General Specifications: EJA110A Differential Pressure Transmitter
General Specifications: EJA110A Differential Pressure Transmitter
General EJA110A
Specifications Differential Pressure Transmitter
GS 01C21B01-00EN
STANDARD SPECIFICATIONS
Refer to GS 01C22T02-00EN for FOUNDATION Fieldbus
communication type and GS 01C22T03-00EN for
PROFIBUS PA communication type marked with “◊.”
□ PERFORMANCE SPECIFICATIONS
Zero-based calibrated span, linear output, wetted parts
material code ‘S’ and silicone oil.
Reference Accuracy of Calibrated Span
(including the effects of zero-based linearity,
hysteresis, and repeatability) Static Pressure Effects
Total Effects per Change
±0.065 % of Span L capsule
For spans below X ±[0.07 % Span+0.052 % URL] per 3.4 MPa {500 psi}
X
M, H and V capsules
±[0.015 + 0.05 Span ] % of Span ±[0.1% Span+0.028 % URL] per 6.9 MPa {1000 psi}
Effect on Zero (can be corrected at line
where X equals: pressure)
Capsule X kPa {inH2O} L capsule
L 3 {12} ±[0.02 % Span+0.052 % URL] per 3.4 MPa {500 psi}
M 10 {40} M, H and V capsules
H 100 {400} ±0.028 % of URL per 6.9 MPa {1000 psi}
V 1.4 MPa {200 psi} Overpressure Effects (M, H and V capsules)
±0.03 % of URL per 16 MPa {2300 psi}
Square Root Output Accuracy Stability
The square root accuracy is a percent of flow span. ±0.1 % of URL per 60 months (M, H and V capsules)
±0.2 % of URL per 12 months (L capsule)
Output Accuracy
50 % or Greater same as reference accuracy Power Supply Effects “◊”
±0.005 % per Volt (from 21.6 to 32 V DC, 350 Ω)
reference accuracy × 50
50 % to Dropout point square root output (%)
Capsule Effect
L ±[0.08 % Span + 0.09 % URL]
M ±[0.07 % Span + 0.02 % URL]
H ±[0.07 % Span + 0.015 % URL]
V ±[0.07 % Span + 0.03 % URL]
(approval codes may affect limits) Figure 2. Relationship Between Power Supply
−40 to 85 °C (−40 to 185 °F) Voltage and External Load Resistance
−30 to 80 °C (−22 to 176 °F) with LCD Display
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 01C21B01-00EN Jan. 27, 2016-00
<<Contents>> <<Index>> 3
Supply Voltage “◊” Non-wetted Parts Materials
10.5 to 42 V DC for general use and flameproof type Bolting
10.5 to 32 V DC for lightning protector (Optional code SCM435, SUS630, or SUH660
/A)
10.5 to 30 V DC for intrinsically safe, Type n, Housing
nonincendive, or non-sparking type Low copper cast-aluminum alloy with polyurethane
Minimum voltage limited at 16.4 V DC for digital paint (Munsell 0.6GY3.1/2.0)
communications, BRAIN and HART Degrees of Protection
Load(Output signal code D and E) IP67, Type 4X
0 to 1335 Ω for operation Cover O-rings
250 to 600 Ω for digital communication Buna-N, fluoro-rubber (optional)
EMC Conformity Standards “◊” Name plate and tag
EN61326-1 Class A, Table2 (For use in industrial SUS304 or SUS316 (option)
locations) Fill Fluid
EN61326-2-3 Silicone, Fluorinated oil (option)
European Pressure Equipment Directive 97/23/EC Weight
Sound Engineering Practice 3.9 kg (8.6 lb) without integral indicator, mounting
Safety Requirement Standards bracket, and process connector.
EN61010-1 Connections
• Altitude of installation site: Max. 2,000 m above sea Refer to the model code to specify the process and
level electrical connection type.
• Installation category: I Process Connection of Cover Flange:
• Pollution degree: 2 DIN 19213 with 7/16 inch × 20 unf female thread.
• Indoor/Outdoor use
Communication Requirements “◊”
BRAIN < Settings When Shipped > “◊”
Communication Distance Tag Number As specified in order *1
Up to 2 km (1.25 miles) when using CEV
Output Mode ‘Linear’ unless otherwise
polyethylene-insulated PVC-sheathed cables.
specified in order
Communication distance varies depending on type of
cable used. Display Mode ‘Linear’ unless otherwise
specified in order
Load Capacitance Operation Mode ‘Normal’ unless otherwise
0.22 µF or less (see note) specified in order
Load Inductance Damping Time Constant *2 ‘2 sec.’
3.3 mH or less (see note) Calibration Range Lower As specified in order
Spacing from power line Range Value
15 cm or more. Calibration Range Higher As specified in order
Input Impedance of communicating device Range Value
10 kΩ or more at 2.4 kHz. Calibration Range Units Selected from mmH2O, mmAq,
mmWG, mmHg, Pa, hPa, kPa,
Note: For general-use and Flameproof type. MPa, mbar, bar, gf/cm2, kgf/cm2,
For Intrinsically safe type, please refer to inH2O, inHg, ftH2O, or psi.
‘OPTIONAL SPECIFICATIONS.’ (Only one unit can be specified)
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 01C21B01-00EN Jan. 27, 2016-00
<<Contents>> <<Index>> 4
MODEL AND SUFFIX CODES
Model Suffix Codes Description
EJA110A ..................... Differential pressure transmitter
Output Signal -D . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
-E . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (HART protocol, refer to GS 01C22T01-00EN)
-F . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C22T02-00EN)
-G . . . . . . . . . . . . . . . . . . . Digital communication (PROFIBUS PA protocol, refer to GS 01C22T03-00EN)
Measurement L . . . . . . . . . . . . . . . . . . 0.5 to 10 kPa {50 to 1000 mmH2O} {2 to 40 inH2O} {5 to 100 mbar}
span (capsule) M . . . . . . . . . . . . . . . . . . 1 to 100 kPa {100 to 10000 mmH2O} {4 to 400 inH2O} {10 to 1000 mbar}
H . . . . . . . . . . . . . . . . . . 5 to 500 kPa { 0.05 to 5 kgf/cm2} {20 to 2000 inH2O} {50 to 5000 mbar}
V . . . . . . . . . . . . . . . . . . 0.14 to 14 MPa { 1.4 to 140 kgf/cm2}*1 {20 to 2000 psi} {1.4 to 140 bar}
Wetted parts [Body]*2 [Capsule] [Vent plug]
material*11 S# . . . . . . . . . . . . . . . SCS14A SUS316L*5 SUS316*13
H# . . . . . . . . . . . . . . . SCS14A Hastelloy C-276*6*12 SUS316*13
M# . . . . . . . . . . . . . . . SCS14A Monel*6 SUS316*13
T . . . . . . . . . . . . . . . . SCS14A Tantalum*6 SUS316*13
A# . . . . . . . . . . . . . . . Hastelloy C-276 equivalent*3 Hastelloy C-276*6*12 Hastelloy C-276*12
D . . . . . . . . . . . . . . . . Hastelloy C-276 equivalent*3 Tantalum*6 Hastelloy C-276*12
B# . . . . . . . . . . . . . . . Monel equivalent*4 Monel*6 Monel
Process connections 0 . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
1 . . . . . . . . . . . . . . with Rc1/4 female process connector
2 . . . . . . . . . . . . . . with Rc1/2 female process connector
3 . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . with 1/2 NPT female process connector
► 5 . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts material [Maximum working pressure]
► A . . . . . . . . . . . . SCM435 16 MPa {160 kgf/cm2}*9
B . . . . . . . . . . . . SUS630 16 MPa {160 kgf/cm2}*9
C . . . . . . . . . . . . SUH660 16 MPa {160 kgf/cm2}*9
Installation -2 . . . . . . . . . . Vertical impulse piping type, right side high pressure, process connector upside*7
-3 . . . . . . . . . . Vertical impulse piping type, right side high pressure, process connector downside*7
-6 . . . . . . . . . . Vertical impulse piping type, left side high pressure, process connector upside*7
-7 . . . . . . . . . . Vertical impulse piping type, left side high pressure, process connector downside*7
-8 . . . . . . . . . . Horizontal impulse piping type, right side high pressure*8
► -9 . . . . . . . . . . Horizontal impulse piping type, left side high pressure*8
Electrical connection 0 . . . . . . . . G1/2 female, one electrical connection
► 2 . . . . . . . . 1/2 NPT female, two electrical connections without blind plug
3 . . . . . . . . Pg 13.5 female, two electrical connections without blind plug
4 . . . . . . . . M20 female, two electrical connections without blind plug
5 . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
8 . . . . . . . . Pg 13.5 female, two electrical connections and a blind plug
9 . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . G1/2 female, two electrical connections and a SUS316 blind plug
C . . . . . . . . 1/2 NPT female, two electrical connections and a SUS316 blind plug
D . . . . . . . . M20 female, two electrical connections and a SUS316 blind plug
Integral indicator D . . . . . . Digital indicator
E . . . . . . Digital indicator with the range setting switch*10
► N . . . . . . (None)
Mounting bracket ► A . . . SECC Carbon steel 2-inch pipe mounting (flat type)
B . . . SUS304 2-inch pipe mounting (flat type)
J . . . SUS316 2-inch pipe mounting (flat type)
C . . . SECC Carbon steel 2-inch pipe mounting (L type)
D . . . SUS304 or SCS13A 2-inch pipe mounting (L type)
K . . . SUS316 or SCS14A 2-inch pipe mounting (L type)
N . . . (None)
Optional codes / Optional specification
The “►” marks indicate the most typical selection for each specification. Example: EJA110A-DMS5A-92NA/
The ‘#’ marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of
SUS316 material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for
details.
*1: For Wetted parts material code H, M, T, A, D, and B, the range limits are 0 to 14 MPa{0 to 140 kgf/cm2}.
*2: Indicates material of cover flanges and process connectors.
*3: Indicated material is equivalent to ASTM CW-12MW.
*4: Indicated material is equivalent to ASTM M35-2.
*5: Diaphragm material is Hastelloy C-276 or ASTM N10276. Other capsule wetted parts materials are SUSF316L, SUS316L
or ASTM grade 316L.
*6: Indicates diaphragm and other capsule wetted parts material.
*7: If necessary, specify Mounting bracket code C, D or K.
*8: If necessary, specify Mounting bracket code A, B or J.
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 01C21B01-00EN Jan. 27, 2016-00
<<Contents>> <<Index>> 5
*9: For Capsule code L when combined with Wetted parts material code H, M, T, A, D, and B, the maximum working pressure
is 3.5 MPa {35 kgf/cm2}.
*10: Not applicable for Output signal code F and G.
*11: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage
to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm
and the fill fluid can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium
hypochlorite, and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the
wetted parts material.
*12: Hastelloy C-276 or ASTM N10276.
*13: SUS316 or ASTM grade 316.
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 01C21B01-00EN Jan. 27, 2016-00
<<Contents>> <<Index>> 6
OPTIONAL SPECIFICATIONS (For Explosion Protected type “◊”)
For FOUNDATION Fieldbus explosion protected type, see GS 01C22T02-00EN.
For PROFIBUS PA explosion protected type, see GS 01C22T03-00EN.
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 01C21B01-00EN Jan. 27, 2016-00
<<Contents>> <<Index>> 7
Item Description Code
IECEx IECEx Intrinsically safe, type n and Flameproof Approval *3 *4 *5
Scheme Intrinsically safe and type n
Applicable Standard: IEC 60079-0:2004, IEC 60079-11:1999, IEC 60079-15:2005, IEC 60079-26:2005
Certificate: IECEx KEM 06.0007X
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP67
Amb. Temp.: –40 to 60°C (–40 to 140°F), Max. Process Temp.: 120°C (248°F)
Electrical Parameters: [Ex ia] Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 µH
[Ex nL] Ui=30 V, Ci=22.5 nF, Li=730 µH SU2
Flameproof
Applicable Standard: IEC 60079-0:2004, IEC60079-1:2003
Certificate: IECEx KEM 06.0005
Ex d IIC T6...T4 Enclosure: IP67
Max.Process Temp.: T4;120°C (248°F), T5;100°C (212°F), T6; 85°C (185°F)
Amb.Temp.: –40 to 75°C (–40 to 167°F) for T4, –40 to 80°C (–40 to 176°F) for T5,
–40 to 75°C (–40 to 167°F) for T6
*1: Applicable for Electrical connection code 2, 7 and C (1/2 NPT female).
*2: (Not used)
*3: Applicable for Output signal code D and E.
For intrinsically safe approval, use the safety barrier certified by the testing laboratories (BARD-400 is not applicable).
*4: Lower limit of ambient temperature is –15°C (5°F) when /HE is specified.
*5: Applicable for Electrical connection code 2, 4, 7, C and D (1/2 NPT and M20 female).
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 01C21B01-00EN Jan. 27, 2016-00
<<Contents>> <<Index>> 8
OPTIONAL SPECIFICATIONS
Item Description Code
Painting *10 Color change Amplifier cover only P
Amplifier cover and terminal cover, Munsell 7.5 R4/14 PR
Coating change Epoxy resin-baked coating *11 X1
316 SST exterior parts Exterior parts on the amplifier housing (name plates, tag plate, zero-adjustment screw,
HC
stopper screw) will become 316 SST *12
Fluoro-rubber O-ring All O-rings of amplifier housing. Lower limit of ambient temperature: −15°C (5°F) HE
Lightning protector Transmitter power supply voltage: 10.5 to 32 V DC ( 10.5 to 30 V DC for intrinsically safe type,
9 to 32 V DC for Fieldbus communication type.) A
Allowable current: Max. 6000 A ( 1×40 µs ), Repeating 1000 A ( 1×40 µs ) 100 times
Oil-prohibited use *6 Degrease cleansing treatment K1
Degrease cleansing treatment with fluorinated oilfilled capsule.
K2
Operating temperature −20 to 80°C
Oil-prohibited use with Degrease cleansing and dehydrating treatment K5
dehydrating treatment *6 Degrease cleansing and dehydrating treatment with fluorinated oilfilled capsule.
K6
Operating temperature −20 to 80°C
Calibration units *1 P calibration (psi unit) D1
bar calibration (bar unit) (See Table for Span and Range Limits.) D3
M calibration (kgf/cm2 unit) D4
Sealing treatment to SUS630 Sealant (liquid silicone rubber) is coated on JIS SUS630 cover flange mounting nuts against
Y
nuts stress corrosion cracking.
Long vent *2 Total length: 119 mm (standard: 34 mm); Total length when combining with Optional code K1,
U
K2, K5, and K6: 130 mm. Material: SUS316 or ASTM grade 316.
Fast response *7 Update time: 0.125 sec
Amplifier damping time constant: 0.1 to 64 sec in 9 increments
F1
Response time (with min. damping time constant): max. 0.5 sec
(for L capsule: max. 0.6 sec)
Failure alarm down-scale *3 Output status at CPU failure and hardware error is –5%, 3.2 mA or less. C1
NAMUR NE43 compliant *3 *9 Failure alarm down-scale: output status at CPU failure and
C2
Output signal limits: hardware error is –5%, 3.2 mA or less.
3.8 mA to 20.5 mA Failure alarm up-scale: output status at CPU failure and
C3
hardware error is 110%, 21.6 mA or more.
Stainless steel amplifier Amplifier housing material: SCS14A stainless steel
E1
housing *4 (equivalent to SUS316 cast stainless steel or ASTM CF-8M)
Gold-plate *5 Surface of isolating diaphragms are gold plated, effective for hydrogen permeation. A1
Configuration Custom software configuration R1
Body option *8
Right side high pressure, without drain and vent plugs N1
Terminal
side N1 and Process connection, based on DIN 19213 with 7/16 inch×20 unf female thread, on
N2
both sides of cover flange with blind kidney flanges on back
L H
F03E.ai N1, N2, and Mill certificate for cover flange, diaphragm, capsule body, and blind kidney flange N3
Wired tag plate Stainless steel tag plate wired onto transmitter N4
Data configuration at factory Description into “Descriptor” parameter of HART protocol
*13 CA
Mill Certificate Cover flange *14 M01
Cover flange, Process connector *15 M11
Pressure test/ Test Pressure: 3.5 MPa{35 kgf/cm2}*17 Nitrogen(N2) Gas*19 T01
Leak test Certificate *16 Test Pressure: 16 MPa{160 kgf/cm2}*18 Retention time: 10 minutes T12
*1: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by Option code D1,
D3, and D4.
*2: Applicable for vertical impulse piping type (Installation code 2, 3, 6, and 7) and Wetted parts material code S, H, M, and T.
*3: Applicable for Output signal code D and E. The hardware error indicates faulty amplifier or capsule.
When combining with Option code F1, output status for down-scale is –2.5%, 3.6 mA DC or less.
*4: Applicable for Electrical connection code 2, 3, 4, A, C, and D. Not applicable for Option code P and X1.
*5: Applicable for Wetted parts material code S.
*6: Applicable for Wetted parts material code S, H, M, and T.
*7: Applicable for Output signal code D and E. Write protection switch is attached for Output code E.
*8: Applicable for Wetted parts material code S, H, T, and M; Process connection code 3, 4, and 5; Installation code 9; and
Mounting bracket code N. Process connection faces on the other side of zero adjustment screw.
*9: Not applicable for Option code C1.
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 01C21B01-00EN Jan. 27, 2016-00
<<Contents>> <<Index>> 9
*10: Standard polyurethan painting can be used in acid atmosphere, whereas the epoxy resin-baked coating (Option code X1)
can be used in alkaline atmosphere. Anti-corrosion coating, the combination of polyurethan and epoxy resin-baked coating,
is available by special order as sea water, alkaline, and acid resistant.
*11: Not applicable for color change option.
*12: 316 or 316L SST. The specification is included in option code /E1.
*13: Applicable for Output signal code E.
*14: Applicable for Process connections code 0 and 5.
*15: Applicable for Process connections code 1, 2, 3, and 4.
*16: The unit on the certificate is always MPa regardless of selection of option code D1, D3, or D4.
*17: Applicable for Capsule code L when combined with Wetted parts material code H, M, T, A, D, and B.
*18: Applicable for Capsule code M, H, and V and Capsule code L when combined with Wetted parts material code S.
*19: Pure nitrogen gas is used for oil-prohibited use (Option code K1, K2, K5, and K6).
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 01C21B01-00EN Jan. 27, 2016-00
<<Contents>> <<Index>> 10
DIMENSIONS
Model EJA110A
Unit : mm (approx.inch)
Vertical Impulse Piping Type
Process connector upside (INSTALLATION CODE '6') (For CODE '2' or '3,' refer to the notes below.)
External indicator
259(10.20) conduit connection
197 (7.76) (Optional)
110 (4.33)
Process connections 97 146 (5.75) High 54 Low
(3.82) pressure (2.13)
pressure
Process side *1 side
connector
(Optional)
(2.83)
72
(1.81)
148 *3
46
(5.83)
(3.07)
ø78
234(9.21)
Terminal
side
(4.02)
102
Internal
indicator
(Optional)
Ground
terminal Conduit Vent/Drain plugs
( 2.09)
connection 9 *2
53
(0.35)
Zero adjustment 2-inch pipe
Mounting bracket Shrouding bolt *5 (O.D. 60.5 mm)
(L-type, Optional)
Vent/Drain plugs
234(9.21)
(4.02)
102
(2.83)
72
High Low
Process connections pressure pressure
side side
Horizontal Impulse Piping Type (INSTALLATION CODE '9') (For CODE '8', refer to the notes below.)
110 (4.33)
94 72 Conduit
connection 9 *2 Zero
(3.70) (2.83) (0.35) adjustment
Internal
indicator
(Optional)
(3.07)
Ground
146
162
(7.76)
terminal
197
High Low
pressure pressure
side *1 side
46 connections
124
(Optional)
47
Mounting bracket
2-inch pipe (O.D. 60.5mm) (Flat-type, Optional)
* 1: When Installation code 2, 3, or 8 is selected, high and low pressure side on above figure are reversed.
(i.e. High pressure side is on the right side.)
* 2: 15 mm(0.59 inch) for right side high pressure.(for code 2, 3 or 8)
* 3: When Optional code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.
* 4: When Optional code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value in the figure.
* 5: Applicable only for ATEX and IECEx Flameproof type. F04E.ai
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 01C21B01-00EN Jan. 27, 2016-00
<<Contents>> <<Index>> 11
SELECTION GUIDE
Measurement Span Maximum Working Pressure
Application Type Model Capsule
kPa inH2O MPa psi
L 0.5 to 10 2 to 40 16*4 2250*4
Traditional- M 1 to 100 4 to 400 16 2250
Differential Pressure EJA110A
Mounting*1 H 5 to 500 20 to 2000 16 2250
V 0.14 to 14 MPa 20 to 2000 psi 16 2250
L 1 to 10 4 to 40 3.5 500
Flow Integral Orifice EJA115 M 2 to 100 8 to 400 14 2000
H 20 to 210 80 to 830 14 2000
Differential Pressure EJA118N
Extended Flush M 2.5 to 100 10 to 400
& Liquid Level with EJA118W Based on Flange Rating
Combination H 25 to 500 100 to 2000
Remote Seals EJA118Y
Traditional-
Draft Range EJA120A E 0.1 to 1 0.4 to 4 50 kPa 7.25
Mounting*1
Differential Pressure Traditional- M 1 to 100 4 to 400 32 4500
EJA130A
& Liquid Level Mounting*1 H 5 to 500 20 to 2000 32 4500
Liquid Level, Closed EJA210A M 1 to 100 4 to 400
Flush Extended Based on Flange Rating
or Open Tank EJA220A H 5 to 500 20 to 2000
L 0.67 to 10*2 2.67 to 40*2 10 kPa*2 40 in H2O*2
Absolute (vacuum) Traditional-
EJA310A M 1.3 to 130*2 0.38 to 38 inHg*2 130 kPa*2 18.65*2
Pressure Mounting*1
A 0.03 to 3 MPa*2 4.3 to 430 psi*2 3000 kPa*2 430*2
Traditional- A 0.03 to 3 MPa 4.3 to 430 psi 3 430
Gauge Pressure EJA430A
Mounting*1 B 0.14 to 14 MPa 20 to 2000 psi 14 2000
Gauge Pressure with A 0.06 to 3 MPa 8.6 to 430 psi
Extended EJA438N Based on Flange Rating
Remote Seal B 0.46 to 7 MPa 66 to 1000 psi
Gauge Pressure with A 0.06 to 3 MPa 8.6 to 430 psi
Flush EJA438W Based on Flange Rating
Remote Seal B 0.46 to 14 MPa 66 to 2000 psi
Traditional- C 5 to 32 MPa 720 to 4500 psi 32 4500
High Gauge EJA440A
Mounting*1 D 5 to 50 MPa 720 to 7200 psi 50 7200
A 10 to 200 1.45 to 29 psi 200 kPa 29
Absolute & Gauge EJA510A B 0.1 to 2 MPa 14.5 to 290 psi 2 290
Direct-Mounting
Pressure*3 EJA530A C 0.5 to 10 MPa 72.5 to 1450 psi 10 1450
D 5 to 50 MPa 720 to 7200 psi 50 7200
*1: Traditional-mounting is 1/4 - 18 NPTF process connections ( 1/2 - 14 NPTF with process adapters ) on 2-1/8” centers.
*2: Measurement values in absolute.
*3: Measurement values in absolute for EJA510A.
*4: When combined with Wetted parts material code H, M, T, A, D, and B, the value is 3.5 MPa (500 psi).
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 01C21B01-00EN Jan. 27, 2016-00
<<Contents>> <<Index>> 12
< Ordering Information > “◊” < Related Instruments > “◊”
Specify the following when ordering Power Distributor: Refer to GS 01B04T01-02E or
1. Model, suffix codes, and optional codes GS 01B04T02-02E
2. Calibration range and units: BRAIN TERMINAL: Refer to GS 01C00A11-00E
1) Calibration range can be specified with range
value specifications up to 5 digits (excluding any < Reference >
decimal point) for low or high range limits within 1. Teflon; Trademark of E.I. DuPont de Nemours & Co.
the range of -32000 to 32000. 2. Hastelloy; Trademark of Haynes International Inc.
2) Specify only one unit from the table, ‘Settings 3. Monel; Trademark of Inco Alloys International, Inc.
when shipped.’ 4. HART; Trademark of the HART Communication
3. Select linear or square root for output mode and Foundation.
display mode. 5. FOUNDATION; Trademark of Fieldbus Foundation.
Note: If not specified, the instrument is shipped set for 6. PROFIBUS; Registered trademark of Profibus
linear mode. Nutzerorganisation e.v., Karlsruhe, Germany.
4. Select normal or reverse for operation mode
Note: If not specified, the instrument is shipped in Material Cross Reference Table
normal operation mode. SUS316L AISI 316L
5. Display scale and units (for transmitters equipped SUS316 AISI 316
with integral indicator only)
SUS304 AISI 304
Specify either 0 to 100 % or engineering unit scale
and ‘Range and Unit’ for engineering units scale: S25C AISI 1025
Scale range can be specified with range limit SCM435 AISI 4137
specifications up to 5 digits (excluding any decimal SUS630 ASTM630
point) for low or high range limits within the range of SCS14A ASTM CF-8M
-19999 to 19999.
6. Tag Number (if required) 7. Other company names and product names used
in this material are registered trademarks or
trademarks of their respective owners.
All Rights Reserved. Copyright © 1997, Yokogawa Electric Corporation GS 01C21B01-00EN Jan. 27, 2016-00
Subject to change without notice.