P521 En2141
P521 En2141
MiCOM P521
Fast Feeder
Differential Protection
protection.
• Variety of end-to-end
communications
interface options
• Integrated back-up
elements can run as hot
standby in the
event of comms
channel outage
AREVA T&D
APPLICATION > Transformer Applications
The MiCOM P521 current differential scheme provides Figure 1 shows a protected line and transformer "unit".
a comprehensive protection package, primarily The P521 compensates for the vector group shift and
designed for unit protection of overhead and zero sequence filtering effects of the in-zone
underground feeders up to and including distribution transformer. Second harmonic restraint is used to
voltage levels. stabilize the protection against magnetizing inrush
currents.
The P521 is limited to three pole tripping only and is
suitable for cable applications where no auto-reclosing Where transformer loads are tapped off the protected
is required. line, it is not essential to install CTs at the tap. There
exists the facility to time grade the differential
The MiCOM P521 is supplied with a full suite of protection with downstream relays or fuses.
protection and control functions as standard.
P521 P521
•
Protection Functions Overview P521
87P Phase segregated current differential protection
Intertripping (Direct, Permissive and Current differential) •
Propagation delay compensation •
3 Pole tripping only •
Fibre optic or metallic signalling channels •
Supervision of protection signalling channel •
Interchangeable protection signalling interface •
Vector Compensation (all vector groups) •
Ratio Correction •
Inrush restraint (menu selectable) •
50/51 Non-directional phase overcurrent protection •
50/51N Non-directional earth fault protection •
49 Thermal overload •
46 Negative sequence overcurrent protection •
46BC Broken conductor detection •
37 Undercurrent detection •
CBF Circuit breaker fail protection •
Circuit breaker control •
Circuit breaker monitoring •
TCS Trip circuit supervision •
Cold load pick-up protection for phase and E/F protection •
Blocking logic •
Selective logic •
5 optically isolated inputs •
8 output relays + watchdog output relay •
4 fixed function LEDs and 4 programmable LEDs •
2 setting groups •
Front EIA(RS)232 communication port (Modbus) •
Rear EIA(RS)485 communication port (choice of protocol) •
2>3
MAIN FUNCTIONS
I1 I2
> Differential Protection
I diff = I 1 + I 2
Operate
The measurement algorithm is extremely reliable,
offering fast detection of internal faults, and stability for
Percentage
external faults.
bias k2
FUNCTIONAL OVERVIEW
P521 P521
P521 P59x
PCM
Other protection and
telecommunications MUX
equipment
b) Multiplexed link - relay connected to a remote PCM multiplexer using optical fibres
and via P59x interface unit
MT RS485
1.2 km max. MT RS485
P521 P521
10 km max.
P595 P595
Interface Interface
P521 P521
d) EIA485 connection via P595 interface
(with optional PCM-FLU isolating transformers) - (Schemes F,G)
4>5
In direct fibre optic applications, the distance
achievable depends on the type of fibre interface
PROTECTION SIGNALLING
chosen, as detailed in the table below.
> Interfacing Options
Fibre Interface Option Typical fibre run
The MiCOM P521 relay is designed to ensure 850nm multi-mode (to P59x) 1 km
compatibility with a wide range of communication 1300nm multi-mode 50 km
equipment and media. It is supplied fitted with one of 1300nm single-mode 100 km
the following protection signalling interfaces (order
option): The P521 protection signalling interface is
interchangeable, which allows simple upgrade without
• 850nm multi-mode fibre the need for any software changes.
• 1300nm multi-mode fibre
• 1300nm single-mode fibre
> Direct Intertripping
• EIA(RS)232 electrical
• EIA(RS)485 electrical
A typical application of the user defined direct
intertripping facility is shown in Figure 4.
These interfaces allow a variety of signalling links to
be used, as shown in Figure 3 and summarised below.
Using the selective Intertrip settings, either a user-
Signalling bandwidths of 9.6 / 19.2 / 56 / 64 kbps are
configurable input or an internal status signal can be
available, subject to the type of link used.
assigned for this purpose. Upon receipt of this
message the remote relay will operate user specified
Where 4 wire unconditioned twisted-pair metallic pilots
outputs for direct transfer tripping or blocking, and
are available, distances up to 25km can be achieved
provide indication of the remote intertrip. The indication
using the P595 Interfacing Unit. For distances less
can be disabled then it acts as signal transfer function.
than 1.2km, direct 4 wire EIA(RS)485 connection can
be used.
> Permissive Intertripping
For 2 or 4 wire unconditioned twisted-pair metallic
pilots, options for other modems exist, allowing
There is an auxiliary signalling facility whereby
distances up to 18km to be achieved.
a permissive intertrip command is sent over the
protection communication channel.
For 2 wire conditioned pilots (provided by a
telecommunications company), a suitable type of
A user configurable input can be assigned for this
modem must be used, and there is no strict limit to
purpose. When energised, the communication
the distance.
message to the remote relay is modified. Upon receipt
of this message, and providing one or more currents
For connection to multiplexer equipment, electrical
are above the differential setting (Is1), the remote
interfaces conforming to the G.703, V.35, and X.21
relays will initiate a trip, operate the user defined
recommendations are available, by using the 850nm
outputs and provide an indication of the remote
fibre interface in the P521 plus a P591, P592 or P593
intertrip. If required the current checking can be
interface unit.
disabled thus enabling the permissive intertrip feature
to operate as a second direct intertrip function. The
indication can be disabled then it acts as signal transfer
function.
X X
Transformer
P521 P521 protection
DTT=1
Data message
- + - Opto +
CONTROL MEASUREMENTS &
POST FAULT ANALYSIS
The MiCOM P521 relay includes 5 logic inputs and 9 > Fault Records
logic outputs including a watch-dog. All inputs and
outputs are freely configurable, with the exception of Records of the last 5 faults are stored in Flash memory.
RLY1 which is a dedicated trip relay. The information provided in the fault record includes:
RLY1 and RLY2 outputs are changeover contacts,
typically used for tripping. • Indication of faulted phase
All programmed thresholds (time delayed or • Protection flags
instantaneous) can be easily routed to any of the • Active setting group
outputs.
• Local phase and neutral currents
• Differential currents
> Blocking Logic • Maximum bias current
• Communications channel status
When the MiCOM P521 relay is used on critical • Fault time and date
networks, management of protection relays must take
surrounding devices into consideration.
Blocking inputs can be configured independently from > Disturbance Recording (Oscillography)
each other to block any combination of the user
selected elements (e.g. current differential, thermal A total of 5 disturbance records can be stored each of
overload, overcurrent etc.). up to 3 seconds in duration. The disturbance recorder
function is triggered by any of the programmable
thresholds, by an external input, or via the remote
> Selective Relay Scheme Logic communications. The data is stored in memory and can
be transferred to a data analyser using the front
A dedicated input can temporarily alter the overcurrent communication port or the rear EIA(RS)485 port.
and earth fault time-delay settings in response to a
downstream phase/earth fault start condition. This
function allows the MiCOM relay to discriminate > Instantaneous Records
correctly when used in a cascade scheme.The
selective relay scheme logic function can be enabled Five instantaneous (start) records can be stored in the
or disabled by the user as required. MiCOM P521 relay. Each instantaneous record
includes:
P521 makes
current differential protection
available over pilot wires
6>7
MEASUREMENTS > Circuit Breaker Supervision and Monitoring
Local Fig. 5
User
Interface Connect to
Control System
Data logger
TM
Modbus
protocol
AREVA TRACK RECORD - HIGH SPEED
DIFFERENTIAL PROTECTION
>> LFCB digital current differential protection launched in 1986.
Class-leading protection applied at all voltage levels -
over 5000 units delivered.
>> P54x MiCOM series introduced in 1999.
Worldwide application, with over 13,200 units delivered.
>> PQ741 numerical current differential protection launched in 1996.
Over 3000 units delivered.
>> P521 MiCOM series introduced in 2003.
Worldwide application, with over 2,200 units delivered.
MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
AUTOMATION-L3-P521-BR-09.09-2141-EN - © - AREVA - 2009. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.
AREVA T&D Worldwide Contact Centre: Our policy is one of continuous development. Accordingly the
design of our products may change at any time. Whilst every
effort is made to produce up to date literature, this brochure
http://www.areva-td.com/contactcentre/
should only be regarded as a guide and is intended for
information purposes only. Its contents do not constitute an offer
Tel.: +44 (0) 1785 250 070
for sale or advise on the application of any product referred to in
it. We cannot be held responsible for any reliance on any
www.areva-td.com decisions taken on its contents without specific advice.
www.areva-td.com/protectionrelays