Ac Floor Standing Manual
Ac Floor Standing Manual
SAFETY PRECAUTIONS
Warning .............................................................................................................................................2
Caution ..............................................................................................................................................2
INSTALLATION INSTRUCTIONS
Accessories .......................................................................................................................................3
Selecting installation place ................................................................................................................4
PIPE CONNECTION
Refrigerant pipe connection ..............................................................................................................7
Drain pipe connection ......................................................................................................................10
ELECTRICAL WORK
Wire connection ...............................................................................................................................11
TEST RUNNING
Test running ...................... .............................................................................................................13
CAUTION
Contact an authorised service technician for repair or maintenance of this unit.
Contact an authorised installer for installation of this unit.
The air conditioner is not intended for use by young children or infirmed persons without supervision.
Young children should be supervised to ensure that they do not play with the air conditioner.
If the power cord is to be replaced, replacement work shall be performed by authorised personnel only.
Installation work must be performed in accordance with the National Wiring Standards by authorised
personnel only.
1
SAFETY PRECAUTIONS
Symbol will background white denotes item that is PROHIBITED from doing.
WARNING
1) Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water
leakage, electrical shock, or fire.
2) Install according to this installation instructions strictly. If installation is defective, it will cause water leakage,
electrical shock, or fire.
3) Use the attached accessories parts and specified parts for installation. otherwise, it will cause the set to fall,
water leakage, electrical shock, or fire.
,
4) Install at a strong and firm location which is able to withstand the set s weight. If the strength is not enough or
installation is not properly done, the set will drop and cause injury.
5) For electrical work, follow the local national wiring standard, regulation and this installation instructions. An
independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in
electrical work, it will cause electrical shock, or fire.
6) Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on
the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7) Wiring routing must be properly arranged so that control board cover is fixed properly. If control board cover
is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
8) When carrying out piping connection, take care not to let air substances other than the specified
refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure
in the refrigeration cycle, explosion and injury.
9) Do not modify the length of the power supply cord or use of extension cord, and do not share the
single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock.
CAUTION
1) This equipment must be earthed and installed with earth leakage current breaker. It may cause electrical
shock if grounding is not perfect.
2) Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and
accumulates at surrounding of the unit, it may cause fire.
3) Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water
may enter the room and damage the furniture.
4) The appliance shall be installed in accordance with national wiring regulations.
5) Do not operate your air conditioner in a wet room such as a bathroom or laundry room.
6) An all-pole disconnection device which has at least 3mm clearances in all poles , and have a
leakage current that may exceed 10mA, the residual current device (RCD) having a rated residual
operating current not exceeding 30mA, and disconnection must be incorporated in the fixed wiring
in accordance with the wiring rules.
2
INSTALLATION INSTRUCTIONS
Accessories
Before installing, please check the available accessories according to the list given below.
Please carefully keep the temporarily useless parts.
1 Safety Lock 1
3 Flat Washers 2
4 Bushing-Sleeve Cover 1
9 Remote Battery 2
HEALTH
TIMER OFF
ON/OFF FAN SPEED
TIMER ON
HIGH
LOW
DISPLAY
Remote Control
LED
¡
10 1
RESET LOCK
ADJUST
SLEEP
CLEAN
DIRECTION AIR
SWING
MODE
AIR
COOL
AUTO
HEAT
DRY
11 Connection Cables 1
Putty on some 1
12
models
13 Ratproof board 1
14 Installation manual 1
15 User's manual 1
3
INSTALLATION INSTRUCTIONS
..
1-1 Indoor Unit
Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
..
There should not be any heat source or steam near the unit.
There should not be any obstacles blocking the air circulation.
..
A place where air circulation in the room is good.
A place where drainage can be easily done.
Do not install the unit near the door way.
There should not be any direct sunlight. Otherwise, the sun will fade the plastic cabinet and affect
its appearance. If unavoidable, sunlight prevention should be taken into consideration.
( wall or obstacle )
( Ceiling)
(min)
5cm
>30(cm) Rear
(min)
4cm Front
(min) >200cm
50cm(min) 50cm(min)
(2) Please check the elevation difference between the indoor unit and the outdoor unit, the length of the
refrigerant pipe, and the curved places (bend) of the pipe are no more than the following numbers:
Elevation difference: no more than 10 M (if the elevation difference between indoor and outdoor unit
is more than 10 meters, it is recommended that the outdoor unit be located
higher than the indoor unit.)
Pipe length: no more than 20 M
Bends: no more than 5 places
4
INSTALLATION INSTRUCTIONS
(2) If the outdoor unit is to be installed on a roof or where no constructions are around, you should avoid
hard wind blows directly to the air outlet, because it may cause trouble for air-flow shortage.
For example:
Let the air outlet face a wall (if there is one) Try to make the air outlet vertical to wind
with a distance about 300 centimeters bet- direction if it is known in the season you use
ween them. the system.
Strong Wind
A B
When the air-in surface is facing a wall When the air-out surface is facing a wall
(Wall or Obstacle) Air In
Air In
>30cm Air In >30cm Maintenance
Maintenance
Maintenance Side Side
Air In Side Air Out >50cm
>300cm
Air Out
>50cm (Wall or Obstacle)
.
Caution
Installation in the following places may cause trouble. If it is unavoidable to use in such places, please
consult with the dealer.
(1) A place full of machine oil.
(2) A saline place such as coast.
(3) Hot-spring resort.
(4) A place full of sulfide gas.
(5) A place where there are high frequency machines such as wireless installation, welding
machine, medical facility.
(6) A place of special environmental conditions.
5
INSTALLATION INSTRUCTIONS
(1) Anti-falling
To prevent the indoor unit from falling, you must:
Pay full attention to the unit because its long outer shape makes it easy to fall;
Firmly fix the unit to the wall(using two 3.9*25 screws) or in the ground(by using 2 M8 screws fix
the chassis on the ground ) to avoid accidental falling.
Safety Lock
Flat washer
Air Outlet
Screw hole
(on the unit)
Air Inlet
(3) Remove the Pipe Clip before connecting the pipes and wiring; fix it again after finishing connection.
Use accessories 4 and 8 to connect the pipes/wires on both sides and back side.
Drain Pipe
6
PIPE CONNECTION
Pipe/wire-hole position on back side Pipe/wire-hole position on the bottom
Refrigerant/drain Refrigerant/drain
Wiring
Pipe holeφ85 Pipe holeφ85
Holeφ35
2 Outdoor Unit
Ship the air conditioner to the installation place originally packed;
Be careful while hanging the unit because the center of gravity of the unit is not centralized;
Do not make the angle of inclination more than 45 degrees while shipping;(Avoid horizontal
storage)
Be sure the electric insulation work is well done if installed on metal ceiling / wall.
Fix the unit feet with bolts (M10/M8). Be sure the unit is fixed strongly enough to against blast
or earthquake.
Make a concrete basement to the unit by the above references.
NOTE
Polythene pipe
The pipe can not be curved for more than 3 times. Heat-insulation cover
Cover all exposed reamer joint pipes and refrigerant
pipes with heat-insulation material. Bendable
7
PIPE CONNECTION
1. Connecting Of Refrigerant Pipe
(1) Only the correctly installing of indoor and outdoor unit done, can the refrigerant pipe be
connected.
(2) The cut-off valves are completely closed before ex-work. Before connecting the refrigerant pipe, be
careful to check whether the valves are completely closed.
(3) The connection procedure of refrigerant pipe: first, unscrew the two valves on the outdoor unit and
the pipe-jointing nut on the indoor unit(please save them care fully). Please connect the refrigerant
pipe according to the manual, the pipe-jointing nut should be screwed tightly and no leakage.
Note: you need two wrenches to make balance.
(4) When the connection of refrigerant pipe is finished, before power on the system, you should
vacuum the indoor unit through the maintenance port on the cut-off valves, or open the high-
pressure valve, and exhaust the air through the maintenance port on the low-pressure valve
(closed). It will take about ten seconds. Then screw the maintenance port on tightly.
(When supplement the refrigerant, fill from the maintenance port of the low-pressure valves on
the outdoor unit ).
(5) Open all the valves completely before power on the system, or it will cause low efficiency.
(6) Gas leak check. Make sure no gas comes from the connections by using leak detector or soap water.
Indoor unit
D
Caution check point
C
Electrical box
A: Lo packed valve B: Hi packed valve
C and D are ends of indoor unit connection.
B
Outdoor unit A
check point
8
PIPE CONNECTION
Use thumb to curve the pipe
Torque wrench
Spanner
Indoor unit
Outdoor unit
4. Refrigerant charging
The correct refrigerant charging amount to the 5-meter-long pipe of the outdoor unit is marked on the
Product Data Plate. If you have to use longer pipe for every meter plus pipe, the refrigerant should be
added according to the following calculation.
Use vacuum
Less than 5m
pump.
Use vacuum Liquid side: 6.35 Liquid side: 9.53 Liquid side: 12.7
More than 5m pump.
R22: (Pipe length-5)x30g/m R22: (Pipe length-5)x60g/m R22: (Pipe length-5)x80g/m
R410A: (Pipe length-5)x20g/m R410A: (Pipe length-5)x40g/m R410A: (Pipe length-5)x60g/m
NOTE: If you are using a pipe purchased in the market, please make sure the heat-insulation
material is the same as what we supply(at least 12mm in thickness).
9
PIPE CONNECTION
Drain pipe
Make sure the drain pipe is connected to the outdoor side downward;
The hard polyvinyl chloride(PVC)plastic pipe (external diameter 26 mm) sold in the market is
suitable for attached with the soft drain pipe;
Please connect the Soft Drain Pipe with the Drain Pipe , then fix it with band; if you have to connect
the Drain Pipe indoors, to avoid condensing caused by air intake, you must protect the pipe with
heat-insulation material (polyethylene with Specific Gravity of 0.03, at least 9 mm in thickness),
and wrap it with band.
After the Drain Pipe has been connected, please check if the water drains out through the pipe
efficiently without leakage.
Refrigerant Pipe and Drain Pipe should be heat-insulated to avoid condensing and water -dropping
later on.
10
ELECTRICAL WORK
Operation Tips
1. Wire connecting
NOTE: The outdoor unit you purchased may be
look like one of the following, and the wire connecting
is different. Cover
Note: Put the power supply cable in the same outlet hole to ensure it would not loosen.
Note: The power supply of the air conditioner is different according to the models. Please refer
to the WIRING DIAGRAM pasted on the indoor and outdoor units before wire connection.
Note: The power supply of the unit is subject to the wiring diagram above.
Note: Some models is equipped with a cord having a plug, So a wall outlet shall be properly
installed.
11
ELECTRICAL WORK
1. Wire connecting
1. Remove the right-side front panel from the unit .
2. Connect the connective cables to the terminals as
identified with their respective matched numbers on
the terminal block of indoor and outdoor units.
3. Secure the cable onto the control board with the cord clamp.
Connective Cable
4. Reinstall the right-side front panel to its original position after
finishing the wire connection. Connective Pipe
5. Wiring connection must be done strictly according to the Right-side
"Wiring Diagram"located on the side panel of air conditioner . front panel
6. Follow the instructions of wiring connection in this manual, never
attempt to modify the wiring by yourself. Model B
CAUTION
Wrong wiring connections may cause some electrical parts to malfunction. The air conditioner must
be grounded well.
NOTE: The cable size and the current of the fuse or switch are determined by the maximum current
indicated on the nameplate which located on the side panel of the unit. Please refer to the
nameplate before selecting the cable, fuse and switch.
NOTE:
1. Please pay attention to the surroundings (environmental temperature, direct sunlight, rain etc.)
2. We consider the minimal size of the metal core as the wire size. So it is recommended you
adopt a thicker one as the power conducting wire so as to avoid power decrease;
3. Connect the grounded wire to both indoor and outdoor units;
4. This table is just an on-site wire-connecting example. For details, please refer to relative
National criteria.
12
ELECTRICAL WORK
5-3. Electrical safety check
Perform the electric safe check after completing installation:
1. Insulated resistance
The insulated resistance must be more than 2MΩ.
2. Grounding work
After finishing grounding work, measure the grounding resistance by visual detection and
grounding resistance tester. Make sure the grounding resistance is less than 4Ω.
3. Electrical leakage check (performing during test running)
During test operation after finishing installation, the serviceman can use the electroprobe and
multimeter to perform the electrical leakage check. Turn off the unit immediately if leakage
happens. Check and find out the solution ways till the unit operate properly.
Test Running
Perform test running operation after finishing gas leak and electrical safety check. The test operation
time should last more than 30 minutes.
1. Turn on the unit.
2. Press the TEST RUNNING button on control panel, the unit will begin TEST RUNNING operation.
3. Check if all the functions works well while in testing operation. Especially check whether the water
drainage of indoor unit is smoothly or not.
4. Press the TEST RUNNING button again till the operation indicator turns dark after finishing the
test operation and the unit stops operation.
13