PM044F - Winding 17: Technical Data Sheet
PM044F - Winding 17: Technical Data Sheet
Marine generators may be certified to Lloyds, DnV, Bureau Standard generators are 3-phase reconnectable with 12
Veritas, ABS, Germanischer-Lloyd or RINA. ends brought out to the terminals, which are mounted at
Other standards and certifications can be considered on the non-drive end of the generator. Dedicated single
request. phase generators are also available. A sheet steel
terminal box contains provides ample space for the
VOLTAGE REGULATOR customers' wiring and gland arrangements. Alternative
terminal boxes are available for customers who want to fit
AS480 AVR additional components in the terminal box.
With this self-excited system the main stator provides SHAFT & KEYS
power via the AVR to the exciter stator. The high efficiency
semi-conductors of the AVR ensure positive build-up from All generator rotors are dynamically balanced to better
initial low levels of residual voltage. than BS6861:Part 1 Grade 2.5 for minimum vibration in
The exciter rotor output is fed to the main rotor through a operation. Two bearing generators are balanced with a
three-phase full-wave bridge rectifier. The rectifier is half key.
protected by a surge suppressor against surges caused, for
example, by short circuit or out-of-phase paralleling. The
APPROVED DOCUMENT
INSULATION / IMPREGNATION
AS480 will support limited accessories, RFI suppession
remote voltage trimmer and for the P1 range only a 'droop' The insulation system is class 'H'.
Current Transformer (CT) to permit parallel operation with All wound components are impregnated with materials and
other ac generators. processes designed specifically to provide the high build
The AVR is can be fitted to either side of the generator in its required for static windings and the high mechanical
own housing in the non-drive end bracket. strength required for rotating components.
The EBS is a single, self-contained unit, attached to the Generators are manufactured using production
non-drive end of the generator. procedures having a quality assurance level to BS EN ISO
The EBS unit consists of the Excitation Boost Controller 9001.
(EBC) and an Excitation Boost Generator (EBG). Under
fault conditions, or when the generator is subjected to a The stated voltage regulation may not be maintained in
large impact load such as a motor starting, the generator the presence of certain radio transmitted signals. Any
voltage will drop. The EBC senses the drop in voltage and change in performance will fall within the limits of Criteria
engages the output power of the EBG. This additional 'B' of EN 61000-6-2:2001. At no time will the steady-state
power feeds the generator’s excitation system, supporting voltage regulation exceed 2%.
the load until breaker discrimination can remove the fault or
enable the generator to pick up a motor and drive the DE RATES
voltage recovery.
All values tabulated on page 6 are subject to the following
WINDINGS & ELECTRICAL PERFORMANCE reductions
All generator stators are wound to 2/3 pitch. This 5% when air inlet filters are fitted.
eliminates triplen (3rd, 9th, 15th …) harmonics on the 3% for every 500 metres by which the operating altitude
voltage waveform and is found to be the optimum design exceeds 1000 metres above mean sea level.
for trouble-free supply of non-linear loads. The 2/3 pitch 3% for every 5°C by which the operational ambient
design avoids excessive neutral currents sometimes seen temperature exceeds 50°C.
with higher winding pitches, when in parallel with the mains. Note: Requirement for operating in an ambient exceeding
A fully connected damper winding reduces oscillations 60°C must be referred to the factory.
during paralleling. This winding, with the 2/3 pitch and
carefully selected pole and tooth designs, ensures very low 5% For reverse rotation
waveform distortion. (Standard rotation CW when viewed from DE)
2
PM044F
WINDING 17
CONTROL SYSTEM AS480 AVR WITH EXCITATION BOOST SYSTEM (EBS)
PROTECTION IP23
WINDING LEADS 12
STATOR WDG. RESISTANCE 1.341 Ohms PER PHASE AT 22°C SERIES STAR CONNECTED
R.F.I. SUPPRESSION
APPROVED DOCUMENT
BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING LINEAR LOAD < 5.0%
1 BEARING 2 BEARING
WITH EBS WITHOUT EBS WITH EBS WITHOUT EBS
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
3
PM044F
Winding 17
APPROVED DOCUMENT
600V
30
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
10
0
0 5 10 15 20 25 30 35 40
LOCKED ROTOR kVA
4
PM044F
Winding 17
1000
SYMMETRICAL
CURRENT (Amps)
ASYMMETRICAL
100
APPROVED DOCUMENT
10
0.001 0.01 TIME (secs)
0.1 1 10
Note
The following multiplication factor should be used to convert the values from curve for the
various types of short circuit :
5
PM044F
Winding 17 / 0.8 Power Factor
60Hz RATINGS
Class - Temp Rise Cont. E - 65/50°C Cont. B - 70/50°C Cont. F - 90/50°C Cont. H - 110/50°C
Series Star (V) 600 600 600 600
Parallel StarStar (V) 300 300 300 300
Series Delta (V) 346 346 346 346
kVA 10.6 11.0 12.5 13.8
DIMENSIONS
6
APPROVED DOCUMENT
www.cumminsgeneratortechnologies.com
PM044F-17-TD-EN-SG-A