Condition Monitoring of EHV
Circuit Breakers and Case
Studies on DCRM Test
03/27/2021 Gyanendra Sharma, NPTI Delhi 1
SWITCHYARD EQUIPMENTS
TRANSFORMERS AND REACTORS
CIRCUIT BREAKERS
CURRENT TRANSFORMERS
CAPACITIVE VOLTAGE TRANSFORMERS
SURGE ARRESTERS
ISOLATORS, WAVE TRAPS, BUS BARS
SPARES etc.
03/27/2021 Gyanendra Sharma, NPTI Delhi 2
WHY MAINTENANCE?
HUMAN SAFETY
EQUIPMENT LIFE
COST OF BREAK DOWN
TIME & COST OF REPAIR
RELIABILITY OF SERVICE
03/27/2021 Gyanendra Sharma, NPTI Delhi 3
MAINTENANCE PHILOSOPHY
BREAK DOWN MAINTENANCE
PREVENTIVE MAINTENANCE
CONDITION BASED MAINTENANCE
RELIABILITY CENTRED
MAINTENANCE
MAINTENANCE PREVENTION
03/27/2021 Gyanendra Sharma, NPTI Delhi 4
CB Standards
For Circuit Breakers IEC 62271-100
For New SF6 IEC 60376
SF6 in Service IEC 60480
03/27/2021 Gyanendra Sharma, NPTI Delhi 5
Switch gear - It's function
Gear for Switching
Switching Decision making Sensing
device devices devices
• Current
• Circuit Breaker • Relays Transformer
• Voltage
Transformer
03/27/2021 Gyanendra Sharma, NPTI Delhi 6
One and a Half Breaker scheme
ICT-1 ICT-2 ICT-3 (F)
BUS-II
989B 689B 389B
952 652
989A 689A
889B 589B 289B
852 252
552
889A 589A 289A
489B 189B
452 152
4CT 1CT
789A 489A 189A
BUS-I
489L 189L
4CVT 1CVT
4 LA 1 LA
AGRA(fUTURE) BASSI BALLABHGARH
03/27/2021 Gyanendra Sharma, NPTI Delhi 7
Double Main and Transfer Bus Scheme
T-BUS
MAIN BUS-I
MAIN BUS-II
689A 189C
289A 289C
789B 789A 789C 689B 689C 589B 589A 489B 489A 289B 189B 189A
x
x x x 752
x 6652 x 552
452
x x
252
x 152
5 289L 189L
789L 2 689L 589C
7CT
6CT
6CVT
7CVT
7LA ICT-3(F) ICT-2 ICT-1
6LA
To HVPNL To HVPNL ALWAR (RVPNL)BHIWADI (RVPNL)TRANSFER BUS BUS COUPLER
HVPNL LINES ARE NOT CONNECTED
03/27/2021 Gyanendra Sharma, NPTI Delhi 8
Type of CBs
03/27/2021 Gyanendra Sharma, NPTI Delhi 9
Dielectric Strength of different
mediums
03/27/2021 Gyanendra Sharma, NPTI Delhi 10
CB Operation
03/27/2021 Gyanendra Sharma, NPTI Delhi 11
Current interruption
03/27/2021 Gyanendra Sharma, NPTI Delhi 12
Resistance Circuit
03/27/2021 Gyanendra Sharma, NPTI Delhi 13
Inductance Circuit
03/27/2021 Gyanendra Sharma, NPTI Delhi 14
Line/ Filter Switching
03/27/2021 Gyanendra Sharma, NPTI Delhi 15
Reactor Switching
03/27/2021 Gyanendra Sharma, NPTI Delhi 16
Transient Recovery Voltage (TRV)
03/27/2021 Gyanendra Sharma, NPTI Delhi 17
Recovery Voltage and build up of
dielectric strength of the medium
Dielectric
Strength
TRV
03/27/2021 Gyanendra Sharma, NPTI Delhi 18
Unsuccessful arc quenching
03/27/2021 Gyanendra Sharma, NPTI Delhi 19
First Pole-to-clear Factor
The ratio of the power frequency voltage
between the sound phase and the other two
phases during a two or more phase short
circuit, which may or may not involve earth, at
the location of the circuit breaker, to the
phase-to-neutral voltage which would be
obtained at the same location with the short
circuit removed.
03/27/2021 Gyanendra Sharma, NPTI Delhi 20
Effect of First Pole-to-clear
3-phase operation: arc-extinction is not
B CB
simultaneous in three poles (currents
1200 apart)
Y
3-FAULT
Power frequency recovery n
R
voltage in first-pole-to- clear
= 1.5 * phase voltage(Unearthed system) F
= 1.3 for non effectively (Earthed vRF
through impedance) earthed system
= 1.0 solidly earthed system
R R R
n n n
F
F
Y F B Y B Y B
Un-earthed Non-effectively earthed Earthed
03/27/2021 Gyanendra Sharma, NPTI Delhi 21
CB Interrupter
03/27/2021 Gyanendra Sharma, NPTI Delhi 22
Operating Links
03/27/2021 Gyanendra Sharma, NPTI Delhi 23
03/27/2021 Gyanendra Sharma, NPTI Delhi 24
03/27/2021 Gyanendra Sharma, NPTI Delhi 25
Operating Mechanism
Hydraulic - Hydraulic
Pneumatic – Pneumatic
Spring – Spring
Pneumatic - Spring
03/27/2021 Gyanendra Sharma, NPTI Delhi 26
Performance of Circuit
Breakers
03/27/2021 Gyanendra Sharma, NPTI Delhi 27
Circuit Breaker Failures
Due to
manufacturing
defects
Due to design
defects
Due to improper
maintenance
03/27/2021 Gyanendra Sharma, NPTI Delhi 28
Reasons of CB Failures in
POWERGRID
MECHANICAL - 80%
(OPERATING COMPONENTS FAILURES)
ELECTRICAL - 16%
(DIELECTRIC FAILURE)
OTHERS - 4%
03/27/2021 Gyanendra Sharma, NPTI Delhi 29
CB Failures
Due to looseness of Helicoil
Looseness of PIR contact
Air leakage in operating mechanism
Problems with MCI and failure of Actuator ring
Frequent problems of Magnetic Ventils
Due to PIR failure
Pitting on contacts
Leakage of Hydraulic oil
03/27/2021 Gyanendra Sharma, NPTI Delhi 30
CB failure - Helicoil problem
03/27/2021 Gyanendra Sharma, NPTI Delhi 31
Mechanical disengagement of moving
contact assembly from heli-coil joint
03/27/2021 Gyanendra Sharma, NPTI Delhi 32
PIR ASSEMBLY FAILURES
MECHANICAL BLASTING OF CB
BREAKAGE OF PTFE
ROD DUE TO PIR
PROBLEM
03/27/2021 Gyanendra Sharma, NPTI Delhi 33
Bending of PIR pull rod
03/27/2021 Gyanendra Sharma, NPTI Delhi 34
Condition Monitoring of CBs
Timing Measurement
Dew Point Measurement
Tan delta of grading capacitors
Static Contact resistance
Dynamic Contact Resistance
(DCRM)
03/27/2021 Gyanendra Sharma, NPTI Delhi 35
Timing Measurement
Breaker Timings are to be monitored on
yearly basis
Importance of Pole Discrepancy Timings
Importance of CO Timing
Importance of PIR Timing
03/27/2021 Gyanendra Sharma, NPTI Delhi 36
DEW POINT MEASUREMENT
SOURCES OF MOISTURE IN CB
GAS HANDLING – FILLING AND EMPTYING THE
CB. AIR MAY BE LEFT DURING EVACUATION
WHICH SHALL ADD TO IMPURITIES IN SF6 GAS.
EVACUATION TO BE DONE UPTO 1 mbar (CIGRE-
WG23)
EXUDATION OF MOISTURE CONTAINED IN
ORGANIC INSULATING MATERIALS.
PERMEATION THROUGH SEALED SECTIONS
03/27/2021 Gyanendra Sharma, NPTI Delhi 37
DEW POINT MEASUREMENT
03/27/2021 Gyanendra Sharma, NPTI Delhi 38
DEW POINT MEASUREMENT
IF SF6 GAS CONTAINS MOISTURE, IT IS
EASILY HYDRATED TO PRODUCE HIGHLY
REACTIVE H2SO3 AND HF (HYDROGEN
FLUORIDES).
AS THESE CHEMICALS CAUSE
DEGRADATION OF INSULATION AND
CORROSION IN THE INTERRUPTING
CHAMBER, MONITORING OF MOISTURE
CONTENT IN SF6 GAS IS VERY
IMPORTANT.
03/27/2021 Gyanendra Sharma, NPTI Delhi 39
CONTAMINATION OF SF6 GAS BY
MOISTURE
03/27/2021 Gyanendra Sharma, NPTI Delhi 40
Measurement of Static Contact
Resistance
To be measured with Breaker closed
Indicate healthiness of Main Contacts
To be measured with Precision
instruments due to its low value (in micro
ohm)
Values to be compared with the previous
measurement
03/27/2021 Gyanendra Sharma, NPTI Delhi 41
Measurement of Dynamic
Contact Resistance
03/27/2021 Gyanendra Sharma, NPTI Delhi 42
Healthy Contacts of CB after
16 years
03/27/2021 Gyanendra Sharma, NPTI Delhi 43
Contact Condition of CB after 16
Years
03/27/2021 Gyanendra Sharma, NPTI Delhi 44
Eroded finger contact after 7-8 years
Old
New
03/27/2021 Gyanendra Sharma, NPTI Delhi 45
PROBLEMS IN CB AFTER 7-8 YEARS
03/27/2021 Gyanendra Sharma, NPTI Delhi 46
NEED FOR DCRM
During normal contact resistance
measurement, healthiness of main
contacts is evaluated
Req = R*r/(R+r)= r/(1+r/R), r = Main
contact
R = Arcing contacts
DCRM signatures/finger prints indicate
true condition of CB arcing contacts.
Arcing contact play vital role during CB
operation
03/27/2021 Gyanendra Sharma, NPTI Delhi 47
DYNAMIC CONTACT RESISTANCE
MEASUREMENT (DCRM)
CONTACT RESISTANCE MEASUREMENT DURING
CLOSING AND TRIPPING OPERATION. C-O DELAY
TIME ABOUT 300MS.
100 AMP CURRENT IS INJECTED THROUGH CB
CONTACTS.
VOLTAGE DROP AND CURRENT IS MEASURED TO
COMPUTE CONTACT RESISTANCE.
VARIATION IN FINGER PRINT OF DCRM INDICATE
PROBLEM IN ARCING AND MAIN CONTACTS.
03/27/2021 Gyanendra Sharma, NPTI Delhi 48
Basic connection arrangement
for DCRM Measurement
03/27/2021 Gyanendra Sharma, NPTI Delhi 49
DCRM Equipment
CB
DCRM
PC
HISAC 2406x
HISAC
MB 3.0
PRINTER
03/27/2021 Gyanendra Sharma, NPTI Delhi 50
DCRM CONNECTION
ARRANGEMENT
03/27/2021 Gyanendra Sharma, NPTI Delhi 51
Typical DCRM Signature
03/27/2021 Gyanendra Sharma, NPTI Delhi 52
DCRM can detect…
Erosion of Arcing Contact
Erosion of main contact
Contact misalignments
Contact wipe of main and arcing
contact
Main & arcing contact resistance
Healthiness of damping system
Contact travel & speed
03/27/2021 Gyanendra Sharma, NPTI Delhi 53
Contact Travel and Insertion
Details
Travel
Total Main Arcing
Contact
Contact Contact Insertion
Insertion Insertion
CGL 230mm/ 28 mm 12 mm 16 mm
140mm
BHEL 242/ 54 mm 34 mm 20 mm
130mm
ABB 200mm 50 mm 20 mm 30 mm
AREVA 180mm 45 mm 25 mm 20 mm
03/27/2021 Gyanendra Sharma, NPTI Delhi 54
Contact speed
Trip velocity Close velocity
5-8 m/sec 3-4 m/sec
03/27/2021 Gyanendra Sharma, NPTI Delhi 55
03/27/2021 Gyanendra Sharma, NPTI Delhi 56
03/27/2021 Gyanendra Sharma, NPTI Delhi 57
03/27/2021 Gyanendra Sharma, NPTI Delhi 58
03/27/2021 Gyanendra Sharma, NPTI Delhi 59
03/27/2021 Gyanendra Sharma, NPTI Delhi 60
DCRM case Studies
03/27/2021 Gyanendra Sharma, NPTI Delhi 61
Case Study-1
400kV SF6 CB commissioned in 1997 was
controlling Bus Reactor.
CB had given about 8 years service with 1400
operations.
03/27/2021 Gyanendra Sharma, NPTI Delhi 62
Healthy Pole
03/27/2021 Gyanendra Sharma, NPTI Delhi 63
Suspected Pole
03/27/2021 Gyanendra Sharma, NPTI Delhi 64
Observations
Moving Arcing contact was found de-shaped and
had expanded
One Counter Head Screw of Moving Main Contact
assembly was found loose
PTFE Nozzle of moving contact assembly found
cracked.
Scratch marks were also seen on Main Moving
Contact
03/27/2021 Gyanendra Sharma, NPTI Delhi 65
De-shaped Arcing Contact
03/27/2021 Gyanendra Sharma, NPTI Delhi 66
Loose Screw and marks on main
contact
03/27/2021 Gyanendra Sharma, NPTI Delhi 67
Case Study-2
This CB was commissioned in 1993 at
Hissar and was controlling a
Transmission Line.
DCRM signatures after closing
operation were not stable and wide
variations were observed.
03/27/2021 Gyanendra Sharma, NPTI Delhi 68
DCRM Signature of defective CB
03/27/2021 Gyanendra Sharma, NPTI Delhi 69
Internal Inspection of
Suspected CBs
The CB was opened for internal
inspection.
Bearing Bush (part no. SG90011024)
used for moving main contact to the
operating lever had loosened
This caused misalignment and
subsequent damage to moving contact
Finger Contact Assembly.
Defective Components were replaced
03/27/2021 Gyanendra Sharma, NPTI Delhi 70
Bearing Bush was missing
03/27/2021 Gyanendra Sharma, NPTI Delhi 71
Case Study-3
400kV ABB make CB at Hyderabad
03/27/2021 Gyanendra Sharma, NPTI Delhi 72
Disengaged coupling bolt
Moving
Long Rod Contact
Assembly
03/27/2021 Gyanendra Sharma, NPTI Delhi 73
Helicoil problem
Helicoil
03/27/2021 Gyanendra Sharma, NPTI Delhi 74
DCRM Signatures after
rectification
03/27/2021 Gyanendra Sharma, NPTI Delhi 75
Case Study - 4
Jamshedpur Substation on
26.04.2007
03/27/2021 Gyanendra Sharma, NPTI Delhi 76
220kV CB at Rourkela s/s overhauled by
CGL Engineer – B phase of 552 as on
24.11.2006
03/27/2021 Gyanendra Sharma, NPTI Delhi 77
220kV CB at Rourkela s/s – Y phase of
552 as on 24.11.2006
03/27/2021 Gyanendra Sharma, NPTI Delhi 78
Travel
After lot of persuasion with CGL, Service
Engineer was deputed on 23.05.2007.
Following observations were found:
Actual Wipe of Contacts = 27-28mm
Arcing Contacts = 15-17mm
Main Contacts = 10-12mm
Wipe found as 21mm which was adjusted to
29mm on 24.05.2007
03/27/2021 Gyanendra Sharma, NPTI Delhi 79
220kV CB at Rourkela s/s – B phase of
552 as on 24.05.2007
03/27/2021 Gyanendra Sharma, NPTI Delhi 80
Internal Inspection of CBs
About 50 nos. CBs have been opened so far
based on DCRM evaluations.
Erosion of Contacts, Misalignment, loose
connection etc. problems were observed.
Timely inspection of CBs could help in
rectification of CBs and hence avoiding
major failures.
03/27/2021 Gyanendra Sharma, NPTI Delhi 81
Conclusion
DCRM Test (non-invasive diagnosis) for
CBs proved useful in indicating condition of
main/ arcing contacts for erosion,
misalignment and looseness etc.
Prevention of Major failures by timely
diagnosis
Major overhauling of Interrupters/ Arcing
chamber can be decided based on DCRM
03/27/2021 Gyanendra Sharma, NPTI Delhi 82
POWERGRID PHILOSOPHY FOR
MAJOR OVERHAULING OF CBs
MANUFACTURER’S RECOMMENDATIONS
AFTER 10 YEARS OF COMMISSIOINING OR
AFTER 5000 OPERATIONS WHICHEVER IS
EARLIER
POWERGRID’S PHILOSOPHY
BASED ON EVALUATION OF CONDITION
MONITORING TEST RESULTS LIKE DCRM,
OPERATING TIMINGS, CONTACT TRAVEL ETC.
INITIALLY, 2 NOS. CBs ARE INSPECTED/
OVERHAULED AND BASED ON THE EXPERIENCE
GAINED, DECISION FOR OVERHAUL OF BALANCE
CBs CAN BE TAKEN.
03/27/2021 Gyanendra Sharma, NPTI Delhi 83
POWERGRID EXPERINCE ON
OVERHAULING OF CBs
POWERGRID has so far overhauled
total of 210 Nos. CBs
03/27/2021 Gyanendra Sharma, NPTI Delhi 84
Capacitance and Tan
Delta Measurement
03/27/2021 Gyanendra Sharma, NPTI Delhi 85
Equivalent Circuit
03/27/2021 Gyanendra Sharma, NPTI Delhi 86
Tan delta/ Power factor testing concepts
03/27/2021 Gyanendra Sharma, NPTI Delhi 87
Bushing Insulation
03/27/2021 Gyanendra Sharma, NPTI Delhi 88
HV Lead
03/27/2021 Gyanendra Sharma, NPTI Delhi 89
Interference
03/27/2021 Gyanendra Sharma, NPTI Delhi 90
UST Mode of Measurement
Earth will be connected to N Point
Hence only CHL will be measured
03/27/2021 Gyanendra Sharma, NPTI Delhi 91
GST Mode of Measurement
Here measurement is made for the
Parallel combination of CH and CHL
03/27/2021 Gyanendra Sharma, NPTI Delhi 92
GSTg Mode of Measurement
Here measurement is done for CHE
as L is guarded
03/27/2021 Gyanendra Sharma, NPTI Delhi 93
03/27/2021 Gyanendra Sharma, NPTI Delhi 94
Trend Analysis
03/27/2021 Gyanendra Sharma, NPTI Delhi 95