12/18/2019 DAMPERS FOR FIRE BARRIER AND SMOKE APPLICATIONS | UL Product iQ
EMME.R21925 - DAMPERS FOR FIRE BARRIER AND
SMOKE APPLICATIONS
Dampers for Fire Barrier and Smoke Applications
See General Information for Dampers for Fire Barrier and Smoke Applications
BETEC CAD INDUSTRIES (FZC) R21925
Plot of Land P4-02,03 & 04 Saif Zone
PO Box 8805
Sharjah, UNITED ARAB EMIRATES
Fire Dampers for Use in Static Systems
Single Section Multiple Section
Damper
Hr Mounting Damper Size, in. Damper Size, in.
Model Class Position W H W H
FD-GB-20-A/AS/B/BS/AF/BF/R V 39 1/2 39 1/2 72 72
1-1/2 H 36 36 — —
FD-GB/SB/GSB/SGB-22-A/B/AS/BS/R 1-1/2 V 30 48 60 48
FD-GB-20-A/AS/B/BS/R 1-1/2 V/H 30 48 144 96
FD-GB-30-A/AS/B/BS/AF/BF/R 3 V 39 1/2 39 1/2 72 72
FD-GB-30-A/AS/B/BS/R 3 V 30 48 144 96
FD-GB-21-A/AS/B/BS/R 1-1/2 V/H 30 48 144 96
FD-GB-31-A/AS/B/BS/R 3 V 30 48 144 96
MFD-GB -20-A/R V 36 36 72 72
1-1/2 H 36 36 — —
MFD-SB -20-A/R 1-1/2 V/H 36 36 — —
MFD-GSB-20-A/R 1-1/2 V/H 36 36 — —
MFD-SGB-20-A/R 1-1/2 V/H 36 36 — —
MFD/QFD-GB/SB/GSB/SGB-F-20-A/R 1-1/2 H 36 36 — —
MFD-GB -30-A/R V 36 36 72 72
3 H 36 36 — —
MFD-SB-30-A/R 3 V/H 36 36 — —
https://iq.ulprospector.com/en/profile?e=30767 1/5
12/18/2019 DAMPERS FOR FIRE BARRIER AND SMOKE APPLICATIONS | UL Product iQ
MFD-GSB-30-A/R 3 V/H 36 36 — —
MFD-SGB-30-A/R 3 V/H 36 36 — —
MFD/QFD-GB/SB/GSB/SGB-F-30-A/R 3 H 36 36 — —
MFD-GB-31-A/R 3 V 24 48 144 96
MFD-GB-21-A/R 1-1/2 V/H 24 48 144 96
Fire Dampers for Use in Dynamic Systems
Dampers rated 2000 fpm / 4.0 in. WC:
Damper Single Section Multiple Section
Damper Size, in. Damper Size, in.
Hr Mounting
Model Class Position W H W H
FD-GBD-20-AS/BS/AF/BF/R 1-1/2 V 36 36 — —
FD-GBD-30-AS/BS/R 3 V 36 36 — —
MFD-GB/SB/GSB/SGB-D-20-A/R 1-1/2 V/H 36 36 — —
MFD-GB/SB/GSB/SGB-D-30-A/R 3 V/H 36 36 — —
MFD-GB-F-30-A 3 H 36 36 — —
MFD-GB-D -20-A/R 1-1/2 V 36 36 72 72
MFD-GB-D -20-A/R 1-1/2 H 36 36 — —
MFD-SB-D-20-A/R 1-1/2 V/H 36 36 — —
MFD-GSB-D-20-A/R 1-1/2 V/H 36 36 — —
MFD-SGB-D-20-A/R 1-1/2 V/H 36 36 — —
MFD/QFD-GB/SB/GSB/SGB-D-20-A/R 1-1/2 H 36 36 — —
MFD-GB -D-30-A/R 3 V 36 36 72 72
MFD-GB -D-30-A/R 3 H 36 36 — —
MFD-SB-D-30-A/R 3 V/H 36 36 — —
MFD-GSB-D-30-A/R 3 V/H 36 36 — —
MFD-SGB-D-30-A/R 3 V/H 36 36 — —
MFD/QFD-GB/SB/GSB/SGB-D-30-A/R 3 H 36 36 — —
MFD-GB-D-31-A/R 3 V 24 48 144 96
MFD-GB-D-21-A/R 1-1/2 V/H 24 48 144 96
Combination Fire and Smoke Dampers
Dampers rated 2000 fpm / 4.0 in. WC:
https://iq.ulprospector.com/en/profile?e=30767 2/5
12/18/2019 DAMPERS FOR FIRE BARRIER AND SMOKE APPLICATIONS | UL Product iQ
Single Section Multiple Section
Damper Size, in. Damper Size, in.
Damper
Leakage Mounting W H
Model Hr Class Class Position Min Max Min Max W H
MSFD-GBD-20C2-A/R 1-1/2 II-250 V 9 24 9 24 — —
V 9 36 9 36 72 36
MSFD-GB-20C2-A/R 1-1/2 II-250 H 9 36 9 36 — —
V 9 36 9 36 72 36
MSFD-GSB-20C2-A/R 1-1/2 II-250 H 9 36 9 36 — —
V 6 36 6 36 72 36
MSFD-GB-20C1-A/R 1-1/2 I-250 H 6 36 6 36 — —
V 6 36 6 36 72 36
MSFD-GSB-20C1-A/R 1-1/2 I-250 H 6 36 6 36 — —
V 9 36 9 36 72 36
MSFD-GB-30C2-A/R 3 II-250 H 9 36 9 36 — —
V 9 36 9 36 72 36
MSFD-GSB-30C2-A/R 3 II-250 H 9 36 9 36 — —
V 6 36 6 36 72 36
MSFD-GB-30C1-A/R 3 I-250 H 6 36 6 36 — —
V 6 36 6 36 72 36
MSFD-GSB-30C1-A/R 3 I-250 H 6 36 6 36 — —
MSFD-GB-21C1-A/R 1-1/2 I-250 V/ H 6 24 9 48 144 96
MSFD-GB-21C2-A/R 1-1/2 II-250 V/ H 6 24 9 48 144 96
MSFD-GB-21C3-A/R 1-1/2 III-350 V/ H 6 24 9 48 144 96
MSFD-GB-31C1-A/R 3 I-250 V 6 24 9 48 144 96
MSFD-GB-31C2-A/R 3 II-250 V 6 24 9 48 144 96
MSFD-GB-31C3-A/R 3 III-350 V 6 24 9 48 144 96
MSFD-GB-F-30C2-A/R 3 II-250 H 6 36 8 36 — —
Smoke Dampers
Dampers rated 2000 fpm/4.0 in. WC:
Damper Single Section Multiple Section
Leakage Mounting Damper Size, in. Damper Size, in.
Model Class Position W H W H
https://iq.ulprospector.com/en/profile?e=30767 3/5
12/18/2019 DAMPERS FOR FIRE BARRIER AND SMOKE APPLICATIONS | UL Product iQ
Min Max Min Max
MSD-GBD-20C2-A/R II-250 V/H 9 24 9 24 — —
MSD-GB-20C2-A/R II-250 V/H 9 36 9 36 72 36
MSD-GSB-20C2-A/R II-250 V/H 9 36 9 36 72 36
MSD-GB-20C1-A/R I-250 V/H 6 36 6 36 72 36
MSD-GSB-20C1-A/R I-250 V/H 6 36 6 36 72 36
MSD-GB-30C1-A/R I-250 V/H 6 36 6 36 72 36
MSD-GB-21C1-A/R I-250 V/H 6 36 9 48 144 96
288 48
MSD-GB-21C2-A/R II-250 V/H 6 36 9 48 144 96
288 48
MSD-GB-21C3-A/R III-250 V/H 6 36 9 48 144 96
288 48
III-350 V/H 6 24 9 48 96 48
MSD-S-30C1-A/R I-250 V/H 9 36 9 36 72 36
Dampers rated 3000 fpm/6.0 in. WC:
Single Section Multiple Section
Damper Size, in. Damper Size, in.
Damper
W H
Leakage Mounting
Model Class Position Min Max Min Max W H
MSD-B-40C2-BG, TVD-B-40C2-BG II-350 V/H 8 40 8 48 160 48
MSD-B- 40C3-BG, TVD-B-40C3-BG III-350 V/H 8 40 8 48 160 48
For Curtain type fire damper
A: Blades in air stream, B: Blades above air stream, S: with sleeve, F: with mounting frame, R: with Round spigot & D: for dynamic application.
For Motorized fire damper
GB: GI Frame / GI Blade, SB: SS Frame / SS Blade, GSB: GI Frame / SS Blade, SGB: SS Frame / GI Blade & R: Round Spigot & D: for dynamic
application
Trademark and/or Tradename:
Last Updated on 2019-11-06
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
https://iq.ulprospector.com/en/profile?e=30767 4/5
12/18/2019 DAMPERS FOR FIRE BARRIER AND SMOKE APPLICATIONS | UL Product iQ
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following
format: "© 2019 UL LLC"
https://iq.ulprospector.com/en/profile?e=30767 5/5