XS2 - Negative Sequence Relay: Original Technical Manual XS2 (Revision B)
XS2 - Negative Sequence Relay: Original Technical Manual XS2 (Revision B)
Woodward reserves the right to update any portion of this publication at any time.
Information provided by Woodward is believed to be correct and reliable.
However, no responsibility is assumed by Woodward unless otherwise expressly undertaken.
© Woodward 1994-2018
2 DOK-TD-XS2 Rev. B
Manual XS2 Woodward
Contents
1. Introduction and application ....................................................................... 4
2. Design ........................................................................................................... 5
3. Working principle ......................................................................................... 6
3.1 Principle of negative sequence protection ..........................................................................6
3.2 Measurement principle ........................................................................................................7
4. Operation and settings .............................................................................. 10
4.1 Setting of DIP-switches .....................................................................................................11
4.2 Setting of the tripping values .............................................................................................12
4.3 Communication via serial interface adapter XRS1 ...........................................................13
5. Relay case and technical data .................................................................. 14
5.1 Relay case.........................................................................................................................14
5.2 Technical data ...................................................................................................................15
5.3 Tripping characteristic .......................................................................................................17
DOK-TD-XS2 Rev. B 3
Woodward Manual XS2
There is a choice between an independent and an in-verse time tripping characteristic. In case of
low un-balanced-load, a warning is given after an adjustable time-delay. In case of inadmissible
high unbalanced-load, the XS2 relay trips in accordance with the set characteristic.
When compared to the conventional protection equipment all relays of the PROFESSIONAL LINE
reflect the superiority of digital protection techniques with the following features:
4 DOK-TD-XS2 Rev. B
Manual XS2 Woodward
2. Design
Analog inputs
The phase currents are connected to the protection device via separate c.t.s to the terminals 1S1 -
3S2.
Contact positions
DOK-TD-XS2 Rev. B 5
Woodward Manual XS2
3. Working Principle
The secondary currents of the main current transformers of the protected object are converted to
voltage signals in proportion to the currents via the burdened input transformers. The noise signals
caused by inductive and capacitive coupling are suppressed by an analog R-C filter circuit.
The analog voltage signals are fed to the A/D-converter of the microprocessor and transformed to
digital signals through Sample- and Hold- circuits. The analog signals are sampled at fn = 50 Hz
(60 Hz) with a sampling frequency of 600 Hz (720 Hz), namely, a sampling rate of 1.66 ms (1.38
ms) for every measuring quantity.
The essential part of the XS2 relay is a powerful microcontroller. All of the operations, from the
analog digital conversion to the relay trip decision, are carried out by the microcontroller digitally.
The calculated actual negative sequence current values are compared with the relay settings. If a
negative sequence current exceeds the pickup value, an alarm is given and after the set trip delay
has elapsed, the corresponding trip relay is activated.
Through the unbalanced-load, negative sequence cur-rents occur in the stator, which cause higher
harmonics with odd numbers in the stator winding and higher harmonics with even numbers in the
rotor winding. The rotor is particularly endangered in this because the higher harmonics put extra
load on the rotor winding and induce eddy currents in massive iron content of the rotor which can
even lead to melting of the metal or to the destruction of the metal structure.
An unbalanced-load is, however, permissible in certain limits and with regard to the thermal loading
limit of the generator. In order to avoid a premature outage of the generator in case of unbalanced-
load, the tripping characteristic of the negative sequence protection should be adapted to the ther-
mal characteristic of the generator.
Basically it is established that the better the cooling of the rotor, the lower are generally the permis-
sible negative sequence values. This is due to the fact that with better rotor-cooling the maximum
permissible symmetrical load can be chosen higher, however in relation to that, an unbalanced-
load is permissible to a lesser ex-tent. For turbo-generators the value of the permissible unbal-
anced-load is relatively low. Usual values are approx. 10 - 15 % of the load which is permissible
with symmetrical load.
The negative sequence relay XS2 has a large number of adjustable tripping characteristics. Protec-
tion of al-most every type of generator is thereby possible.
In case of unsymmetrical short-circuits in the grid the negative sequence protection relay normally
also picks up. In order to ensure selectivity, to the extent the over-load carrying capacity of the
generator permits it, a tripping time longer than that of the mains protection (e.g. overload protec-
tion) is to be selected.
6 DOK-TD-XS2 Rev. B
Manual XS2 Woodward
Figure 3.1
A rotating field is produced with opposite direction. If the currents of this negative-sequence system
are added, the sum is zero in case of a symmetrically load.
Figure 3.2:
Figure 3.2 shows the current vectors of an unsymmetrically loaded generator. The XS2 relay forms
the negative-sequence system by rotation and adding of the current vectors. Tripping takes place
according to the adjusted tripping-characteristic. For exact rotation of the current vectors by 120° or
240°, the accurate setting of the system frequency is necessary.
DOK-TD-XS2 Rev. B 7
Woodward Manual XS2
a) The continuously permissible negative sequence related to the rated current (IN) of the genera-
tor.
K2 = I2S/IN
This is usually given in % where I2S is the continuously permissible negative sequence current.
K1 = K22 x TINV
Further values can be taken from DIN 57 530 part 1 / IEC VDE 0530 part 1.
The maximum permissible time tperm of the negative sequence current I2 is given by:
𝑇𝐼𝑁𝑉
𝑡𝑝𝑒𝑟𝑚 = ; 𝑤ℎ𝑒𝑟𝑒 𝑇𝐼𝑁𝑉 = 𝐾1 /𝐾22
(𝐼2 /𝐼2𝑆 )2 − 1
The following table shows current unbalances at different asymmetry occurrences and gives infor-
mation on test results at different cases of asymmetry, based on a 3-phase power source with ad-
justable phase angle of the currents.
Current Negative
sequence
current
IL1 (x In) Angle (°) IL2 (x In) Angle (°) IL3 (x In) Angle (°) I2 (x In)
1,00 - 0 - 0 - 0.33
0 - 1.00 - 0 - 0.33
0 - 0 - 1.00 - 0.33
1.00 0 1.00 240 1.00 120 0
1.00 0 1.00 120 1.00 240 1.00
1.00 0 1.00 180 0.00 - 0.578
0 - 1.00 0 1.00 120 0.33
8 DOK-TD-XS2 Rev. B
Manual XS2 Woodward
Example of setting
At first the calculation is done for the generator nominal current related to the secondary side of
current transformer:
INsec = 800 A x 5 / 1000 = 4 A
The continuously permissible negative sequence current related to the secondary side of the cur-
rent transformer amounts to:
The pickup value I2S of the negative sequence currents (related to IN = 5A) can be calculated to:
The time-constant T for the selection of the tripping characteristic can be calculated as follows:
For the warning stage I2W, a somewhat lower value than I2S (e.g. 10 %) is used. The setting value
I2W then works out as follows:
0.1 ∙ 800 𝐴
𝐼2𝑊 = = 0.064 (6.4%)
1000
∙4𝐴
5
It is recommended that the time-delay tW for the negative sequence warning has to be adjusted to
about 5 s.
DOK-TD-XS2 Rev. B 9
Woodward Manual XS2
For adjustment of the unit the transparent cover has to be opened as illustrated. Do not use force!
The trans-parent cover has two inserts for labels.
10 DOK-TD-XS2 Rev. B
Manual XS2 Woodward
LEDs
LED “ON” is used for display of the readiness for ser-vice (at applied auxiliary voltage Uv). LEDs
I2s> and I2w> signal pickup (flashing) or tripping (steady light) of the corresponding function.
Tripping characteristic
The tripping characteristic requested for the current un-balance protection can be adjusted by
using DIP-switch 1:
DIP switch 1 OFF = definite time characteristic (DEFT) selected for I2s>
DIP switch 1 ON= inverse time characteristic (INV) selected for I2s>
Rated frequency
With the aid of DIP-switch 6 the rated frequency can be set to 50 or 60 Hz, depending upon the
given mains characteristics.
DOK-TD-XS2 Rev. B 11
Woodward Manual XS2
Example:
A tripping value of 36 % In is to be set. The set value of the right potentiometer is just added to the
value of the coarse setting potentiometer. (The arrow of the coarse setting potentiometer must be
inside of the marked bar, otherwise no defined setting value).
Time delay tw
The time delay tw for warning of current unbalance I2w> can be adjusted in the range 0 - 25s or 0 -
250s. The tripping characteristic is always definite time.
12 DOK-TD-XS2 Rev. B
Manual XS2 Woodward
For communication of the units among each other and with a superior management system, the in-
terface adapter XRS1 is available for data transmission, including operating software for our relays.
This adapter can easily be retrofitted at the side of relay. Screw terminals simplify its installation.
Optical transmission of this adapter makes galvanic isolation of the relay possible. Aided by the
software, actual measured values can be processed, relay parameters set and protection functions
programmed at the output relays. Information about unit XRS1 in detail can be taken from the de-
scription of this unit.
DOK-TD-XS2 Rev. B 13
Woodward Manual XS2
Connection terminals
The connection of up to a maximum 2 x 2.5 mm 2 cross-section conductors is possible. For this the
transparent cover of the unit has to be removed (see para. 4).
14 DOK-TD-XS2 Rev. B
Manual XS2 Woodward
Auxiliary voltage
Rated auxiliary voltage Uv/
Power consumption: 19 - 390 V DC or 36 - 275 V AC / 4 W
(terminals A1 and A2)
Maximum permissible auxiliary UV = 24 V DC: tu = 8 ms, UV = 48 VDC: tu = 35 ms
voltage discontinuance tu UV > 60 V DC: tu = 50 ms
Common data
Dropout to pickup ratio: < 97 %
Resetting time from pickup: <50 ms
Returning time from trip: 200 ms
Minimum initialization time after
supply voltage has applied: 120 ms
Minimum response time
when supply voltage is available: 70 ms
Output relay
Number of relays: 2
Contacts: 1 changeover contact for each trip relay
Maximum breaking capacity: ohmic 1250 VA / AC resp. 120 W / DC
inductive 500VA / AC resp. 75 W / DC
Max. rated voltage: 250 V AC
220 V DC ohmic load Imax. = 0,2 A
inductive load Imax. = 0,1 A at L/R ≤ 50 ms
24 V DC inductive load Imax. = 5 A
Minimum load: 1 W / 1 VA at Umin ≥ 10 V
Maximum rated voltage: 250 V AC/125 V DC
Maximum rated current: 5A
Making current (16ms): 20 A
Contact life span: 105 operations at max. breaking capacity
Contact material: AgCdO
System data
Design standard: VDE 0435 T303; IEC 0801 part 1-4;
VDE 0160; IEC 255-4; BS142; VDE 0871
Temperature range at storage
and operation: - 25°C to + 70°C
DOK-TD-XS2 Rev. B 15
Woodward Manual XS2
Repeat accuracy: 1%
Basic time delay accuracy: 0.5 % or ±25 ms
Basic accuracy of current: 2 % of In
Transient overreach at
instantaneous operation: ≤5%
Temperature effect: 0.02 % per K
Frequency effect: 3 % per K deviation from rated value
Mechanical test:
Shock: class 1 acc. to DIN IEC 255-21-2
Vibration: class 1 acc. to DIN IEC 255-21-1
Degree of protection
Front plate: IP40 at closed front cover
Weight: approx. 0.5 kg
Mounting position: any
Relay case material: self-extinguishing
16 DOK-TD-XS2 Rev. B
Manual XS2 Woodward
DOK-TD-XS2 Rev. B 17
Woodward Manual XS2
Setting of parameters
18 DOK-TD-XS2 Rev. B
Manual XS2 Woodward
DOK-TD-XS2 Rev. B 19
Woodward Manual XS2
Internet
www.woodward.com
Sales
Phone: +49 (0) 21 52 145 331 Telefax: +49 (0) 21 52 145 354
E-mail: [email protected]
Service
Phone: +49 (0) 21 52 145 600 Telefax: +49 (0) 21 52 145 455
E-mail: [email protected]