PROJECT : KALINGA HOSPITAL AT
BHUBANESWAR
BILL OF QUANTITY - HVAC WORKS
S.NO. DESCRIPTION UNIT QTY RATE AMOUNT
A. EQUIPMENTS
1
Supply, installation,testing and commissioning of 200 TR nominal capacity
AIR Cooled Package Chiller with Fixed Speed.The chiller shall have semi-
hermitic Screw compressor, shell and tube chiller with necessary thermal
insulation, copper tube and aluminium fin condenser coil with adequate
number of fans for air circulation over the coils. The fans to be with IP 55
protected squirrel cage induction motors and interconnected copper
refrigerant piping with necessary accessories. The package chillers shall
have factory wire controls panel with touch type 12" LED screen, multiple
compressor and independent refrigerant circuit with thermostatic expansion
valve. Chillers shall be with initial charge of refrigerant R-134a or equivalent
and oil.
The price shall include anti-vibration mount,insulation, bellows.The
electrical accessories and components should withstand +/- 10% voltage
variation. Chillers should be selected for following duty conditions. and chiller
make should be AHRI certified
The cost shall also include supply and wiring of contactors, auxiliary
contactors, timers, control switches and providing necessary interlocking
between all high side equipments including all wiring and testing.(1W+1S )
Please note it is the responsibility of the HVAC contractor to provide the
necessary details for giving provision in the electrical panel
CHW In 12.0 deg C
CHW Out 7.0 deg C
Ambient temp 38 deg.C Dry Bulb
The chiller
should have provision for compatibility with BMS system capable of being
compatible with BacNet / Modbus / LON protocol.The chiller shall have soft
starter and spring isolator for vibration isolation.
Kindly refer to the enclosed chiller equipment schedule
Note: The enclosed Chiller data sheet has to be filled in
and submitted along with the tender
Supply Nos 1 0
Installation Nos 1 0
2 Factory fitted Adiabatic Cooling System to reduced Condensing
temperaturein which water should be sprayed in the form of mist over a
dedicated panel (plastic net), thus improving the heat exchange process with
a partial water evaporation.The cost shall also include Dedicated controller
with temperature probe to manage the ON/OFFsolenoid Valve,Nozzle,Plastic
Net etc..,
Supply Nos 1 0
Installation Nos 1 0
TOTAL 0