Power Factor: What Is The Difference Between Lagging Power Factor and Leading Power Factor?
Power Factor: What Is The Difference Between Lagging Power Factor and Leading Power Factor?
The ratio of watts average power (the average power measured in watts) to the
apparent power of an alternating-current circuit. By definition, the equation below
holds, which is the ratio of instrument readings.
Using highly inductive loads may lead to reduction in the power factor. or
consumption of unappreciable amount of power also results in the same.
What is the difference between lagging power factor and leading power
factor?
Power factor is the ratio of watts (true power) to VA (volt-amperes, also called apparent power).
Where the load is resistive only, the power factor is one, or unity, because the voltage waveform
and the current waveform are in phase. Thus, for resistive loads only, true power and VA are the
same.
Where the load is reactive, the load stores energy, releasing it during a different part of the cycle.
This shifts the current waveform so that it is offset, or out of phase with the voltage waveform.
When the load is inductive, the inductance tends to oppose the flow of current,
storing energy then releasing it later in the cycle. The current waveform lags
behind the voltage waveform. When the load is capacitive, the opposite occurs, and
the current waveform leads the voltage waveform.
So, lagging vs. leading is another way of saying the net reactance is either
inductive or capacitive.
This is slightly simplistic, and what we are talking about above is really DPF, or
Displacement Power Factor. Non-linear loads don't really shift the current
waveform, they distort it. The current waveform starts to look like a square wave,
and square waves contain harmonics. So non-linear loads add harmonic distortion,
and this tends to mimic a capacitively reactive load, adding some leading power
factor. So when we say power factor, we really must include DPF plus harmonic
distortion in total.
One memory aid that may help to remember all this is:
The L in ELI means inductance. The E (voltage) comes first, then the I (current)
lags behind. Inductive reactance produces a lagging power factor.
The C in ICE means capacitance. The I (current) comes first (leads) then the E
(voltage) comes later. Capacitive reactance produces a leading power factor.
Remember, it's always the current waveform that is affected by the reactive load,
so you have to think about whether the current is leading or lagging.
The power factor of an AC electric power system is defined as the ratio of the real
power flowing to the load to the apparent power,[1][2] and is a number between 0
and 1 (frequently expressed as a percentage, e.g. 0.5 pf = 50% pf). Real power is
the capacity of the circuit for performing work in a particular time. Apparent
power is the product of the current and voltage of the circuit. Due to energy stored
in the load and returned to the source, or due to a non-linear load that distorts the
wave shape of the current drawn from the source, the apparent power can be
greater than the real power.
In an electric power system, a load with low power factor draws more current than
a load with a high power factor for the same amount of useful power transferred.
The higher currents increase the energy lost in the distribution system, and require
larger wires and other equipment. Because of the costs of larger equipment and
wasted energy, electrical utilities will usually charge a higher cost to industrial or
commercial customers where there is a low power factor.
Linear loads with low power factor (such as induction motors) can be corrected
with a passive network of capacitors or inductors. Non-linear loads, such as
rectifiers, distort the current drawn from the system. In such cases, active power
factor correction is used to counteract the distortion and raise power factor. The
devices for correction of power factor may be at a central substation, or spread out
over a distribution system, or built into power-consuming equipment.
Instantaneous and average power calculated from AC voltage and current with a
unity power factor (φ=0, cosφ=1)
Instantaneous and average power calculated from AC voltage and current with a
zero power factor (φ=90, cosφ=0)
Instantaneous and average power calculated from AC voltage and current with a
lagging power factor (φ=45, cosφ=0.71)
In a purely resistive AC circuit, voltage and current waveforms are in step (or in
phase), changing polarity at the same instant in each cycle. Where reactive loads
are present, such as with capacitors or inductors, energy storage in the loads result
in a time difference between the current and voltage waveforms. This stored
energy returns to the source and is not available to do work at the load. Thus, a
circuit with a low power factor will have higher currents to transfer a given
quantity of real power than a circuit with a high power factor. A linear load does
not change the shape of the waveform of the current, but may change the relative
timing (phase) between voltage and current.
Circuits containing purely resistive heating elements (filament lamps, strip heaters,
cooking stoves, etc.) have a power factor of 1.0. Circuits containing inductive or
capacitive elements (compact fluorescent lamps,[3] lamp ballasts, motors, etc.) often
have a power factor below 1.0.
AC power flow has the three components: real power (P), measured in watts (W);
apparent power (S), measured in volt-amperes (VA); and reactive power (Q),
measured in reactive volt-amperes (var).
If φ is the phase angle between the current and voltage, then the power factor is
equal to , and:
Since the units are consistent, the power factor is by definition a dimensionless
number between 0 and 1. When power factor is equal to 0, the energy flow is
entirely reactive, and stored energy in the load returns to the source on each cycle.
When the power factor is 1, all the energy supplied by the source is consumed by
the load. Power factors are usually stated as "leading" or "lagging" to show the
sign of the phase angle.
If a purely resistive load is connected to a power supply, current and voltage will
change polarity in step, the power factor will be unity (1), and the electrical energy
flows in a single direction across the network in each cycle. Inductive loads such as
transformers and motors (any type of wound coil) consume reactive power with
current waveform lagging the voltage. Capacitive loads such as capacitor banks or
buried cable generate reactive power with current phase leading the voltage. Both
types of loads will absorb energy during part of the AC cycle, which is stored in
the device's magnetic or electric field, only to return this energy back to the source
during the rest of the cycle.
For example, to get 1 kW of real power, if the power factor is unity, 1 kVA of
apparent power needs to be transferred (1 kW ÷ 1 = 1 kVA). At low values of
power factor, more apparent power needs to be transferred to get the same real
power. To get 1 kW of real power at 0.2 power factor, 5 kVA of apparent power
needs to be transferred (1 kW ÷ 0.2 = 5 kVA). This apparent power must be
produced and transmitted to the load in the conventional fashion, and is subject to
the usual distributed losses in the production and transmission processes.
Linear loads
Electrical loads consuming alternating current power consume both real power and
reactive power. The vector sum of real and reactive power is the apparent power.
The presence of reactive power causes the real power to be less than the apparent
power, and so, the electric load has a power factor of less than 1.
It is often desirable to adjust the power factor of a system to near 1.0. This power
factor correction is achieved by switching in or out banks of inductors or
capacitors. For example the inductive effect of motor loads may be offset by
locally connected capacitors. When reactive elements supply or absorb reactive
power near the load, the apparent power is reduced.
Power factor correction brings the power factor of an AC power circuit closer to 1
by supplying reactive power of opposite sign, adding capacitors or inductors which
act to cancel the inductive or capacitive effects of the load, respectively. For
example, the inductive effect of motor loads may be offset by locally connected
capacitors. If a load had a capacitive value, inductors (also known as reactors in
this context) are connected to correct the power factor. In the electricity industry,
inductors are said to consume reactive power and capacitors are said to supply it,
even though the reactive power is actually just moving back and forth on each AC
cycle.
The reactive elements can create voltage fluctuations and harmonic noise when
switched on or off. They will supply or sink reactive power regardless of whether
there is a corresponding load operating nearby, increasing the system's no-load
losses. In a worst case, reactive elements can interact with the system and with
each other to create resonant conditions, resulting in system instability and severe
overvoltage fluctuations. As such, reactive elements cannot simply be applied at
will, and power factor correction is normally subject to engineering analysis.
1. Reactive Power Control Relay; 2. Network connection points; 3. Slow-blow
Fuses; 4. Inrush Limiting Contactors; 5. Capacitors (single-phase or three-phase
units, delta-connection); 6. Transformer Suitable voltage transformation to suit
control power (contactors, ventilation,...)
Depending on the load and power factor of the network, the power factor controller
will switch the necessary blocks of capacitors in steps to make sure the power
factor stays above a selected value (usually demanded by the energy supplier), say
0.9.
Instead of using a set of switched capacitors, an unloaded synchronous motor can
supply reactive power. The reactive power drawn by the synchronous motor is a
function of its field excitation. This is referred to as a synchronous condenser. It is
started and connected to the electrical network. It operates at full leading power
factor and puts vars onto the network as required to support a system’s voltage or
to maintain the system power factor at a specified level.
The condenser’s installation and operation are identical to large electric motors. Its
principal advantage is the ease with which the amount of correction can be
adjusted; it behaves like an electrically variable capacitor. Unlike capacitors, the
amount of reactive power supplied is proportional to voltage, not the square of voltage;
this improves voltage stability on large networks. Synchronous condensors are often used in
connection with high voltage direct current transmission projects or in large industrial plants
such as steel mills.
Non-linear loads
A non-linear load on a power system is typically a rectifier (such as used in a
power supply), or some kind of arc discharge device such as a fluorescent lamp,
electric welding machine, or arc furnace. Because current in these systems is
interrupted by a switching action, the current contains frequency components that
are multiples of the power system frequency.
Non-sinusoidal components
Non-linear loads change the shape of the current waveform from a sine wave to
some other form. Non-linear loads create harmonic currents in addition to the
original (fundamental frequency) AC current. Addition of linear components such
as capacitors and inductors cannot cancel these harmonic currents, so other
methods such as filters or active power factor correction are required to smooth out
their current demand over each cycle of alternating current and so reduce the
generated harmonic currents.
In circuits having only sinusoidal currents and voltages, the power factor effect
arises only from the difference in phase between the current and voltage. This is
narrowly known as "displacement power factor". The concept can be generalized
to a total, distortion, or true power factor where the apparent power includes all
harmonic components. This is of importance in practical power systems which
contain non-linear loads such as rectifiers, some forms of electric lighting, electric
arc furnaces, welding equipment, switched-mode power supplies and other
devices.
A typical multimeter will give incorrect results when attempting to measure the
AC current drawn by a non-sinusoidal load. A true RMS multimeter must be used
to measure the actual RMS currents and voltages (and therefore apparent power).
To measure the real power or reactive power, a wattmeter designed to properly
work with non-sinusoidal currents must be used.
This presents a particular problem for the power companies, because they cannot
compensate for the harmonic current by adding simple capacitors or inductors, as
they could for the reactive power drawn by a linear load. Many jurisdictions are
beginning to legally require power factor correction for all power supplies above a
certain power level.
Passive PFC
The simplest way to control the harmonic current is to use a filter: it is possible to
design a filter that passes current only at line frequency (e.g. 50 or 60 Hz). This
filter reduces the harmonic current, which means that the non-linear device now
looks like a linear load. At this point the power factor can be brought to near unity,
using capacitors or inductors as required. This filter requires large-value high-
current inductors, however, which are bulky and expensive.
A passive PFC requires an inductor larger than the inductor in an active PFC, but
costs less.[5][6]
Passive PFCs are typically more power efficient than active PFCs – a passive PFC
on a switching computer PSU has a typical power efficiency of around 96%, while
an active PFC has a typical efficiency of about 94%.[12]
Active PFC
1. Boost
2. Buck
3. Buck-boost
The significance of power factor lies in the fact that utility companies
supply customers with volt-amperes, but bill them for watts. Power
factors below 1.0 require a utility to generate more than the minimum
volt-amperes necessary to supply the real power (watts). This increases
generation and transmission costs. For example, if the load power factor
were as low as 0.7, the apparent power would be 1.4 times the real
power used by the load. Line current in the circuit would also be 1.4
times the current required at 1.0 power factor, so the losses in the circuit
would be doubled (since they are proportional to the square of the
current). Alternatively all components of the system such as generators,
conductors, transformers, and switchgear would be increased in size
(and cost) to carry the extra current.
Digital instruments can be made that either directly measure the time lag between
voltage and current waveforms and so calculate the power factor, or by measuring
both true and apparent power in the circuit and calculating the quotient. The first
method is only accurate if voltage and current are sinusoidal; loads such as
rectifiers distort the waveforms from the sinusoidal shape.
Mnemonics
The apparent power is the vector sum of real and reactive power
If a capacitor and an inductor are placed in parallel, then the currents flowing
through the inductor and the capacitor tend to cancel out rather than adding.
Conventionally, capacitors are considered to generate reactive power and inductors
to consume it. This is the fundamental mechanism for controlling the power factor
in electric power transmission; capacitors (or inductors) are inserted in a circuit to
partially cancel reactive power of the load.
The apparent power is the product of voltage and current. Apparent power is handy
for sizing of equipment or wiring. However, adding the apparent power for two
loads will not accurately give the total apparent power unless they have the same
displacement between current and voltage (the same power factor).
Engineers use the following terms to describe energy flow in a system (and assign
each of them a different unit to differentiate between them):
In the diagram, P is the real power, Q is the reactive power (in this case positive),
S is the complex power and the length of S is the apparent power.
The unit for all forms of power is the watt (symbol: W), but this unit is generally
reserved for real power. Apparent power is conventionally expressed in volt-
amperes (VA) since it is the product of rms voltage and rms current. The unit for
reactive power is expressed as "VAr", which stands for volt-amperes reactive.
Since reactive power flow transfers no net energy to the load, it is sometimes
called "wattless" power.
Understanding the relationship between these three quantities lies at the heart of
understanding power engineering. The mathematical relationship among them can
be represented by vectors or expressed using complex numbers,
Power factor
The ratio between real power and apparent power in a circuit is called the power
factor. Where the waveforms are purely sinusoidal, the power factor is the cosine
of the phase angle (φ) between the current and voltage sinusoid waveforms.
Equipment data sheets and nameplates often will abbreviate power factor as "cosφ"
for this reason.
Power factor equals 1 when the voltage and current are in phase, and is zero when
the current leads or lags the voltage by 90 degrees. Power factors are usually stated
as "leading" or "lagging" to show the sign of the phase angle, where leading
indicates a negative sign. For two systems transmitting the same amount of real
power, the system with the lower power factor will have higher circulating currents
due to energy that returns to the source from energy storage in the load. These
higher currents in a practical system will produce higher losses and reduce overall
transmission efficiency. A lower power factor circuit will have a higher apparent
power and higher losses for the same amount of real power transfer.
Purely capacitive circuits cause reactive power with the current waveform leading
the voltage wave by 90 degrees, while purely inductive circuits cause reactive
power with the current waveform lagging the voltage waveform by 90 degrees.
The result of this is that capacitive and inductive circuit elements tend to cancel
each other out.
While real power and reactive power are well defined in any system, the definition
of apparent power for unbalanced polyphase systems is considered to be one of the
most controversial topics in power engineering. Originally, apparent power arose
merely as a figure of merit. Major delineations of the concept are attributed to
Stanley's Phenomena of Retardation in the Induction Coil (1888) and Steinmetz's
Theoretical Elements of Engineering (1915). However, with the development of
three phase power distribution, it became clear that the definition of apparent
power and the power factor could not be applied to unbalanced polyphase systems.
In 1920, a "Special Joint Committee of the AIEE and the National Electric Light
Association met to resolve the issue. They considered two definitions:
that is, the quotient of the sums of the real powers for each phase over the sum of
the apparent power for each phase.
that is, the quotient of the sums of the real powers for each phase over the
magnitude of the sum of the complex powers for each phase.
The 1920 committee found no consensus and the topic continued to dominate
discussions. In 1930 another committee formed and once again failed to resolve the
question. The transcripts of their discussions are the lengthiest and most
controversial ever published by the AIEE (Emanuel, 1993). Further resolution of
this debate did not come until the late 1990s.
A perfect resistor stores no energy, so current and voltage are in phase. Therefore
there is no reactive power and P = S. Therefore for a perfect resistor:
For a perfect capacitor or inductor on the other hand there is no net power transfer,
so all power is reactive. Therefore for a perfect capacitor or inductor:
If X is defined as being positive for an inductor and negative for a capacitor then
we can remove the modulus signs from Q and X and get.
Since an RMS value can be calculated for any waveform, apparent power can be
calculated from this.
For real power it would at first appear that we would have to calculate loads of
product terms and average all of them. However if we look at one of these product
terms in more detail we come to a very interesting result.
however the time average of a function of the form cos(ωt + k) is zero provided
that ω is nonzero. Therefore the only product terms that have a nonzero average are
those where the frequency of voltage and current match. In other words it is
possible to calculate real (average) power by simply treating each frequency
separately and adding up the answers.
Harmonic currents can be reduced by a filter placed at the input of the device.
Typically this will consist of either just a capacitor (relying on parasitic resistance
and inductance in the supply) or a capacitor-inductor network. An active power
factor correction circuit at the input would generally reduce the harmonic currents
further and maintain the power factor closer to unity. And hence, the different
components of current is defined.
References
If a capacitor and an inductor are placed in parallel, then the currents flowing
through the inductor and the capacitor tend to cancel out rather than adding.
Conventionally, capacitors are considered to generate reactive power and inductors
to consume it. This is the fundamental mechanism for controlling the power factor
in electric power transmission; capacitors (or inductors) are inserted in a circuit to
partially cancel reactive power of the load.
The apparent power is the product of voltage and current. Apparent power is handy
for sizing of equipment or wiring. However, adding the apparent power for two
loads will not accurately give the total apparent power unless they have the same
displacement between current and voltage (the same power factor).
Engineers use the following terms to describe energy flow in a system (and assign
each of them a different unit to differentiate between them):
The unit for all forms of power is the watt (symbol: W), but this unit is generally
reserved for real power. Apparent power is conventionally expressed in volt-
amperes (VA) since it is the product of rms voltage and rms current. The unit for
reactive power is expressed as "VAr", which stands for volt-amperes reactive.
Since reactive power flow transfers no net energy to the load, it is sometimes
called "wattless" power.
Understanding the relationship between these three quantities lies at the heart of
understanding power engineering. The mathematical relationship among them can
be represented by vectors or expressed using complex numbers,
Power factor
The ratio between real power and apparent power in a circuit is called the power
factor. Where the waveforms are purely sinusoidal, the power factor is the cosine
of the phase angle (φ) between the current and voltage sinusoid waveforms.
Equipment data sheets and nameplates often will abbreviate power factor as "cosφ"
for this reason.
Power factor equals 1 when the voltage and current are in phase, and is zero when
the current leads or lags the voltage by 90 degrees. Power factors are usually stated
as "leading" or "lagging" to show the sign of the phase angle, where leading
indicates a negative sign. For two systems transmitting the same amount of real
power, the system with the lower power factor will have higher circulating currents
due to energy that returns to the source from energy storage in the load. These
higher currents in a practical system will produce higher losses and reduce overall
transmission efficiency. A lower power factor circuit will have a higher apparent
power and higher losses for the same amount of real power transfer.
Purely capacitive circuits cause reactive power with the current waveform leading
the voltage wave by 90 degrees, while purely inductive circuits cause reactive
power with the current waveform lagging the voltage waveform by 90 degrees.
The result of this is that capacitive and inductive circuit elements tend to cancel
each other out.
While real power and reactive power are well defined in any system, the definition
of apparent power for unbalanced polyphase systems is considered to be one of the
most controversial topics in power engineering. Originally, apparent power arose
merely as a figure of merit. Major delineations of the concept are attributed to
Stanley's Phenomena of Retardation in the Induction Coil (1888) and Steinmetz's
Theoretical Elements of Engineering (1915). However, with the development of
three phase power distribution, it became clear that the definition of apparent
power and the power factor could not be applied to unbalanced polyphase systems.
In 1920, a "Special Joint Committee of the AIEE and the National Electric Light
Association met to resolve the issue. They considered two definitions:
that is, the quotient of the sums of the real powers for each phase over the sum of
the apparent power for each phase.
that is, the quotient of the sums of the real powers for each phase over the
magnitude of the sum of the complex powers for each phase.
The 1920 committee found no consensus and the topic continued to dominate
discussions. In 1930 another committee formed and once again failed to resolve the
question. The transcripts of their discussions are the lengthiest and most
controversial ever published by the AIEE (Emanuel, 1993). Further resolution of
this debate did not come until the late 1990s.
A perfect resistor stores no energy, so current and voltage are in phase. Therefore
there is no reactive power and P = S. Therefore for a perfect resistor:
For a perfect capacitor or inductor on the other hand there is no net power transfer,
so all power is reactive. Therefore for a perfect capacitor or inductor:
If X is defined as being positive for an inductor and negative for a capacitor then
we can remove the modulus signs from Q and X and get.
Since an RMS value can be calculated for any waveform, apparent power can be
calculated from this.
For real power it would at first appear that we would have to calculate loads of
product terms and average all of them. However if we look at one of these product
terms in more detail we come to a very interesting result.
however the time average of a function of the form cos(ωt + k) is zero provided
that ω is nonzero. Therefore the only product terms that have a nonzero average are
those where the frequency of voltage and current match. In other words it is
possible to calculate real (average) power by simply treating each frequency
separately and adding up the answers.
Harmonic currents can be reduced by a filter placed at the input of the device.
Typically this will consist of either just a capacitor (relying on parasitic resistance
and inductance in the supply) or a capacitor-inductor network. An active power
factor correction circuit at the input would generally reduce the harmonic currents
further and maintain the power factor closer to unity. And hence, the different
components of current is defined.
Anyone who has heard a refrigeration unit groan through a brownout or been
frustrated by an inexplicable series of control system trips should have a healthy
respect for the effects of power quality on equipment reliability and energy
efficiency. Few doubt that sags and harmonics contribute to downtime, off-spec
production and shortened equipment life.
But, like so many potential projects that improve uptime, product quality and life
cycle cost, it’s hard to make a financial case for spending on power conditioning.
These days, it’s much easier to gain support and financial backing for the rapid
paybacks you can calculate from improving energy efficiency.
The problem is that some of the solution providers significantly overstate the
savings and customers are deceived. Carnovale says, “While these solutions
provide excellent protection, they often provide very little, if any, energy savings.”
Common sense as well as the Electric Power Research Institute (EPRI) point out
that you can only save energy that is wasted. The losses in a typical plant power
system range from 1% to 4%, so eliminating them would, at best, reduce your bill
by 1% to 4%.
But these days, even a couple percent of energy savings can add up to a worthy
return on investment, and paying attention to power quality in the form of power
factor and peak demand can reduce some industrial power bills as much as 30%.
Sources of savings
Sags, surges, interruptions and harmonics wreak havoc on equipment. It’s easy to
believe they contribute to inefficiencies, and they do. But how much?
You might find low-hanging fruit in your existing power quality or uninterruptible
power supply (UPS) equipment. Strides have been made in the efficiency of the
rectifier stages that condition incoming power and connect capacitors or batteries
to support sags and outages. Just a few years ago, “Typical losses were 10% to
15%, and worse at lighter loads,” says Ed Spears, product marketing manager,
critical power solutions, Eaton. “Now we are in the range of 92% to 98%, even
99% efficient. This from better semiconductor technology but also topology. We
can operate in modes where we can allow more straight utility power to come
through.”
From there, savings directly from reducing inefficiencies drop off rapidly. For
example, in motors, “A 3% voltage imbalance can lead to a 25% to 30% current
imbalance, and increase motor losses by 10% to 20%. It also raises motor
operating temperatures,” says Mike Melfi, manager, advanced variable-speed
motor technologies, Baldor (www.baldor.com). But the increase in loss might not
add up to much. “Altogether, a 95% efficient motor might be reduced to 94%,”
Melfi says.
Furthermore, some of the ways plants deal with harmonics add to energy
inefficiencies. “People used to throw in K-rated transformers all over the place
because harmonics were eating up their standard transformers, but they would lose
2% to 4% efficiency,” says Carnovale. “Newer versions are much more efficient,
and they handle the harmonics — they can absorb them like a capacitor set. You
can use them in pairs to cancel out harmonics.”
The upshot is, while cleaning up power might pay off in higher system efficiency,
that’s not where you’ll find 25% savings. “Companies want to install a black box
and save a lot of energy, but unless they have a power factor situation and the
utility is imposing a penalty, they’re not going to save 20% to 30%,” Carnovale
says. “If they replace an inefficient UPS, they might pick up 10%. For harmonics,
it’s going to be more like 2% to 4%.”
Page 1 of 4
The utility is paid by the kilowatt-hour (kWh) for real power, and charges a fee
based on the peak demand represented by the combination of real and reactive
power. “If a plant has a large reactive load because of poor power factor control,
along with the price of the power, you’re paying rent on an oversized ‘pipe’ to
deliver it,” Vesel says.
The demand fee might not be explicit. “Sometimes it’s obvious, sometimes not,”
Perry says. “If your bill includes terms like kVA or kVAR, they’re measuring your
power factor and they might be charging for it with a surcharge that shows up on
your bill.”
Power factor penalties take a variety of forms, calculated in different ways that are
detailed in the white paper “Power Quality Solutions and Energy Savings — What
Is Real?” at www.eaton.com/experience. Some utilities use multiple methods and
might apply more than one penalty.
Maybe you did, but those were simpler times. “Loads have changed
tremendously,” Boulos says. “VSDs, presses, welders and automation together
cause problems on the network. With cyclic loads, traditional correction with a
fixed capacitor, or even with a controller averaging every 30 seconds or every
minute, doesn’t always work.”
VSDs offer higher system efficiency but can aggravate plant power quality and
reduce the reliability and efficiency of fixed-speed and constant-torque motors on
the same power supply. “The net energy savings can be reduced by these effects,”
says John Malinowski, senior product manager, AC and DC motors, Baldor. “The
drive design can help or hurt, and this is true of any load. Hence IEEE Standard
519, which is driven by reliability considerations but applying it also affects energy
efficiency.”
Page 3 of 4
So one strategy is to be selective about the technologies you install. VSDs with
active rectifier units (ARUs) compensate for other inductive
loads on the same power supply or bus — for example, in a
group of motors on a bus where one or more run at full power
and speed, a motor with an ARU can compensate the
inductive loads of the full-power motors and correct the bus
power factor. “It’s best to consider only drives with active
front ends, where you can control reactive power and power
factor,” Malinowski says.
The interactions call for combining corrections for harmonics and power factor.
For example, an active harmonic filter (AHF) can be part of a power factor
correction system (Figure 4). Some potential benefits of a holistic approach
include:
The first step toward improving energy efficiency is to know where your energy is
going, and suppliers are supporting this measure by rapidly improving the
capabilities and reducing the costs of power monitoring systems.
Monitoring systems are being used to look at power quality, sequence of events,
trends in loads, temperatures and currents, and more. “We have a million boxes —
relays, meters, current transformers — to go into any power system,” says Vince
Tullo, general manager, sales, GE Digital Energy (www.gedigitalenergy.com).
“From inputs to motor control centers — substations, switchgear, protective relays
— you have, at every point, the ability to put on intelligence. You can have
control, metering and fault detection all in one box.
Page 3 of 4
Page 4 of 4
“But it’s not the boxes, it’s the ability to take that data, turn it into information and
give it to the right person in an actionable format,” Tullo continues. “The news
during the past few years is the ability to get information down to the process level
and be able to use it.”
Capturing triggered events like sags, swells, and interruptions (many energy
meters only captured time triggered data not threshold triggered data)
Evaluating real-time and snapshot data for key electrical and power quality
variables
Having sufficient frequency response and sampling rate to capture high-
speed transients such as events related to lighting or switching
Trending appropriate variables so a change or variation from normal is
obvious and can be flagged and used for analysis.
Trending harmonic currents and voltage distortion to evaluate issues related
to harmonics (overheating, nuisance operation or capacitor failures)
Time/date stamping events to within one millisecond to help determine the
correlation between cause/effect
“Electric power distribution units (EPDUs) can monitor and control, and be set to
alarm on overload or unbalance, to help maintain efficiency and prevent failures,”
says Perry. “By monitoring breakers and submetering components, you can catch
negative trends to save energy and downtime.”
Shave a peak
With harmonics under control and a plan to keep power factors close to unity,
you’re ready to work with your utility to reduce peak loads and shift non-critical
power consumption to off-peak times. Your power company might offer to help
pay for it.
Sags can be filled and peaks can be shaved with energy storage devices. Flywheel
systems are used on material handling cranes, connected to the DC section of a
VSD. “During lift, power usage peaks and the DC bus can sag, but during let-
down, there’s energy available for regeneration,” says Frank DeLattre, chief sales
officer, Vycon (www.vycon.com). “That energy can be stored and used during lifts
to reduce consumption.” The devices also provide power for a short time during
outages.
Energy storage also can be used to cover peak loads where capacity is limited, such
as at the end of a heavily loaded power transmission line or a location where the
substation has become marginal. “You can draw more than the utility can provide
during short peaks, and use the flywheel to prevent a voltage sag,” DeLattre says.
“Clients like Valero Oil, BASF and Publix are putting in load-shedding systems to
reduce peak loads and handle outages,” Tullo says.
When hurricanes take out the power lines, Publix food stores are shut down — no
lights, no registers, and soon, the food spoils. So they put in standby power
systems with generators. “Now, when a hurricane comes through, they stay in
business, but more importantly, they also manage their peak demand,” Tullo says.
“On hot summer days, they run the generators and sell excess capacity back to
Florida Power and Light.”
Typical paybacks are 12 months to 18 months for load-shedding and critical power
initiatives, Tullo says. “They’re spending money to save money.”
Utilities often have formal demand-side reduction programs where they invest as
much to reduce demand as they would have to spend to increase capacity. “Some
have called them ‘dollar-a-watt’ programs,” Vesel says. “Talk with your utility.
Get your plant audited by people who know how to do it right and can give you a
well-analyzed and well-engineered result, and go from there.”
Page 4 of 4
The Smith Chart, invented by Phillip H. Smith (1905-1987 is a graphical aid or nomogram
designed for electrical engineering specialising in radio frequency (RF) engineering to assist in
solving problems with transmission lines and impedance matching circuits.
Use of the Smith Chart utility has grown steadily over the years and it is still widely used today,
not only as a problem solving aid, but as a graphical demonstrator of how many RF parameters
behave at one or more frequencies, an alternative to using tabular information. The Smith Chart
can be used to represent many parameters including impedance, admittances, reflection
coefficients, scattering parameters, noise figure circles, constant gain contours and regions for
[[stability theory|unconditional stability
Contents
[hide]
1 Overview
2 Mathematical Basis
o 2.1 Actual and Normalised Impedance and Admittance
o 2.2 The Normalised Impedance Smith Chart
2.2.1 The Variation of Complex Reflection Coefficient with Position Along the
Line
2.2.2 The Variation of Normalised Impedance with Position Along the Line
2.2.3 Regions of the Z Smith Chart
2.2.4 Circles of Constant Normalised Resistance and Constant Normalised
Reactance
o 2.3 The Y Smith Chart
o 2.4 Practical Examples
o 2.5 Working with Both the Z Smith Chart and the Y Smith Charts
o 2.6 Choice of Smith Chart Type and Component Type
3 Using the Smith Chart to Solve Conjugate Matching Problems With Distributed Components
4 Using the Smith Chart to Analyse Lumped Element Circuits
5 References
6 External links
[edit] Overview
The Smith Chart is plotted on the complex number and reflection coefficient plane in two
dimension and is scaled in normalised impedance (the most common), normalised admittance or
both, using different colours to distuinguish between them. These are often known as the Z, Y
and YZ Smith Charts respectively
Normalised scaling allows the Smith Chart to be used for problems involving any characteristic
impedance or system impedance, although by far the most commonly used is 50 Ohms. With
relatively simple graphical construction it is straighforward to convert between normalised
impedance (or normalised admittance) and the corresponding complex voltage reflection
coefficient.
The Smith Chart has circumferential scaling in wavelengths and degrees. The wavelengths scale
is used in distributed component problems and represents the distance measured along the
transmission line connected between the signal generator or source and the load to the point
under consideration. The degrees scale represents the angle of the voltage reflection coefficient
at that point. The Smith Chart may also be used for lumped element model matching and
analysis problems.
Use of the Smith Chart and the interpretation of the results obtained using it requires a good
understanding of alternating current and transmission line theory, both of which are pre-
requisites for RF engineers.
As impedances and admittances change with frequency, problems using the Smith Chart can
only be solved manually using one frequency at a time, the result being represented by a
point(geometry). This is often adequate for narrow band applications (typically up to about 5%
to 10% bandwidth) but for wider bandwidths it is usually necessary to apply Smith Chart
techniques at more than one frequency across the operating frequency band. Provided the
frequencies are sufficiently close, the resulting Smith Chart points may be joined by straight
lines to create a locus.
A locus of points on a Smith Chart covering a range of frequencies can be used to visually
represent:
The accuracy of the Smith Chart is reduced for problems involving a large statistics spread of
impedances or admittances, although the scaling can be magnified for individual areas to
accommodate these.
and
where
where
is the distance measured along the transmission line from the generator in metres (m)
Also
where
and
[edit] The Variation of Complex Reflection Coefficient with Position Along the Line
The complex voltage reflection coefficient is defined as the ratio of the reflected wave to the
incident (or forward) wave. Therefore
where C is also a constant. For a uniform transmission line (in which is constant), the complex
reflection coefficient of a standing wave varies according to the position on the line. If the line is
lossy ( is finite) this is represented on the Smith Chart by a spiral path. In most Smith Chart
problems however, losses can be assumed negligible ( ) and the task of solving them is
greatly simplified. For the loss free case therefore, the expression for complex reflection
coefficient becomes
where is the wavelength within the transmission line at the test frequency. Therefore
This equation shows that, for a standing wave, the complex reflection coefficient and impedance
repeats every half wavelength along the transmission line. The complex reflection coefficient is
generally simply referred to as reflection coefficient. The outer circumferential scale of the Smith
Chart represents the distance from the generator to the load scaled in wavelengths and is
therefore scaled from zero to 0.50.
[edit] The Variation of Normalised Impedance with Position Along the Line
If and are the voltage across and the current entering the termination at the end of the
transmission line respectively, then
and
By dividing these equations and substituting for both the voltage reflection coefficient
and the normalised impedance of the termination represented by the lower case Z, subscript T
These are the equations which are used to construct the Z Smith Chart.
Both and are expressed in complex numbers without any units. They both change with
frequency so for any particular measurement, the frequency at which it was performed must be
stated together with the characteristic impedance.
may be expressed in magnitude and angle on a polar diagram. Any actual reflection coefficient
must have a magnitude of less than or equal to unity so, at the test frequency, this may be
expressed by a point inside a circle of unity radius. The Smith Chart is actually constructed on
such a polar diagram. The Smith chart scaling is designed in such a way that reflection
coefficient can be converted to normalised impedance or vice versa. Using the Smith Chart, the
normalised impedance may be obtained with appreciable accuracy by plotting the point
representing the reflection coefficient treating the Smith Chart as a polar diagram and then
reading its value directly using the characteristic Smith Chart scaling. This technique is a
graphical alternative to substituting the values in the equations.
By substituting the expression for how reflection coefficient changes along an unmatched loss
free transmission line
for the loss free case, into the equation for normalised impedance in terms of reflection
coefficient
yields the impedance version transmission line equation for the loss free case:<ref>Hayt,
William H Jr.; "Engineering Electromagnetics" Fourth Ed;McGraw-Hill International Book
Company; pp 428 433. IBSN 0-07-027395-2.</ref>
where is the impedance 'seen' at the input of a loss free transmission line of length l,
terminated with an impedance
Versions of the transmission line equation may be similarly derived for the admittance loss free
case and for the impedance and admittance lossy cases.
The Smith Chart graphical equivalent of using the transmission line equation is to normalise
, to plot the resulting point on a Z Smith Chart and to draw a circle through that point
centred at the Smith Chart centre. The path along the arc of the circle represents how the
impedance changes whilst moving along the transmission line. In this case the circumferential
(wavelength) scaling must be used, remembering that this is the wavelength within the
transmission line and may differ from the free space wavelength.
If the termination is perfectly matched, the reflection coefficient will be zero, represented
effectively by a circle of zero radius or in fact a point at the centre of the Smith Chart. If the
termination was a perfect open circuit or short circuit the magnitude of the reflection coefficient
would be unity, all power would be reflected and the point would lie at some point on the unity
circumference circle. Given that Smith's chart isn't accurate enough, Rafay's chart can be used to
find the inverse impedance.
The normalised impedance Smith Chart is composed of two families of circles: circles of
constant normalised resistance and circles of constant normalised reactance. In the complex
reflection coefficient plane the Smith Chart occupies a circle of unity radius centred at the origin.
In cartesian coordinates therefore the circle would pass through the points (1,0) and (-1,0) on the
x-axis and the points (0,1) and (0,-1) on the y-axis.
Since both and are complex numbers, in general they may be expressed by the following
generic rectangular complex numbers:
Substituting these into the equation relating normalised impedance and complex reflection
coefficient:
This is the equation which describes how the complex reflection coefficient changes with the
normalised impedance and may be used to construct both families of circles.<ref>Davidson, C.
W.;"Transmission Lines for Communications with CAD Programs";Macmillan; pp 80-85. ISBN
0-333-47398-1</ref>
The Y Smith chart is constructed in a similar way to the Z Smith Chart case but by expressing
values of voltage reflection coefficient in terms of normalised admittance instead of normalised
impedance. The normalised admittance yT is the reciprocal of the normalised impedance zT, so
Therefore:
and
The Y Smith Chart appears like the normalised impedance type but with the graphic scaling
rotated through , the numeric scaling remaining unchanged.
The region above the x-axis represents capacitive admittances and the region below the x-axis
represents inductive admittances. Capacitive admittances have positive imaginary parts and
inductive admittances have negative imaginary parts.
Again, if the termination is perfectly matched the reflection coefficient will be zero, represented
by a 'circle' of zero radius or in fact a point at the centre of the Smith Chart. If the termination
was a perfect open or short circuit the magnitude of the voltage reflection coefficient would be
unity, all power would be reflected and the point would lie at some point on the unity
circumference circle of the Smith Chart.
A point with a reflection coefficient magnitude 0.63 and angle , represented in polar form as
, is shown as point P1 on the Smith Chart. To plot this, one may use the
circumferential (reflection coefficient) angle scale to find the graduation and a ruler to
draw a line passing through this and the centre of the Smith Chart. The length of the line would
then be scaled to P1 assuming the Smith Chart radius to be unity. For example if the actual radius
measured from the paper was 100 mm, the length OP1 would be 63 mm.
The following table gives some similar examples of points which are plotted on the Z Smith
Chart. For each, the reflection coefficient is given in polar form together with the corresponding
normalised impedance in rectangular form. The conversion may be read directly from the Smith
Chart or by substitution into the equation.
P1 (Inductive)
P2 (Inductive)
P3 (Capacitive)
[edit] Working with Both the Z Smith Chart and the Y Smith Charts
In RF circuit and matching problems sometimes it is more convenient to work with admittances
(representing conductances and susceptances) and sometimes it is more convenient to work with
impedances (representing resistances and reactances). Solving a typical matching problem will
often require several changes between both types of Smith Chart, using normalised impedance
for series elements and normalised admittances for parallel elements. For these a dual
(normalised) impedance and admittance Smith Chart may be used. Alternatively, one type may
be used and the scaling converted to the other when required. In order to change from normalised
impedance to normalised admittance or vice versa, the point representing the value of reflection
coefficient under consideration is moved through exactly 180 degrees at the same radius. For
example the point P1 in the example representing a reflection coefficient of has a
normalised impedance of . To graphically change this to the equivalent
normalised admittance point, say Q1, a line is drawn with a ruler from P1 through the Smith
Chart centre to Q1, an equal radius in the opposite direction. This is equivalent to moving the
point through a circular path of exactly 180 degrees. Reading the value from the Smith Chart for
Q1, remembering that the scaling is now in normalised admittance, gives .
Performing the calculation
Once a transformation from impedance to admittance has been performed the scaling changes to
normalised admittance until such time that a later transformation back to normalised impedance
is performed.
The table below shows examples of normalised impedances and their equivalent normalised
admittances obtained by rotation of the point through . Again these may either be obtained
by calculation or using a Smith Chart as shown, converting between the normalised impedance
and normalised admittances planes.
Values of reflection coefficient as normalised impedances and the equivalent normalised admittances
P1 ( ) Q1 ( )
P10 ( ) Q10 ( )
Values of complex reflection coefficient plotted on the normalised impedance Smith Chart and their
equivalents on the normalised admittance Smith Chart
The choice of whether to use the Z Smith Chart or the Y Smith Chart for any particular
calculation depends on which is more convenient. Impedances in series and admittances in
parallel add whilst impedances in parallel and admittances in series are related by a reciprocal
equation. If is the equivalent impedance of series impedances and is the equivalent
impedance of parallel impedances, then
Expressions for Real and Normalised Impedance and Admittance with Characteristic Impedance Z 0 or
Characteristic Admittance Y0
Impedance (Z or z) or Reactance (X or x)
Element Type
Real ( ) Normalised (No Unit)
Resistance (R)
Inductance (L)
Capacitance (C)
Admittance (Y or y) or Susceptance (B or b)
Element Type
Real (S) Normalised (No Unit)
Resistance (R)
Inductance (L)
Capacitance (C)
For distributed components the effects on reflection coefficient and impedance of moving along
the transmission line must be allowed for using the outer circumferential scale of the Smith Chart
which is calibrated in wavelengths.
The following example shows how a transmission line, terminated with an arbitrary load, may be
matched at one frequency either with a series or parallel reactive component in each case
connected at precise positions.
From the table above, the reactance of the inductor forming part of the termination at 800 MHz is
This is plotted on the Z Smith Chart at point P20. The line OP20 is extended through to the
wavelength scale where it intersects at the point . As the transmission line is loss
free, a circle centred at the centre of the Smith Chart is drawn through the point P20 to represent
the path of the constant magnitude reflection coefficient due to the termination. At point P21 the
circle intersects with the unity circle of constant normalised resistance at
The extension of the line OP21 intersects the wavelength scale at , therefore the
distance from the termination to this point on the line is given by
Since the transmission line is air-spaced, the wavelength at 800 MHz in the line is the same as
that in free space and is given by
where is the velocity of electromagnetic radiation in free space and is the frequency in hertz.
The result gives , making the position of the matching component 29.6 mm from
the load.
As the Smith Chart is still in the normalised impedance plane, from the table above a series
capacitor is required where
Therefore
To match the termination at 800 MHz, a series capacitor of 2.6 pF must be placed in series with
the transmission line at a distance of 29.6 mm from the termination.
An alternative shunt match could be calculated after performing a Smith Chart transformation
from normalised impedance to normalised admittance. Point Q20 is the equivalent of P20 but
expressed as a normalised admittance. Reading from the Smith Chart scaling, remembering that
this is now a normalised admittance gives
(In fact this value is not actually used). However, the extension of the line OQ20 through to the
wavelength scale gives . The earliest point at which a shunt conjugate match
could be introduced,moving towards the generator, would be at Q21, the same position as the
previous P21, but this time representing a normalised admittance given by
From the table it can be seen that a negative admittance would require to be an inductor,
connected in parallel with the transmission line. If its value is , then
A suitable inductive shunt matching would therefore be a 6.5 nH inductor in parallel with the
line positioned at 123 mm from the load.
The analysis starts with a Z Smith Chart looking into R1 only with no other components present.
As is the same as the system impedance, this is represented by a point at the centre
of the Smith Chart. The first transformation is OP1 along the line of constant normalised
resistance in this case the addition of a normalised reactance of -j0.80, corresponding to a series
capacitor of 40 pF. Points with suffix P are in the Z plane and points with suffix Q are in the Y
plane. Therefore transformations P1 to Q1 and P3 to Q3 are from the Z Smith Chart to the Y Smith
Chart and transformation Q2 to P2 is from the Y Smith Chart to the Z Smith Chart. The following
table shows the steps taken to work through the remaining components and transformations,
returning eventually back to the centre of the Smith Chart and a perfect 50 Ohm match.
x or y
Transformation Plane Normalised Capacitance/Inductance Formula to Solve Result
Value
Capacitance (Series)
Inductance (Shunt)
Z Capacitance (Series)
Y Capacitance (Shunt)
Incomparable Features!
See how powerful the Mesta DPM is, click into the DPM Power Lab.
Observing the Analysis in Figure 1, the power of the Mesta DPM is immediately
obvious. The graphs (A, B, C) display data at three different points of the system:
(A) the targeted, purely sinusoidal utility current with unity power factor (B) the
necessary current harmonics in order for the Mesta DPM to achieve those results
and (C) the non-linear load with harmonics.
By investigation of the line current, the Mesta DPM instantaneously finds and
corrects any non-fundamental current that is requested by a non-linear load.
To further demonstrate the achieved end results, Figure 2 summarizes the above
data into a table.
Figure 2.
Many industrial electrical distribution systems are being used in ways not
foreseen by the designers. These changes in use can cause some problems in
energy consumption and in safety. If a motor is operating at a lower voltage than it
was designed for, it is probably using more amperage than was intended and is
causing unnecessary losses in transmission lines. If the wires are too small for the
load, line losses can be large, and fire hazards increase significantly. Other
problems that can create unnecessary energy loss are voltage imbalance in three-
phase motors and leaks from voltage sources to ground. Another problem that may
be costing money is a low power factor. The optimal use of a plants' electrical use
can reduce operating and production costs. The following module containing the
recommendations below illustrates this energy savings potential.
Notes:
Before choosing the following targeted recommendations READ
THE FOLLOWING:
Pay back estimates for the following recommendations will use the
equation below. They will vary depending on the, application, type of
installation, and purchase quantity of material and labor associated
with each recommendation. It will be up to the person doing the
analyses to use the URL references below each equation to help
estimate an implementation cost.
The data correlating to the variables below each equation will
be prompted for in order to execute a calculation. Frequently the
fuel cost (FC) associated with the specific recommendation will be
prompted for in order to calculate the annual cost savings (ACS).
Unless otherwise specific to a particular recommendation the ACS
will calculated as follows:
Data Conversions?
RPN Calculator?
Data Conversions?
RPN Calculator?
Install demand controller or load shedder to limit peak demand. There
will be no energy savings since demand is shifted, not reduced. The
following equation shows the savings that can be achieved.
DS = demand savings, KW
DC = demand charge, $/KW
MY = months per year savings will occur
Data Conversions?
RPN Calculator?
Data Conversions?
RPN Calculator?
Press the calculate button to execute an estimation
RC = rated capacity, KW
NL = fractional loss with no load*
OT = off time for transformers, hrs/yr
Data Conversions?
RPN Calculator?
Power Engineering Books
Thomas Register
NEMA
Data Conversions?
RPN Calculator?
Reduce rates and/or restructure rate schedules or make other changes in
electric service in order to obtain lowest possible rates. The following
equation illustrates the potential savings that can occur when rate schedule
changes are made to obtain the least possible rates.
Power Engineering Books
Thomas Register
Data Conversions?
RPN Calculator?
Data Conversions?
RPN Calculator?
Data Conversions?
RPN Calculator?
** Note: When ordering please specify whether you need a right or left hand unit; The picture
above denotes a left hand unit wiring on left side.
All units come prewired with 3' of wire and flex for your convenience.
***Important: to assure you order the correct size Power Factor Unit, check your main breaker
or
fuse size this will determine the size of your unit!
****LINK: TO VIEW WARRANTY'S AND SPECIFICATIONS
WE ACCEPT
The PFCD 3100 is a 100amp 208/ 480v, three phase/ 4wire unit.
This unit is fused and needs to be installed on a 3pole 30amp breaker closest to the main breaker.
Lowers electric bills up to 20%.
Reduces power consumption.
Eliminates power surges and spikes.
Enhances capacity of existing electrical system.
Protects appliances and sensitive electronic equipment.
Reduces harmful (EMFs) electro magnetic fields.
Improves power factor.
Reduces electricity required by inductive loads (motors).
increases the life of appliances and motors.
Certified Green Product, Reduces Carbon Footprint
The PFCD 3200 is a 200amp 208/ 480v, three phase/ 4wire unit.
This unit is fused and needs to be installed on a 3pole 30amp breaker closest to the main breaker.
Lowers electric bills up to 20%.
Reduces power consumption.
Eliminates power surges and spikes.
Enhances capacity of existing electrical system.
Protects appliances and sensitive electronic equipment.
Reduces harmful (EMFs) electro magnetic fields.
Improves power factor.
Reduces electricity required by inductive loads (motors).
increases the life of appliances and motors.
Certified Green Product, Reduces Carbon Footprint
March
1996
Volume 2 Issue 5
Correcting power factor in a production facility often reduces the electricity
bill by thousands of dollars a year. That was the message in the last issue of
$mart Energy User. This issue deals with actually doing it, with getting the
technical advice you need, selecting the best correction option for your plant, and
pricing out the job.
Let’s assume that the Energy and Minerals Section has done an electrical energy
audit of your facility. We came, took measurements, and found that your plant’s
peak electrical demand was accompanied by a low power factor. We then
calculated what the annual electricity bill savings would be if the power factor was
corrected. We may also have come up with a rough cost estimate, based on the
experience of others, and calculated an approximate payback figure. You liked the
preliminary numbers, and would now like to proceed. What’s the next step?
Because production facilities differ greatly from each other, there is no single
approach to power factor correction that is best in all situations. Someone must
analyze your situation and decide which approach is best for your plant.
Depending on plant complexity and other issues, that analysis might be done by
The following questions indicate what needs looking into, and might also help you
decide who should do the looking.
The electric utility is concerned with the plant’s power factor at the point of
metering, not whether the compensating capacitors are installed at the electrical
service entrance or at individual motors. Because installing one capacitor bank at
the service entrance is less expensive than installing individual capacitors at each
motor, this is the approach that is usually taken. There are exceptions, however.
Perhaps the facility has only one or two large motors. Or a large motor causes an
excessive drop on the circuit that feeds it. In these and some other situations,
compensation at the motor can be more cost effective.
The electric utility is also concerned that any power factor of less than 100% be
inductive, not capacitive. A capacitive (leading) power factor can occur if an
inductive (lagging) power factor has been overcompensated by putting too much
capacitance across the line. This can happen if, for instance, a fixed capacitor bank
is installed at the service entrance and then some large motor loads are
subsequently turned off. Compensating individual motor loads avoids this
problem. So does installing a power factor controller. A power factor controller
continuously monitors the service entrance power factor, and connects, at any
given time, only the amount of capacitance needed to accomplish the desired level
of correction. These controllers often come packaged together with a capacitor
bank in a steel cabinet. Here the engineering has been done by the manufacturer,
eliminating (in many cases) the need for on-site design by an engineer, and
eliminating that cost.
Power factor correction tends to increase voltage levels within the plant. Where
plant voltages are on the low side, this increase is welcome. But if the voltage is
already on the high side, it may not be. Someone should estimate the magnitude of
this increase, consider its possible effects, and contact the electric utility if it would
be unacceptably high.
· Where will the capacitor banks and the controller go?
Any changes or additions to a plant’s electrical system must meet electrical code
requirements. There are usually costs associated with this, and they should be
considered when deciding what approach to take. For instance, if installing a
capacitor bank and controller also means enlarging the electrical room, it might be
less expensive to eliminate the controller and mount capacitors near individual
motors.
Once the best approach has been pinned down, the next step is to decide what
specific hardware to purchase, and to get firm quotes. Unless your organization
happens to be blessed with a staff person experienced in specifying and installing
power factor correction systems, or you have engaged an electrical engineer to
analyze your situation and design your solution, you will probably want a
competent electrical contractor to price out the job for you — preferably a
contractor who works regularly with suppliers of capacitors and P.F. control
systems.