Grease Interceptor Sizing - Seat Method (Version 1)

This document is a design calculation sheet for sizing a grease interceptor. It calculates that for a commercial kitchen with 50 seats, a 200 gallon (757.08 L) interceptor is required based on a waste flow rate of 1.5 gallons per meal over a retention time of 2.5 hours. It also calculates that for a kitchen with 100 seats, a 400 gallon (1514.16 L) interceptor is needed. Both interceptors must have a drainage period of at least 2 minutes according to relevant plumbing codes.

Uploaded by

FARRUKH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
118 views2 pages

Grease Interceptor Sizing - Seat Method (Version 1)

This document is a design calculation sheet for sizing a grease interceptor. It calculates that for a commercial kitchen with 50 seats, a 200 gallon (757.08 L) interceptor is required based on a waste flow rate of 1.5 gallons per meal over a retention time of 2.5 hours. It also calculates that for a kitchen with 100 seats, a 400 gallon (1514.16 L) interceptor is needed. Both interceptors must have a drainage period of at least 2 minutes according to relevant plumbing codes.

Uploaded by

FARRUKH
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

Design calculation sheet

Project no: Date: 30/09/2007 Sheet No. 1 of 1 Computed by:


Subject: Checked by:
Approved by:

See Uniform Plumbing Code -2006

No. of seats = 50 Seats (As per plan)


Waste Flow rate = 1.5 gal/meal (Seating dining)
Retention Time = 2.5 hours (Commerical Kitchen waste)
Interceptor Size = 187.5 gal
200 gal
757.08 L

Drainage Period = 2 minutes (See NSPC -2003)

Interceptor Flow-rate = 100 gpm


6.31 l/s

6000
144000
545.45454545

1 M3 = 264 GALLONS 22.72727273


Design calculation sheet
Project no: Date: 30/09/2007 Sheet No. 1 of 1 Computed by:
Subject: Checked by:
Approved by:

See Uniform Plumbing Code -2006

No. of seats = 100 Seats (As per plan)


Waste Flow rate = 1.5 gal/meal (Seating dining)
Retention Time = 2.5 hours (Commerical Kitchen waste)
Interceptor Size = 375 gal
400 gal
1514.16 L

Drainage Period = 2 minutes (See NSPC -2003)

Interceptor Flow-rate = 200 gpm


12.62 l/s