4k, or 76.8k baud; pluggable and keyed
4 position terminal blocks (RS-485 terminal blocks available on NAE55 models only)
Two RS-232-C serial ports, with standard 9-pin sub-D connectors, that support all standard
baud rates
Two USB 2.0 serial ports; standard USB connectors support an optional, user-supplied external
modem
Options: One telephone port for internal modem; up to 56 kbps; 6-pin RJ-12 connector; one
LONWORKS port; FTT10 78 Kbps; pluggable, keyed 3-position terminal block (LONWORKS port
available on NAE552x-x models only)
Housing Plastic housing with internal metal shield
Plastic material: ABS + polycarbonate; Protection: IP20 (IEC 60529)
Mounting On flat surface with screws on four mounting feet or on dual 35 mm DIN rail
Dimensions(Height x Width x 226 x 332 x 96.5 mm (8.9 x 13.1 x 3.8 in.) including mounting feet
Depth)
Minimum space for mounting: 303 x 408 x 148 mm (12.0 x 16.1 x 5.8 in.)
Shipping Weight 2.9 kg (6.4 lb)
Compliance United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment,
FCC Compliant to CFR47, Part 15, Subpart B, Class A
Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment,
Industry Canada Compliant, ICES-003
Europe: CE Mark - Johnson Controls, Inc. declares that this product is in compliance with
the essential requirements and other relevant provisions of the EMC Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
BACnet International: BTL 35-2004 Listed B-BC

The performance specifications are nominal and conform to acceptable industry standard. For application at conditions
beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.

European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
WESTENDHOF 3 507 E MICHIGAN ST C/O CONTROLS PRODUCT MANAGEMENT
45143 ESSEN MILWAUKEE WI 53202 NO. 22 BLOCK D NEW DISTRICT
GERMANY USA WUXI JIANGSU PROVINCE 214142
CHINA

Building Technologies & Solutions


507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
All other marks herein are the marks of their respective owners.© 2017 Johnson Controls

Published in U.S.A. www.johnsoncontrols.com


NAE55/NIE55 Installation Instructions 18

You might also like