100% found this document useful (1 vote)
210 views

1KHW002609AE Programming and Testing of ETL600R4

dfffffffffffff

Uploaded by

fayssal salvador
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
210 views

1KHW002609AE Programming and Testing of ETL600R4

dfffffffffffff

Uploaded by

fayssal salvador
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 27

ABB Switzerland Ltd 1KHW002609-EN

Archive No.: Rev. Date:


Programming and Testing Instructions ETL600R4 - A 2013-03-15
Responsible Department: Prepared: Approved: Distribution: Lang.: Page:
PSND 2012-04-11 H. Benninger 2013-03-15 H.-J. Maag - EN 1/24+3
Valid for: Derived from: Replaces: Classification-No.: File:
- 1KHL015940-EN - - 1KHW002609AE Programming and Testing of ETL600R4

Powerline Carrier Equipment: Series ETL600

Programming and Testing Instructions ETL600R4

This document describes programming and testing of power line carrier equipment ETL600 Rel.4, including the
teleprotection system NSD600.

Contents
A Programming Instructions for the ETL600R4 Equipment 3
A.1 General 3
A.2 Create a configuration for the equipment using HMI600 3
A.3 Hardware 3
A.4 Settings for basic equipment ETL600 4
A.5 Settings for alarm unit R1BC, if present 4
A.6 Settings for NSD600 interface G4AI, if present 4
A.7 Check service keys 4
B Testing Instructions for the ETL600 Equipment. 7
B.1 General 7
B.2 Check power supply B5LD 7
B.3 Connect to the equipment, download configuration and prepare for tuning
& testing 7
B.4 Change configuration, if necessary 8
B.5 Transmitter 8
B.6 Receiver 9
B.7 Equalization of APLC channels 11
B.8 Testing of R1BC, if present 12
B.9 Configure Real Time Clock (RTC) 12
B.10 Testing of NSD600 with interface G4AI, if present 13
B.11 Testing of O4LE, if present 14
B.12 Testing of the V.11 ports 19
B.13 Testing of the V.24 ports 19
B.14 Testing of the LAN ports 19
B.15 Testing of O4CV, if present 20
B.16 Documentation 24
B.17 Manual reset 24
ETL600R4 Hardware Checks: ..................................................................... A1 - A3
ETL600R4 System Test Report: ........................ Refer to document 1KHW002568

The terminal designations in this document apply to terminals blocks for 10 wire pairs.

Test conditions:
• Temperature range: 10 °C to 40 °C.
• The connections for the tests can be made either at the test sockets on the front of the
equipment or at the terminals.

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to
third parties without express authority is strictly forbidden. © 2013 ABB
Revision: Language: Page:

A EN 2 1KHW002609-EN

Basic test equipment


PC with Windows XP, Vista or Windows 7
HMI600 software Newest version
Cable PC  P4LT/V/X 1:1 Sub-D 9 pole serial RS-232
Digital multimeter GMC METRAhit one, or equivalent
Level meter True RMS with a frequency range up to 1 MHz

Optional test equipment


Level generator PS-33A (Acterna) or equivalent
Selective level meter SPM-33A (Acterna) or equivalent
Storage oscilloscope Fluke 190C ScopeMeter or equivalent
Rx tuning adapter P4LM HENF 209665
Data tester PFA-35 (Acterna) or equivalent
Ethernet Tester CMA3000 (Anritsu) or equivalent

Notes:


• This document is part of instruction manual 1KHW002582.
• Please refer 1KHW001490 for compatibility between software HMI600, firmware and hardware
of ETL600.

Designations and abbreviations used:

Designation Meaning
___________ Measured value
[ ... ] Programmed value
[ ]D Preferred setting (default)
[X ] Test passed or jumper is set
[ ] Not tested or jumper is not set
P4LT Module type
BER Bit error ratio
Def. Default value
equ. Equipment
fLo Lower frequency, usually meant as low cut-off frequency
LED Light Emitting Diode
HMI600 User interface program for ETL600 running on a PC
N02 Position in rack: Slot number N02
Rx Receiver
Tx Transmitter
PC Personal computer
(T.02/..1) Connector 1 of terminal block connected to board at rack position N02
Revision: Language: Page:

A EN 3 1KHW002609-EN

A Programming Instructions for the ETL600R4 Equipment

A.1 General
All RF channel settings, all settings of telephony- and teleoperation-ports, most settings of the
integrated teleprotection system NSD600 are performed with the configuration program HMI600.
Typically these data are configured off-line and stored as a file on a disk. All these settings are
loaded from a file – the ETL600 configuration file *.et6 – and downloaded to the equipment. The
download of hardware settings such as jumpers or the presence or absence of modules without
access to the TDM bus is just for documentation and the correctness of this information must be
verified in the course of this instruction.
The most important settings are the RF Tx and Rx carrier. A few settings have to be adjusted with
the equipment e.g. the Tx RF level. Most of these tuning, testing and adjustment procedures are
supported by HMI600.
First the hardware settings of the analogue passive modules, such as the Tx- and Rx-Filters must
be done. For these hardware settings, refer to the applicable instructions. All steps and
measurements have to be documented in the protocol starting with page A1 of this document and
in the separate document 1KHW002568 System Test Report ETL600R4.
Follow conscientiously and step-by-step this instruction and the equipment will work properly!

A.2 Create a configuration for the equipment using HMI600


Create a configuration for your equipment with HMI600. This is described in the instruction manual
1KHW002582, section 5, ‘Configuration and set-up’.
If a preconfigured file exists, open this file. Make sure, that you have opened the right file by
displaying the configuration text on screen (View / Display configuration) and check the entries of
‘Equipment identification’.

A.3 Hardware

A.3.1 Racks
Check in the configuration file (View / Display hardware settings only) if the racks (P7LP, P7LQ,
P7LF, P7LH) correspond to the hardware. If entries are wrong, they can be corrected in the dialog
Configuration / Services / Type and Configuration / Services / RF-PEP [W] by selecting the
correct entries as shown in the following table:
Configuration /
Resulting
Configuration / Services / Type Services / Racks
equipment type
RF-PEP [W]
ETL600-050-1 12.5, 25, 50 ETL600-050-1 P7LH
12.5, 25, 50 ETL600-050-2 P7LP, P7LF
ETL600-050-2, ETL600-100-2
100 ETL600-100-2 P7LQ, P7LF

A.3.2 Modules
Make sure that all assemblies are mounted in the correct rack at the correct position as given by
the configuration file (View / Display hardware settings only) under the headings Modules in
rack P7LH, Modules in rack P7LP, Modules in rack P7LQ, Modules in rack P7LF.
The type of the DSP module is given by the following table:
Configuration / Services / Data Communication /
Allowed DSP module types
Data ports
1 V.11 / 2 V.24 P4LT, P4LV, P4LX
1 V.11 / 2 V.24 / Transit / 4 LAN P4LV, P4LX
1 V.11 / 4 V.24 / Transit / 4 LAN P4LX
If entries regarding the receive filter P4RX, alarm relay module R1BC and/or the number of power
supply modules B5LD are wrong, they can be corrected in the the dialog Configuration / System /
Equipment settings, frames Modules in rack P7LH, Modules in rack P7LP, Modules in rack
P7LQ or Modules in rack P7LF.
Revision: Language: Page:

A EN 4 1KHW002609-EN

The numbers of O4LE, O4CV and G4AI boards depend on the entries made in the dialog box
Configuration / Services.

A.3.3 SFP transceiver


If the LAN 4 port is configured, check if the SFP transceiver is fitted on the P4LV/X module.

A.3.4 Spare plates


The front of the racks should be completely covered. Check if all spare plates are present.

A.4 Settings for basic equipment ETL600

A.4.1 Power amplifier P1LP


Set the jumpers on the power amplifier(s) P1LP as specified by the configuration file (View /
Display hardware settings only).

A.4.2 Settings for the RF hybrid on module E5TH


Set the jumpers for the RF hybrid on module E5TH as given in the configuration view (View /
Display hardware settings only).
Also put the jumpers for standard tuning of the RF hybrid on E5TH.

A.5 Settings for alarm unit R1BC, if present


Set the jumpers on R1BC as given in the configuration file (View / Display configuration) under
the heading R1BC settings.

A.6 Settings for NSD600 interface G4AI, if present


Set the jumpers for each G4AI module as listed in the configuration file (View / Display hardware
settings only). For access to the jumper plugs, remove the cover of G4AI at the component side.

A.6.1 Tripping of the inputs


Set the jumpers for each G4AI module as listed under “Tripping of the inputs” in the configuration
file (View / Display hardware settings only).

A.6.2 Nominal input voltage


Set the jumpers for each G4AI module as listed under “Nominal input voltage” in the configuration
file (View / Display hardware settings only).

A.6.3 Relay contacts


Set the jumpers for each G4AI module as listed under “Relay contacts” in the configuration file
(View / Display hardware settings only).

A.6.4 Concluding work


Mount the cover of the G4AI modules at component side.

A.7 Check service keys


Depending on the desired services, an appropriate data key has to be installed on P4LT / P4LV /
P4LX and appropriate voice keys on the O4CV boards. Physically, the keys are circular button-like
devices called “iButtons” and have to be inserted into their sockets (also called “retainers”) on P4LT
/ P4LV / P4LX and O4CV.

A.7.1 P4LT / P4LV / P4LX data keys


Six different types of keys exist, identified by colored labels. Refer to the ETL600 instruction
manual 1KHW002582 at the end of chapter 11 for more information. The number of required
Revision: Language: Page:

A EN 5 1KHW002609-EN

MOD600 and NSK600 modems decides about the color of the needed data key, which is displayed
in the configuration file (View / Display hardware settings only./ Equipment identification /
Needed data key on P4L<T/U/V/X>. Data keys with colors offering more modems than required
will work as well. This is shown in the following table:
Needed data key on Keys which will work as well as the needed
P4LT / P4LV / P4LX key
Blue Green Yellow Orange Red
White     
Blue    
Green   
Yellow  
Orange 
Red

Check if the data key mounted on the P4LT / P4LV / P4LX board is valid according to the table
above.
Please ask your local representative about the update procedure if the data key is not sufficient or
if no data key is installed on P4LT / P4LV / P4LX.
When the new data keys are available, proceed as described in the procedure “Replace data key”
below.

A.7.2 O4CV voice keys


Two different types of keys exist, identified by the numbers 2 or 4 corresponding to the maximum
number of compressed telephony channels that can be used on each O4CV board. Refer to the
ETL600 instruction manual 1KHW002582 at the end of chapter 11 for more information. The
needed voice key for each O4CV board is displayed in the configuration file (View / Display
configuration / Equipment identification / Needed voice key on O4CV) under the headings
O4CV CONFIGURATION at slot N... The 4 channel voice key works also if the needed voice key
is a 2 channel key. If several O4CV modules are used in an ETL600 terminal, at most one of them
can have a 2 channel key. The remaining ones must be equipped with 4 channel keys.
Check if the voice keys mounted on the O4CV boards are valid as given by the HMI600
configuration view.
Please ask your local representative about the update procedure if the voice key is not sufficient or
if no voice key is installed on one or more of the O4CV boards.
When the required voice keys are available, proceed as described in the procedure “Replace voice
key” below.

Replace data or voice key (if required)


The service personnel must follow the precautions for ESD protection while handling the modules.

ESD protection

Caution The modules in this equipment contain devices, which can be damaged by
ESD electrostatic discharges. Appropriate measures must be taken before
unpacking modules or withdrawing them from equipment racks. Essential
precautions to prevent ESD damage when handling or working on modules
are grounding straps for technical personnel and the provision of anti-static
workbenches. Modules may only be shipped either in their original packing
or installed in equipment racks.
Revision: Language: Page:

A EN 6 1KHW002609-EN

Insertion and removal of plug-in modules

Caution Neither removing nor inserting of modules is permitted during power-up of


the equipment. Preceding to plug in and out of modules, the power supply
of the equipment has to be switched OFF.
There are two exceptions to this:
1. Rx filter P4RX:
It has to be removed and inserted while the equipment remains
powered when performing the Rx level adjustment procedure.
2. Redundant power supply module B5LD:
It can be removed or inserted while the equipment remains powered by
the other B5LD module in the rack.

1. Switch off the equipment.


2. Loosen the four mounting screws and pull out the P4LT/P4LV/P4LX
or O4CV module. In case of the O4CV module, remove the cover
plates by bending them slightly so that they can be drawn out of the
notches in the mounting bolts.
3. Removal of the installed data or voice key, if any:
Limit deflection of socket latches to just free the iButton edge from
retained state. Avoid applying excess force to latches. The socket is
shown in Figure 1.
4. Insertion of the new data or voice key:
Apply appropriate back pressure at the opposite side of the
P4LT/P4LV/P4LX or O4CV board before the data or voice key is
inserted into the socket.
Closely align the axis of the iButton and the socket. The socket then
latches the flange of the iButton. The socket is shown in Figure 1.
5. In case of the O4CV module, reinstall the cover plates. Insert the
P4LT/P4LV/P4LX or O4CV module back into the rack and tighten
the four mounting screws. Figure 1
6. Switch on the equipment.
Revision: Language: Page:

A EN 7 1KHW002609-EN

B Testing Instructions for the ETL600 Equipment.

B.1 General
Most of the testing for the ETL600 system can be done with assistance of HMI600. For some
adjustments like Tx RF level, Rx RF level etc. the permissible limits are calculated by the HMI600
and displayed in the dialog boxes.
The pilot signal is QPSK modulated to accommodate both Signaling and Embedded Operations
Channel. As a result, the level of the pilot signal changes continuously so that its exact level cannot
be measured.
The Tx filter on E5TH and the Rx filter P4RX (if used) have to be tuned before testing.
An attenuator with 75 Ohm impedance and a minimum attenuation of 15 dB is inserted between
two terminals to simulate a power line. For testing, the attenuation between the two terminals is
chosen as follows:

Max. Equipment type Attenu- Switches of standard ‘80 Watt-


output ation attenuator’ (minimum = 15 dB)
power +3 dB +6 dB +10 dB +20 dB
(PEP)
50 W ETL600-050, 1 channel, no MOD600 31 dB x x
100 W ETL600-100, 1 channel, no MOD600 34 dB x x x
50 W ETL600-050, 2 channels, no MOD600 25 dB x
100 W ETL600-100, 2 channel, no MOD600 28 dB x x
50 W ETL600-050, 3 channels, no MOD600 21 dB x
100 W ETL600-100, 3 channels, no MOD600 24 dB x x
50 W ETL600-050, with MOD600 18 dB x
100 W ETL600-100, with MOD600 21 dB x

B.1.1 Visual checks before switching ON the equipment.

Check the wiring of protective earth to the equipment. Check, if a


DANGER protective earth wire of at least 25 mm2 has been connected visibly to
the earth bolt of the cubicle.

In case of battery supply: Check if the positive pole (+) of the battery is grounded. If it is, place an
earth jumper to the positive pole of the cubicle supply.

 Note: Now switch on the equipment.

B.2 Check power supply B5LD


Check the DC supply voltage and verify that the green LED on the front panel of the right and – if
any – of the left power supply module B5LD is/are lit.
There is no access to the internal DC voltages generated by B5LD. However, hardware alarms will
be generated if these voltages go outside their limits.

B.3 Connect to the equipment, download configuration and prepare for tuning &
testing
1. Start the HMI600 program, open the preconfigured file and connect to the equipment as
described in the instruction manual, 1KHW002582, chapter 4, section ‘Communication to
the ETL600’.
Revision: Language: Page:

A EN 8 1KHW002609-EN

2. From the Equipment menu, click Download configuration. The keys are checked and
error messages appear if any of them is not sufficient. Compatibility checks are
performed to verify that the firmware versions in the equipment belong to the same
release as the HMI600. If not, an error message pops up. Depending on the message, an
earlier version of HMI600 must be used and/or the firmware of some modules must be
upgraded. The latter is described in the document 1KHW002589 Firmware Download for
ETL600.
3. If the download operation is possible, a message box appears informing that the link will
be cut off for a few seconds.
Click Yes
4. The Test configuration time dialog box has been opened.
Click OK.
5. HMI600 now compares the equipment identification from the file with the identification in
the equipment. If it is different, a warning message box appears.
Click OK. This starts the download configuration process.
6. A dialog box informs you, that the configuration has not been stored in the nonvolatile
flash EPROM and asks you if you want to do so.
Click Yes.
The configuration data are now stored in the flash EPROMs. This process needs some
seconds. Please wait until the color of the stop button in the toolbar changes from red to
grey. The actual status of the process is displayed in the status bar.
7. From the equipment menu, click Tuning & testing. This opens a dialog box, which
informs you that activating tests in the following dialog boxes may cause malfunctions of
the PLC-link.
8. Click OK and the Tuning & testing dialog box appears.

B.4 Change configuration, if necessary


In case configuration parameters have to be changed, refer to section 5 of the instruction manual,
chapter 'Configuration and Setup'.

B.5 Transmitter
The frequency in the APLC bands when converted in to the RF band will have an additional offset
of -150 Hz. This has been done to simplify the filtering by DSP. The frequency shift when
reconverted to the AF band will be restored.

B.5.1 Programming of Tx RF filter


The transmit filter on the module E5TH is programmed and tuned according to 1KHW002585. The
center frequency, bandwidth and associated jumper positions are supplied by HMI600.
In case of ETL600-100, the module E5TC is present, holding a second transmit filter. It must also
be tuned according to 1KHW002585.

B.5.2 Settings for RF hybrid on E5TH


The jumper settings depending on the presence or absence of the Rx filter are shown in the view
View / Display hardware settings only under the heading E5TH in rack P7LH at slot N54 or
E5TH in rack P7LQ at slot N54.

B.5.3 Tune Tx RF filter


The Tx filter(s) is/are tuned according to the ETL600R4 Tx filter tuning instructions 1KHW002585.

B.5.4 Adjust Tx RF level


The Tx RF level is adjusted with help of the HMI600 program. Two adjustment modes are available
in the Adjust Tx RF level dialog box under Equipment / Tuning & testing: default and manual.
The default mode allows fast and easy Tx RF level adjustment based on the filter settings used in
the equipment. The obtained setting accuracy is better than ± 0.2dB.
Revision: Language: Page:

A EN 9 1KHW002609-EN

If the Tx RF level needs to be verified by external measurement equipment, the manual adjustment
mode can be used.
Default adjustment procedure:
1. Choose the Default adjustment mode at the top of the dialog box.
2. Click the button Download in order to download the default adjustment value for the
current filter settings.
3. Click the button Save & Close to store the downloaded adjustment value on the equipment
and quit the dialog.
Manual adjustment procedure:
1. Choose the Manual adjustment mode at the top of the dialog box.
2. Remove the remote equipment by disconnecting the coaxial cable from the RF LINE
socket at the E5TH front panel.
3. Connect a 75 Ohm termination resistor or attenuator dimensioned for ≥ 50 W (ETL600-
050) or ≥ 100 W (ETL600-100) to the RF LINE socket.
4. Click Download.
5. Measure the level at the RF LINE MONITOR socket on the E5TH front panel with a level
meter having 75 or 50 Ohm input impedance.

 Note: The tolerance of the level at the test socket RF LINE MONITOR is ± 0.2 dB. Thus, if
the level meter has a tolerance of ± X dB, the resulting tolerance for the adjusted
Tx level is ± (X + 0.2) dB.
Alternatively, measure the test tone level at the RF LINE socket via an attenuator
required in order not to overdrive the input of the level meter. In this case, the tolerance of
the attenuator must also be taken into account.
6. Adjust the value in the Tx RF level [dB] field, download it by clicking Download and
measure the test tone level again. Continue until the measurement corresponds to the
permissible value displayed in the dialog box.

B.5.5 Adjust Tx alarm level


The Tx alarm level threshold is adjusted with the help of HMI600, the LED(s) TX-LVL-AL and the
potentiometer(s) TX-LVL-AL ADJUST (R1805) in the rear of the backplane of the power
amplifier(s) P1LP. In case of ETL600-100, there are two such potentiometers, one on each P1LP
backplane, which both have to be tuned.
1. In the Tuning & testing dialog box, click Adjust Tx alarm level.
2. Click Activate Tx alarm level.
3. Turn the potentiometer(s) TX-LVL-AL ADJUST in the rear of the backplane(s) P1LP of
the rack P7LH, P7LP or P7LQ clockwise until the associated TX-LVL-AL LED(s) to the
right of the potentiometer(s) go(es) on.
4. Check that the Tx ALARM LED(s) on E5TH – and in case of ETL600-100 also on E5TC –
light(s). After the programmed delay time, the Hardware alarm on the front plate of
P4LT/P4LV/P4LX appears. The relay contacts on the cable V9OT Pin 2-3 are closed.
5. Turn the potentiometer(s) TX-LVL-AL ADJUST slowly anticlockwise until the TX-LVL-AL
LED(s) go(es) off.
6. Click OK. The Alarm LED(s) go(es) off and the contacts open after the programmed
delay.
Note: Exact measurement of the programmed delay times is not essential.

B.6 Receiver

B.6.1 Programming of Rx RF filter


The receive filter type P4RX is programmed, tuned and checked according to 1KHW002584. The
center frequency, bandwidth and associated jumper positions are supplied by HMI600.
Revision: Language: Page:

A EN 10 1KHW002609-EN

B.6.2 Tune Rx RF filter


The tuning is done with help of the Rx filter tuning adapter P4LM in accordance with the document
1KHW002584 ‘Tuning of ETL600R4 Rx RF Filter P4RX’.

B.6.3 Adjust Rx RF level


The Rx RF level is adjusted using HMI600 program.
1. In the Tuning & testing dialog box click Adjust Rx RF level.
2. Follow the instructions given in the dialog box.

 Note: The number of adjustment steps depends on the presence of the Rx filter P4RX
(configured with Configuration / System / Equipment settings / Assemblies in
rack P7LC).

3. After all adjustment steps have been executed, click Close to close the dialog box.

B.6.4 Tune RF hybrid on E5TH


The goal of hybrid tuning is to increase the trans-hybrid loss, thereby reducing the amount of signal
from the local transmitter entering the local receiver. Tuning is done while the equipment is
energized and connected to the (artificial) line by setting the appropriate line balancing network
jumpers for the hybrid on the E5TH board. These jumpers can be accessed by plugging the E5TH
unit on the extender board P4EX.
Tuning is not required in the test field. If for some reasons – e.g. to get a customer approval – the
tuning is done in the test field, it has to be repeated during commissioning later on site when the
equipment is connected to the line.
If the hybrid is not tuned, the following default settings for the line balancing network must be used:
Jumpers R2, L17 and C3 inserted and the potentiometer R1101 set to mid position (indicated by
50).
Procedure for tuning the hybrid:
1. Insert the PCB extender type P4EX in place of the E5TH module into the rack and plug
E5TH on top of it.
2. Connect the artificial line to the RF LINE socket of the equipment.
3. Remove all line balancing jumpers R0 … R4, L0 … L17 and C0 … C17 on E5TH and set
the potentiometer R1101 to mid position (indicated by 50).
4. In the Equipment menu of HMI600, click Tuning & testing. This opens the Tuning &
testing dialog box.
5. Click Tune RF hybrid. This opens the Tune RF hybrid dialog box.
6. Click Start measurement and wait until the measured Rx RF level appears in the dialog
box.

 Note: It is possible that the operator phone of remote equipment is ringing during the
measurement. This has no effect on the measurement.

HMI600 selectively measures the level of the RF signal from the own transmitter.
In the following, this level is set to a minimum with the aid of the balancing network:
- resistance with one of the jumpers R0 … R4 and the potentiometer R1101,
- inductance with one of the jumpers L0 … L17,
- capacitance with one or several of the jumpers C1 to C17.
7. Reduce the measured Rx RF level by moving the R-jumper between R4, R3, R2, R1 and
R0. When the best jumper position has been found, turn potentiometer R1101 until a first
minimum is reached.
8. Search for a lower minimum by moving the L-jumper sequentially from L17 (largest
inductance) to L1 (smallest inductance). L17 produces the smallest inductive current and
L1 the largest. If jumper L17 does not produce any reduction, set jumper L0 which means
no inductive current.
When the best jumper position for the inductance has been found, turn potentiometer
R1101 until a minimum is reached.
Revision: Language: Page:

A EN 11 1KHW002609-EN

 9.
Note: Only one L jumper (L0 to L17) may be inserted at any time

Search for a lower minimum by moving the C-jumper sequentially from C1 (smallest
capacitance) to C17 (largest capacitance). More than one jumper may be inserted in
parallel to increase the capacitance.
When the best jumper position for the capacitance has been found, turn potentiometer
R1101 until a minimum is reached.
Click Stop measurement and Cancel to close the dialog box.
10. Remove the extender board P4EX and reinsert the E5TH module into the rack.

 Note: If the coaxial cable (connection to the line) is removed or reconnected


during the test, a rattling sound of a few seconds duration caused by the
loop back relay on E5TH may occur. This happens only when E5TH is
plugged on top of P4EX and has no influence on the performance.

 Note: The transhybrid loss that has been achieved by tuning the hybrid is
equal to the increase of the measured RF level when the RF cable is
unplugged. If it is higher than 20 dB, the tuning can be considered as
successful and may be terminated.

B.6.5 Link alarm indication


Trigger the link alarm by interrupting the RF connection (disconnecting the RF line coaxial cable).
After the programmed delay time the link alarm relay on P4LT/V/X operates. The relay contacts,
terminals 5 and 6 at the cable V9OT, are closed. Now restore the RF connection. The Alarm LED’s
go OFF and the contacts will open after the programmed delay.

B.7 Equalization of APLC channels


Refer to 1KHL001494 ‘APLC Channel Equalization for ETL600’. The document is put into a short
instruction in sections B.7.1 and B.7.2.

B.7.1 Measure frequency response


It is assumed, that
- the RF tuning of the remote equipment is already finished. If it isn’t finished, tune the remote
equipment.
- the link works and all alarms are cleared.
Measure the frequency response as described in 1KHW001494 ‘APLC Channel equalization for
ETL600’:
1. Select Equipment / Commissioning and maintenance / Frequency response /
APLC channel 1, APLC channel 2 or APLC channel 3, respectively.
2. In the following message box click OK and wait until measurement is done. The dialog
box Select equalizer appears.

B.7.2 Select Equalizer


For each APLC channel, an equalizer can be selected under Equipment / Commissioning and
maintenance / Select Equalizer / APLC channel 1, APLC channel 2 or APLC channel 3,
respectively.
Channel equalization is required for all DAPSK channels and recommended also for the FSK
channels.
1. Select the new equalizer:
In the field New equalizer, activate checkbox Amplitude response equalisation only.
2. External teleprotection equipment connected to ETL600 suffer from the additional delay
introduced by the equalizer. To reduce this delay, select type None or Short in the frame
Revision: Language: Page:

A EN 12 1KHW002609-EN

New equalizer of the dialog box Select equalizer.


If delay is uncritical, select type Middle or Long in the frame New equalizer of the dialog
box Select equalizer.
3. View the amplitude response by clicking View. If the amplitude response is acceptable,
go back to the Select equalizer dialog and select the viewed settings again. Download
the new equalizer settings by clicking Download. The equipment is reset now.
4. Wait until the equipment has restarted. The new equalizer is active now.
5. Exit.

B.8 Testing of R1BC, if present


For testing the R1BC, refer the client specific setting instructions. Depending upon the programmed
criteria, activate the required alarms using the following table. Check the contact closure of the
programmed relays on R1BC. Restore the link after this test is completed.

Alarm on R1BC Action to enforce the alarm


Warning LED on P4LT/V/X Activate a testtone in the ‘Adjust Tx RF level’ dialog box
Link alarm Disconnect the RF line coaxial cable
Hardware (HW) alarm Unplug the RF hybrid.
Interface alarm, In case an external real time clock is configured and
P4LT/V/X alarm connected: Disconnect the clock input to P4LT/V/X.
In case no external real time clock is configured: Configure
it (dialog box ‘Configuration / System / Channel settings /
Event recorder: Ext. real time clock sync available’).
System alarm (i.e. cabinet alarm) Enforce either Link alarm or HW alarm

B.9 Configure Real Time Clock (RTC)


The real time clock has to be set to the actual date and time for proper operation of the event
recorder.

B.9.1 Setting real time clock


Setting the date and time using HMI600:
1. On the Equipment menu, click Commissioning and maintenance, click Event recorder
and click Set Clock.
2. In the Real Time Clock (RTC) dialog box, check if PC time and PC date are correct.
3. Click Download date/time to RTC
This sets the RTC to the given date and time.
4. Click Upload date/time from RTC
The date and time displayed at Read RTC date & time part of the Real Time Clock (RTC)
box should be correct.
5. Click Cancel

B.9.2 Testing external real time clock synchronization (if available)


The external clock source with IRIG-B format has to be connected to the IRIG-B port at the front
panel of P4LT/V/X via external cable V9OV.
Testing the external synchronization using HMI600:
1. Set the time on the PC a few hours back/forward
2. On the Equipment menu point to Commissioning and maintenance menu point to
Event recorder and click Set Clock.
3. Click Download date/time to RTC. This sets the RTC to the wrong time.
4. Click Upload date/time from RTC. The date and time displayed at Read RTC date &
time part of the Real time Clock (RTC) box should be correct and not correspond to the
PC-date/time setting.
5. Click Cancel.
Revision: Language: Page:

A EN 13 1KHW002609-EN

6. Set the time on the PC back to the correct time

B.10 Testing of NSD600 with interface G4AI, if present

B.10.1 Inputs

How to activate an input command depends on the jumper settings on G4AI.


• G4AI input programmed as ‘contact and battery voltage’:
Inject a signal at input port with the voltage level U1 according to the jumper settings on
G4AI (24 VDC, 48 VDC, 110 VDC, 220 VDC)
• G4AI input programmed as ‘contact only’:
Short circuit the input port
The way to activate the input port is the same for a Tx command input and a start input.
Activate the input port and check, if the IN LED lights.

B.10.2 Outputs
Depending upon the programmed criteria, activate the required action using the following table.
Check the contact closure of the programmed outputs on G4AI.
Set the link back to an alarm free operation after this test.

Output on G4AI Action to enforce the output


Rx command Inject a Tx command at the corresponding input at the remote
station
Unblocking Disconnect the RF line coaxial cable
Rx guard Disconnect the RF line coaxial cable
Ack Tx command Inject a Tx command at the corresponding input
TPE link alarm Disconnect the RF line coaxial cable
TPE alarm Disconnect the RF line coaxial cable
TPE hardware alarm Inject a Tx command of length > Max. Tx Trip Duration
G4AI alarm Inject a Tx command of length > Max. Tx Trip Duration
User alarm 1 Depends upon programmed alarm criteria
User alarm 2 Depends upon programmed alarm criteria

B.10.3 NSD600 loop test


The NSD600 is tested by issuing a loop test via HMI600.
In the Commissioning & maintenance … dialog box click NSD600 send loop test / TPE1 and –
if TPE2 is configured – NSD600 send loop test / TPE2.
If the loop test is successful, a dialog box indicating the loop test time (TLink) appears.
Click OK to close the dialog box.

B.10.4 Command transmission time


Check the transmission time of the NSD600 commands over the link, e.g. by means of an
oscilloscope.

How to activate an input command depends on the jumper settings on G4AI.


• G4AI input programmed as ‘contact and battery voltage’:
Inject a signal at input port with the voltage level U1 according to the jumper settings on
G4AI (24 VDC, 48 VDC, 110 VDC, 220VDC)
• G4AI input programmed as ‘contact only’:
Short circuit the input port
Revision: Language: Page:

A EN 14 1KHW002609-EN

Transmit at few commands with a command / pause duration of about 100 ms / 1000 ms and
measure the actual transmission time for the command from the local station to the remote station.

 Note: The nominal transmission time as given in the technical data shall serve as a
guideline for the mean value of several commands.

B.10.5 Reset counters


After NSD600 testing reset the counters by using HMI600.
From the Equipment menu point to Commissioning and maintenance menu point to Event
recorder and click Reset counter.
In the Reset Counter box click check box Reset all counters
Click OK

B.11 Testing of O4LE, if present

B.11.1 Service phone


Only a functional test must be done. The buzzer, the ringing of the connected service phone, and
the audibility between the two service phones will be tested.

B.11.2 Hot line direct phone


The following tests must be done if the operation mode ‘Hot line direct phone’ is configured.
1. A functional test must be done to check the ringer. Connect on both sides of link a phone,
make a call from one side to remote and vice versa.
2. Check the Output level of speech:
Use coupling bridges similar to that, shown in Figure 2. The resistor R should be chosen
to 500 Ohm, included the resistance of the two coils. If the coupling bridge has polarity,
check first polarity of the subscriber interface at the cable terminals.
3. Feed a 800 Hz tone, with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in ±1 dB
range of the configured output level from the local equipment.
Connector X2

Termninal,
telephony

EUT:
O4LE
remote 7.5 H/240 Ω R
14 µF
Audio Analyzer
A32 0a 7.5 H/240 Ω
C32 0b Generator Analyzer
14 µF
Connector X2

EUT:
telephony
Terminal,

O4LE
local 7.5 H/240 Ω R
14 µF

A32 0a 7.5 H/240 Ω


C32 0b

14 µF

Figure 2

B.11.3 ‘Remote subscriber’, remote is Pax 2-wire


The following tests must be done if the operation mode ‘Remote subscriber’ is configured at the
local equipment and the operation mode ‘Pax 2-wire’ is selected at the remote equipment.
1. A functional test must be done to check the ringer. Connect a phone, at local equipment
and feed into remote PAX2W connection a ringing tone with 25 Hz and about 25 VAC.
Connect a 2.2 kOhm resistor between PAX2W input and generator! The generator
needn’t be programmed with a special ringing sequence. Now the phone should ring in a
typical sequence.
Revision: Language: Page:

A EN 15 1KHW002609-EN

2. Check the Output level of subscriber:


Use coupling bridges similar to that, shown in Figure 3. The resistor R should be chosen
to 500 Ohm, included the resistance of the two coils. If the coupling bridge has polarity.
Check first polarity at external cable of appropriate O4LE, terminal telephony, 0a-0b and
observe polarity of external voltage source.
3. Feed a 800 Hz tone, with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in 1 dB range
of the configured output level from the local equipment.

B.11.4 ‘Remote subscriber’, remote is Pax 4-wire


The following tests must be done if the operation mode ‘Remote subscriber’ is configured at the
local equipment and the operation mode ‘Pax 4-wire’ is selected at the remote equipment.
1. A functional test must be done to check the ringer. Connect a phone, at local equipment
and activate M-WIRE at the remote equipment. If M-WIRE is configured as ‘inverted’,
contacts at terminal, telephony, 4a-4b must be opened, otherwise closed. The phone
should ring in a typical sequence.
2. Check the Output level of subscriber:
Instead of phone use a coupling bridge similar to that, shown in Figure 3. The resistor R
should be chosen to 500 Ohm, included the resistance of the two coils. If the coupling
bridge has polarity. Check first polarity at terminal, telephony, 0a-0b. At remote side
generator can be direct connected to AF1-IN, at terminal, telephony, 1a-1b. M-WIRE
should be activated.
3. Feed a 800 Hz tone, with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in 1 dB range
of the configured output level from the local equipment.
Connector X2

EUT:
telephony
Terminal,

O4LE
remote 7.5 H/240 Ω R = 2k2

14 µF
Audio Analyzer
A14 8a 7.5 H/240 Ω
C14 8b Generator Analyzer

14 µF
U = 50 V
Connector X2

EUT:
Terminial,
telephony

O4LE
local 7.5 H/240 Ω R

14 µF

A32 0a 7.5 H/240 Ω


C32 0b

14 µF

Figure 3

B.11.5 Pax 2-wire


The following tests must be done if the operation mode ‘Pax 2-wire’ is configured at the local
equipment.
1. Check the Output level of Pax 2-wire interface:
Use coupling bridges similar to that, shown in Figure 4. The resistor R should be chosen
to 500 Ohm, included the resistance of the two coils. If the coupling bridge has polarity.
Check first polarity at appropriate, telephony, 0a-0b and observe polarity of external
voltage source.
2. Feed a 800 Hz tone, with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in 1 dB range
of the configured output level from the local equipment.
3. Check PAX-BLOCKING relay. In normal operation contacts at terminal, telephony, 6b-7a
should be closed and contacts 6a-6b should be open.
Switch off the remote equipment, after the programmed delay time the link alarm occurs.
Now contacts at terminal, telephony, 6b-7a should be open and contacts 6a-6b should be
closed.
Revision: Language: Page:

A EN 16 1KHW002609-EN

Connector X2
EUT:

telephony
Terminal,
O4LE
remote 7.5 H/240 Ω R

14 µF
Audio Analyzer
A32 0a 7.5 H/240 Ω
C32 0b Generator Analyzer
14 µF

Connector X2
EUT:

telephony
Terminal,
O4LE
local 7.5 H/240 Ω R = 2k2

14 µF

A14 8a 7.5 H/240 Ω


C14 8b
14 µF
U = 50 V

Figure 4

B.11.6 Pax 4-wire, remote is Pax 4-wire


The following tests must be done if the operation mode ‘Pax 4-wire’ is configured at the local
equipment and the operation mode ‘Pax 4-wire’ is selected at the remote equipment.
1. Toggling the M-WIRE at remote equipment, E-WIRE output should toggle simultaneously
at local equipment. Note: E-WIRE is a switching contact without inherent voltage source
and without polarity.
2. Activate M-WIRE at both equipments. If M-WIRE is configured as ‘inverted’, contacts at
terminal, telephony, 4a-4b must be opened, otherwise closed.
3. Feed a 800 Hz tone, with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in 1 dB range
of the configured output level from the local equipment.
4. Check PAX-BLOCKING relay. In normal operation contacts at terminal, telephony, 6b-7a
should be closed and contacts 6a-6b should be open.
Switch off the remote equipment, after the programmed delay time the link alarm occurs.
Now contacts at terminal, telephony, 6b-7a should be open and contacts 6a-6b should be
closed.

B.11.7 Pax 4-wire, remote is ‘Remote subscriber’


The following tests must be done if the operation mode ‘Pax 4-wire’ is configured at the local
equipment and the operation mode ‘Remote subscriber’ is selected at the remote equipment.
1. Toggling the hook contact of remote equipment, E-WIRE output should toggle
simultaneously at local equipment. Switching of hook contact can simulated by closing
the subscriber contacts at terminal, telephony, 0a-0b. Note: E-WIRE is a switching
contact without inherent voltage source and without polarity.
2. Check the Output level of speech:
Instead of subscriber, use coupling bridge similar to that, shown in Figure 2. The resistor
R should be chosen to 500 Ohm, included the resistance of the two coils. If the coupling
bridge has polarity. Check first polarity at terminal, telephony, 0a-0b.
3. Activate M-WIRE at local equipments. If M-WIRE is configured as ‘inverted’, contacts at
terminal, telephony, 4a-4b must be opened, otherwise closed.
4. Feed a 800 Hz tone, with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in 1 dB range
of the configured output level from the local equipment.
5. Check PAX-BLOCKING relay. In normal operation contacts at terminal, telephony, 6b-7a
should be closed and contacts 6a-6b should be open.
Switch off the remote equipment, after the programmed delay time the link alarm occurs.
Now contacts at terminal, telephony, 6b-7a should be open and contacts 6a-6b should be
closed.
Revision: Language: Page:

A EN 17 1KHW002609-EN

B.11.8 Pax 4/2-wire


The following tests must be done if the operation mode ‘Pax 4/2wire’ is configured at both ends of
the link.
1. Toggling the M-WIRE at remote equipment, E-WIRE output should toggle simultaneously
at local equipment. Note: E-WIRE is a switching contact without inherent voltage source
and without polarity.
2. Activate M-WIRE at both equipments. If M-WIRE is configured as ‘inverted’, contacts at
terminal, telephony, 4a-4b must be opened, otherwise closed.
Note: It is assumed, that LOCAL/TRANSIT is deactivated.
3. Feed a 800 Hz tone, with the configured level from remote side into AF1-IN of remote
equipment.
4. Take a measurement of the output level at AF1-OUT of the local equipment. It should be
in 1 dB range of the configured output level from the local equipment.
5. Take a measurement of the output level at P2W-OUT of the local equipment. It should be
in 1 dB range of the configured output level from the local equipment.
6. Activate LOCAL/TRANSIT at remote equipment. . If LOCAL/TRANSIT is configured as
‘inverted’, contacts at terminal, telephony, 5a-4b must be opened, otherwise closed.
7. Feed a 800 Hz tone, with the configured level from remote side into P2W-IN of remote
equipment. Note: the input levels of AF1-IN and P2W-IN are normally configured
different.
8. Take a measurement of the output level at P2W-OUT of the local equipment. It should be
in 1 dB range of the configured output level from the local equipment.
9. Check PAX-BLOCKING relay. In normal operation contacts at terminal, telephony, 6b-7a
should be closed and contacts 6a-6b should be open.
Switch off the remote equipment, after the programmed delay time the link alarm occurs.
Now contacts at terminal, telephony, 6b-7a should be open and contacts 6a-6b should be
closed.

B.11.9 Transit mode for E&M wire


The following tests must be done if the operation mode ‘Transit mode for E&M wire’ is configured at
the local equipment.
1. Toggling the M-WIRE at remote equipment, E-WIRE output should toggle simultaneously
at local equipment. Note: E-WIRE is a switching contact without inherent voltage source
and without polarity.

B.11.10 Testing of the teleoperation ports


For testing the teleoperation ports, first nominal signal levels must be fed into the teleoperation
input port with a level generator. The output level at the other side of the link must then be
measured and compared to the nominal output level. An example of a link configuration is given
below.

First method:
This method only works, if identical Reference signal and identical level unit for the reference
signal, dBm (RMS) or dBm (PEP) is selected on both sides of link.
1. Determine the correct input level fed into the remote equipment.
The Reference signal level input, listed in the configuration printout of the remote
equipment should be fed into AFx-IN of the remote equipment.
2. Determine expected output level of AFx-OUT of local equipment.
The Reference signal level output of AFx-OUT of the local equipment is the expected
output level.
3. Take the measurement with a selective level meter.

Second method:
This method works with any configuration of AF ports, which are switched on.
Revision: Language: Page:

A EN 18 1KHW002609-EN

1. Determine the correct input level fed into the remote equipment.
The Reference signal level input, listed in the configuration printout of the remote
equipment should be fed into AFx-IN of the remote equipment.
2. Calculate expected output level of AFx-OUT of local equipment.
L(out ) local = L(in) remote − L( R el. Input Level ) remote + L( R el. Output Level ) local
3. Take the measurement with a selective level meter.

Example:
Applying the first method to the configuration given below, a sinus with –9.0 dBm is fed into remote
equipment. The tone is expected with –6.0 dBm at AFx-OUT of local equipment.
Applying the second method to the configuration given below, a sinus with –9.0 dBm is fed into
remote equipment. Calculating the expected output level at local equipment with the formula above
results to:
Lout = -9.0 dBm – (-4.00 dBr) + (-1.00 dBr)
The expected output level Lout is just as applying the first method –6.0 dBm.

Equipment REMOTE
TELEOPERATION
Port AFx: Disconnectable at CH1
Squelch: Disabled
Reference signal: 600 Bd FSK
Reference signal level input: -9.00 dBm (RMS)
Reference signal level output: -9.00 dBm (RMS)
Weight of port: 0.71
Max. output level: -7.00 dBm (PEP)
Relative input level: -4.0 dBr
Relative output level: -4.0 dBr
Input filter: None
Output filter: None

Equipment LOCAL
TELEOPERATION
Port AFx: Disconnectable at CH1
Squelch: Disabled
Reference signal: 600 Bd FSK
Reference signal level input: -6.00 dBm (RMS)
Reference signal level output: -6.00 dBm (RMS)
Weight of port: 0.71
Max. output level: -4.00 dBm (PEP)
Relative input level: -1.0 dBr
Relative output level: -1.0 dBr
Input filter: None
Output filter: None

B.11.11 Teleoperation port AF1


If the port AF1 is not used for a telephony application and if the port is switched to ’On –
disconnectable’ or ‘On – non disconnectable’, take the measurement as described in B.11.10.

B.11.12 Teleoperation port AF2


If the port is switched to ’On – disconnectable’ or ‘On – non disconnectable’ take the
measurement as described in B.11.10.

B.11.13 Teleoperation port AF3


If the port is switched to ’On – disconnectable’ or ‘On – non disconnectable’ take the
measurement as described in B.11.10.

B.11.14 Teleoperation port AF4


If the port is switched to ’On – disconnectable’ or ‘On – non disconnectable’ take the
measurement as described in B.11.10.

B.11.15 Teleoperation AF4 used for ext. Teleprotection


After having performed the measurement B.11.14:
Revision: Language: Page:

A EN 19 1KHW002609-EN

1. Recalculate expected output level of AF4-OUT by adding the NSD570 boost value,
available in the configuration view (View / Display Configuration / Effective boost
value ext. TPE1/2/3).
2. Activate the EXT-BOOST input at the remote equipment. If EXT-BOOST is configured as
‘inverted’, contacts at terminal, teleoperation, 9a-9b must be opened, otherwise closed.
3. Take the measurement at AF4-OUT of local equipment.

B.12 Testing of the V.11 ports


The V.11 ports are tested on correct settings and bit errors using data test equipment.
1. Check the port settings in the configuration (Configuration / Data port to modem
assignment) and use the same settings in the test equipment.
2. Connect data testers to corresponding ports on both the local and remote ETL600
equipment. If there is only one data tester available, the digital data stream has to be
looped on the remote equipment.
3. Perform a BER test during the required time. The recommended number of bits to transmit
is 107.

B.12.1 V.11 Port 1


If used, perform a BER test as described above.

B.12.2 V.11 Port 2


If used, perform a BER test as described above.

B.13 Testing of the V.24 ports


The V.24 ports are tested on correct settings and bit errors using data test equipment.

1. Check the port settings in the configuration (Configuration / Data port to modem
assignment) and use the same settings in the test equipment.
2. Connect data testers to corresponding ports on both the local and remote ETL600
equipment. If there is only one data tester available, the digital data stream has to be
looped on the remote equipment.
3. Perform a BER test during the required time. The recommended number of bits to transmit
is 107.

B.13.1 V.24 Port 1


If used, perform a BER test as described above.

B.13.2 V.24 Port 2


If used, perform a BER test as described above.

B.13.3 V.24 Port 3


If used, perform a BER test as described above.

B.13.4 V.24 Port 4


If used, perform a BER test as described above.

B.14 Testing of the LAN ports


For the applications bridging and routing, the LAN ports are tested for bit errors using Ethernet test
equipment.
1. Connect the Ethernet tester to the LAN ports of the local and remote ETL600 equipment.
2. Perform a throughput and errored frame test during the required time. The recommended
number of frames to transmit is 104.
Revision: Language: Page:

A EN 20 1KHW002609-EN

In some cases, pinging can be used as a quick test:


- In mode "IP routing (Static routes)", both the local and the remote R1LB can be pinged;
- In modes "IP routing (Forward All)" and "Bridging", the local R1LB can be pinged.

B.14.1 LAN port 1


If used, perform a BER test as described above.

B.14.2 LAN port 2


If used, perform a BER test as described above.

B.14.3 LAN port 3


If used, perform a BER test as described above.

B.14.4 LAN port 4


If used, perform a BER test as described above.

B.14.5 HMI over LAN


For the application HMI over LAN, test if HMI600 can be connected to the LAN port used for HMI
over LAN access of the ETL600 terminal.

B.15 Testing of O4CV, if present

B.15.1 Slot positions of O4CV boards


Refer to the configuration view of HMI600 for the O4CV slot positions.

B.15.2 Service phone


Only a functional test must be done. The buzzer, the ringing of the connected service phone and
the audibility between the two service phones are tested.

B.15.3 Hot line direct phone


The following tests must be done if the operation mode ‘Hot line direct phone’ is configured at both
the local and remote equipment.
1. A functional test must be done to check the ringer. Connect on both sides of link a phone,
make a call from one side to remote and vice versa.
2. Check the output level of speech:
Use coupling bridges similar to the ones shown in Figure 5. The resistor R should be
chosen to 500 Ohm, the resistance of the two coils included. If the coupling bridge has
polarity, check first polarity at appropriate external cable.
3. Feed an 800 Hz tone with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in ±5 dB
range of the configured output level of the local equipment.
Revision: Language: Page:

A EN 21 1KHW002609-EN

EUT:
O4CV
remote 7.5 H/240 Ω R

14 µF
Audio Analyzer
Subscriber 7.5 H/240 Ω
interface
Generator Analyzer

14 µF

EUT:
O4CV
local 7.5 H/240 Ω R

14 µF

Subscriber 7.5 H/240 Ω


interface

40 µF

Figure 5

B.15.4 ‘Remote subscriber’, remote is Pax 2-wire


The following tests must only be done if the operation mode ‘Remote subscriber’ is configured at
the local equipment and the operation mode ‘Pax 2-wire’ at the remote equipment.
1. A functional test must be done to check the ringer. Connect a phone at local equipment
and feed into remote PAX2W connection a ringing tone with 25 Hz and about 25 VAC.
Connect a 2.2 kOhm resistor between PAX2W input and generator! The generator
needn’t be programmed with a special ringing sequence. Now the phone should ring in a
typical sequence.
2. Check the output level of subscriber:
Use coupling bridges similar to the ones shown in Figure 6. The resistor R should be
chosen to 500 Ohm, the resistance of the two coils included. If the coupling bridge has
polarity, check first polarity of the subscriber interface at the cable terminals and observe
polarity of external voltage source.
3. Feed an 800 Hz tone with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in ±5 dB
range of the configured output level of the local equipment.

EUT:
O4CV
remote 7.5 H/240 Ω R = 2k2

14 µF
Audio Analyzer
PAX2- Wire 7.5 H/240 Ω
interface
Generator Analyzer

14 µF
U = 50 V

EUT:
O4CV
local 7.5 H/240 Ω R

14 µF

Subscriber 7.5 H/240 Ω


interface

14 µF

Figure 6
Revision: Language: Page:

A EN 22 1KHW002609-EN

B.15.5 ‘Remote subscriber’, remote is Pax 4-wire


The following tests must only be done if the operation mode ‘Remote subscriber’ is configured at
the local equipment and the operation mode ‘Pax 4-wire’ at the remote equipment.
1. A functional test must be done to check the ringer. Connect a phone at local equipment
and activate M-WIRE at the remote equipment. If M-WIRE is configured as ‘inverted’,
contacts at terminal, telephony, 4a-4b must be opened, otherwise closed. The phone
should ring in a typical sequence.
2. Check the output level of subscriber:
Instead of phone use a coupling bridge similar to the one shown in Figure 7. The resistor
R should be chosen to 500 Ohm, included the resistance of the two coils. If the coupling
bridge has polarity, check first polarity of the subscriber interface at the cable terminals.
At remote side, M-WIRE must be activated.
3. Feed an 800 Hz tone with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in ±5 dB
range of the configured output level of the local equipment.

EUT:
O4CV
remote

PAX 4-wire
Audio Analyzer
interface,
4-wire input Generator Analyzer

EUT:
O4CV
local 7.5 H/240 Ω R

14 µF

Subscriber 7.5 H/240 Ω


interface

14 µF

Figure 7

B.15.6 Pax 2-wire


The following tests must only be done if the operation mode ‘Pax 2-wire’ is configured at the local
equipment and the operation mode ‘Remote subscriber’ at the remote equipment.
1. Check the output level of Pax 2-wire interface:
Use coupling bridges similar to the ones shown in Figure 8. The resistor R should be
chosen to 500 Ohm, included the resistance of the two coils. If the coupling bridge has
polarity, check first polarity of the subscriber interface at the cable terminals of the remote
equipment and observe polarity of external voltage source.
2. Feed an 800 Hz tone with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in ±5 dB
range of the configured output level of the local equipment.
Revision: Language: Page:

A EN 23 1KHW002609-EN

EUT:
O4CV
remote 7.5 H/240 Ω R

14 µF
Audio Analyzer
Subscriber 7.5 H/240 Ω
interface
Generator Analyzer

14 µF

EUT:
O4CV
local 7.5 H/240 Ω
R = 2k2Ω

14 µF

PAX 2-Wire 7.5 H/240 Ω


interface

14 µF
U = 50 V

Figure 8

B.15.7 Pax 4-wire, remote is Pax 4-wire


The following tests must only be done if the operation mode ‘Pax 4-wire’ is configured at both local
and remote equipment.
1. Toggling the M-WIRE at remote equipment, E-WIRE output should toggle simultaneously
at local equipment. Note: E-WIRE is a switching contact without inherent voltage source
and without polarity.
2. Check the output level of Pax 4-wire interface:
Activate M-WIRE at both equipments. If M-WIRE is configured as ‘inverted’, M-wire
contacts at the cable terminals must be opened, otherwise closed.
3. Feed an 800 Hz tone with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in ±5 dB
range of the configured output level of the local equipment.

B.15.8 Pax 4-wire, remote is ‘Remote subscriber’


The following tests must only be done if the operation mode ‘Pax 4-wire’ is configured at the local
equipment and the operation mode ‘Remote subscriber’ at the remote equipment.
1. Toggling the hook contact of remote equipment, E-WIRE output should toggle
simultaneously at local equipment. Switching of hook contact can simulated by closing
the subscriber contacts at the cable terminal of the remote equipment. Note: E-WIRE is a
switching contact without inherent voltage source and without polarity.
2. Check the output level of Pax 4-wire interface:
Instead of subscriber, use coupling bridge similar to the one shown in Figure 7. The
resistor R should be chosen to 500 Ohm, included the resistance of the two coils. If the
coupling bridge has polarity, check first polarity of the subscriber interface at the cable
terminals.
3. Activate M-WIRE at local equipment. If M-WIRE is configured as ‘inverted’, M-wire
contacts at the cable terminals must be opened, otherwise closed.
4. Feed an 800 Hz tone with the configured level from remote side into remote equipment.
Take a measurement of the output level at the local equipment. It should be in ±5 dB
range of the configured output level of the local equipment.
Revision: Language: Page:

A EN 24 1KHW002609-EN

B.16 Documentation
After the testing is complete, take a printout of the configuration and status data.
1. Click the green Upload arrow  in the HMI600 toolbar with the left mouse button. This
starts configuration and status upload from the equipment. The status is displayed in the
window.
2. From the File menu, click Print to print the status data.
3. From the View menu, click Display configuration.
4. From the File menu, click Print to print the configuration data.
5. From the File menu, click Save As to save the active document to disk with the Serial
No. of the ETL600 coded in the file name, e.g. HE400327B0.ET6. All settings you have
made while working in the document will be saved to the new file, including the last
measured AF and frequency response.

B.17 Manual reset


Reset ETL600 with HMI600 (Equipment / Reset) or by switching off and on the power and wait
until all alarms disappear.
Rev. ind.
Hardware Checks ETL600 Equipment HE

Item to be Selected
No. Action Rack or programmed or alternative Remarks
module fitted or setting

A.1 General

A.2 Create a configuration file using HMI600 [ ]


HMI600

A.3 Hardware

A.3.1 Racks
Configuration file shows the correct [ ] Refer to config file
racks.

A.3.2 Modules
All modules in the racks are mounted at [ ] Refer to config file
the correct positions according to
configuration file.
Type of DSP module P4LT [ ]
P4LV [ ]
P4LX [ ]

A.3.3 SFP transceiver Mark if not configured [ ] Refer to config file


SFP transceiver fitted P4LV/X [ ]

A.3.4 Spare plates


All spare plates mounted [ ] Equipment front
completely
covered

A.4 Settings for basic equipment ETL600

A.4.1 Power amplifier P1LP Right Left


Jumpers set according to configuration P1LP Jumpers [ ] [ ]
file J1 … J12

A.4.2 Settings for RF hybrid on E5TH


Jumpers set according to configuration E5TH Jumpers [ ]
view H1 … H13
Standard tuning for RF hybrid E5TH R2, L17, C3, [ ] Fine tuning during
R1101 in middle pos. commissioning
(i.e. 50)

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHL002609-EN en A A1


Rev. ind.
Hardware Checks ETL600 Equipment HE

Item to be Selected
No. Action Rack or programmed or alternative Remarks
module fitted or setting

A.5 Settings for alarm unit R1BC, if


present
Relay 1 jumper set according to R1BC R1-1, R2-1,CA-1 [ ]
configuration file
Relay 2 jumper set according to R1BC R1-2, R2-2,CA-2 [ ]
configuration file
Relay 3 jumper set according to R1BC R1-3, R2-3,CA-3 [ ]
configuration file
Relay 4 jumper set according to R1BC R1-4, R2-4,CA-4 [ ]
configuration file
Relay 5 jumper set according to R1BC R1-5, R2-5,CA-5 [ ]
configuration file
Relay 6 jumper set according to R1BC R1-6, R2-6,CA-6 [ ]
configuration file
Relay 7 jumper set according to R1BC R1-7, R2-7,CA-7 [ ]
configuration file
Relay 8 jumper set according to R1BC R1-8, R2-8,CA-8 [ ]
configuration file

Item to be
No. Action Rack or programmed Remarks
module or fitted

A.6 Settings for NSD600 Interface


G4AI, if present

A.6.1 Tripping of the inputs


Input 1 G4AI Jumper plug N02 N08 N14 N20
N24 N30 N36 N42 N48 N54 N60
Jumper set according to 1E1, 1E2, [ ] [ ] [ ] [ ] [ ] [ ] [ ]
configuration file 1F1, 1F2
Input 2 G4AI Jumper plug N02 N08 N14 N20
N24 N30 N36 N42 N48 N54 N60
Jumper set according to 2E1, 2E2, [ ] [ ] [ ] [ ] [ ] [ ] [ ]
configuration file 2F1, 2F2
Input 3 G4AI Jumper plug N02 N08 N14 N20
N24 N30 N36 N42 N48 N54 N60
Jumper set according to 3E1, 3E2, [ ] [ ] [ ] [ ] [ ] [ ] [ ]
configuration file 3F1, 3F2
Input 4 G4AI Jumper plug N02 N08 N14 N20
N24 N30 N36 N42 N48 N54 N60
Jumper set according to 4E1, 4E2, [ ] [ ] [ ] [ ] [ ] [ ] [ ]
configuration file 4F1, 4F2

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHL002609-EN en A A2


Rev. ind.
Hardware Checks ETL600 Equipment HE

Item to be
No. Action Rack or programmed Remarks
module or fitted

A.6.2 Nominal input voltage


Input 1: G4AI Jumper plug N02 N08 N14 N20
N24 N30 N36 N42 N48 N54 N60
Jumper set according to 1A, 1B, 1C, 1D [ ] [ ] [ ] [ ] [ ] [ ] [ ]
configuration file
Input 2 G4AI Jumper plug N02 N08 N14 N20
N24 N30 N36 N42 N48 N54 N60
Jumper set according to 2A, 2B, 2C, 2D [ ] [ ] [ ] [ ] [ ] [ ] [ ]
configuration file
Input 3 G4AI Jumper plug N02 N08 N14 N20
N24 N30 N36 N42 N48 N54 N60
Jumper set according to 3A, 3B, 3C, 3D [ ] [ ] [ ] [ ] [ ] [ ] [ ]
configuration file
Input 4 G4AI Jumper plug N02 N08 N14 N20
N24 N30 N36 N42 N48 N54 N60
Jumper set according to 4A, 4B, 4C, 4D [ ] [ ] [ ] [ ] [ ] [ ] [ ]
configuration file

A.6.3 Relay contacts


Relay 1 contacts G4AI Jumper plug N02 N08 N14 N20
N24 N30 N36 N42 N48 N54 N60
Jumper set according to NC1, NO1 [ ] [ ] [ ] [ ] [ ] [ ] [ ]
configuration file
Relay 2 contacts G4AI Jumper plug N02 N08 N14 N20
N24 N30 N36 N42 N48 N54 N60
Jumper set according to NO2 NC2, NO2 [ ] [ ] [ ] [ ] [ ] [ ] [ ]
configuration file

N02 N08 N14 N20


A.6.4 Cover at component side N24 N30 N36 N42 N48 N54 N60
Mounted G4AI [ ] [ ] [ ] [ ] [ ] [ ] [ ]

A.7 Check keys

A.7.1 Valid data key mounted on P4LT, iButton [ ]


P4LT/P4LV/P4LX P4LV or
P4LX

A.7.2 Valid voice key mounted on N02 N08 N14


O4CV boards N24 N30 N36 N42 N48 N54 N60
Slots not occupied with O4CV [ ] [ ] [ ] [ ] [ ] [ ] [ ]
boards
Valid voice keys mounted O4CV [ ] [ ] [ ] [ ] [ ] [ ] [ ]

Doc. no. Lang. Rev. ind. Page

ABB Switzerland Ltd 1KHL002609-EN en A A3

You might also like