DC Motor Protection
DC Motor Protection
DC Motor Protection
The purpose of DC motor protection is Potential Motor Hazards and ing or cabling faults are related to power
to extend a motor’s lifespan by protect- Fault Conditions source-induced faults, they are catego-
ing it from conditions that can damage A review of motor hazards and com- rized as motor-induced faults.)
that the motor’s windings—both elec- mon fault conditions is useful in un- Load-induced faults (Ref. 2) are “the
trically and mechanically. Motor wind- derstanding the different approaches prolonged overloading as a result of the
ing damage can result from any of the taken to protect motors. These fault application of excessive mechanical
following conditions (Ref. 1): conditions are divided into the follow- load” (Ref. 3). Jamming (locked rotor)
• Mechanical damage ing categories (Ref. 2): is a common load-induced fault that
• Excessive moisture • Motor-induced faults causes an apparent overload or high in-
• High dielectric stress • Load-induced faults ertia (Wk2d). In pump applications, for
• High temperature • Environment-induced faults instance, oil that is cold or highly viscous
• Power source-induced faults may cause a fault; oil heaters are a pos-
While each of the above conditions • Application-induced faults sible solution to correct this fault condi-
can lead to winding damage, the appar- tion.
ent failure is “thermal degradation of Motor-induced faults (Ref. 2) are di- Environment-induced faults (Ref.
the insulation or burnouts. Insulation rectly related to the motor and its asso- 2) include high ambient tempera-
life is reduced by about half for each ciated wiring. Common motor-induced ture, cold/damp environment, high
10o C increase in winding temperature” faults include burnt out insulation, contaminant level and blocked ven-
(Ref. 1). To avoid thermal degradation bad bearings, loss-of-field and other tilation, among others. These condi-
of the insulation, there are a number of mechanical failures. Wiring problems, tions can increase the temperature of
methods, devices and circuits used to chafed or exposed wiring, cabling faults the windings by collecting moisture,
monitor potential motor hazards and or abraded insulation can cause “short degrading by corrosion or insulat-
fault conditions and to de-energize the circuits between power phases or be- ing the windings from contaminants.
motor when these conditions are met. tween a power phase and earth ground Loss of ventilation—especially at low
in the motor winding or its connec- speeds—also increases winding tem-
tions” (Ref. 3). (Note: Even though wir- perature.
Power source-induced faults (Ref. 2)
typically will cause high motor currents
that can thermally degrade the motor
windings from I2R heating. These fault
conditions are numerous and include
over-voltage; under-voltage; phase re-
versal; open phase failures (Ref. 3);
unbalances; ground-faults; power tran-
sients; harmonics; and loss-of-field.
Application induced-faults (Ref. 2)
are caused by operating conditions that
typically cause overcurrent or overload
conditions. These conditions include
high duty cycle; jogging; rapid plugging
(or plug reversing); over-speeding (Ref.
4); and synchronization problems.
Reprinted with permission from the Resources Section of Ohio Electric’s Internet Website: www.ohioelectricmotors.com.
open phasing are associated with AC type of motor protection and generally tact coil while the reverse coil will en-
motors, and are not addressed in this ar- is used with motor starters for revers- ergize through its NC auxiliary contact.
ticle. But it should be noted that if a DC ing and/or auxiliary control. There are
motor is powered by a DC converter, this three types of interlocks: Environmental Protection
controller protects the motor from these • Mechanical Environmental contamination can
conditions.) (Ref. 17) Under-voltage • Electrical adversely affect normal motor opera-
faults can cause either high motor cur- • Auxiliary contact tion. Dust, air particulates, explosive
rents or a failure to start. Hence, most vapors, water, humidity and high am-
under-voltage protection is part of the Mechanical interlocks will physically bient temperatures can all shorten the
motor starter. However, for prolonged prevent two motor contactors (forward lifespan of a motor. To protect a motor
under-voltage conditions, an inverse- and reverse) from closing simultane- from these environmental conditions,
time-under-voltage-relay can be used ously. “This interlock locks out one the National Electrical Manufacturers
to protect from this condition (Ref. 18). contactor at the beginning of the stroke Association (NEMA) and the Interna-
Rather than using discrete compo- of either contactor.” On the other hand, tional Electro-Technical Commission
nents to protect a DC motor from over- electrical interlocks use a push-button (IEC) have classified motor enclosures
voltages or surges, DC drives, isolation control or auxiliary contact to electri- based upon the level of protection they
transformers (Ref. 19) and power-con- cally isolate one contactor while en- provide (Ref. 26). The two major classi-
ditioning equipment (Ref. 20) are typi- ergizing the other contactor (Ref. 25). fications of motor enclosures are open
cally used to provide this type of protec- Auxiliary contact interlocking is a wir- and totally enclosed. Open motors are
tion. However, MOVs (Ref. 21), arrestors ing modification of push-button inter- further classified as drip-proof, splash-
(Ref. 22), harmonic filters (Ref. 23) and locking. There are two types of auxiliary proof, weather-protected, semi-guard-
power factor correction capacitors can contacts: normally closed (NC) and ed and guarded. Totally enclosed mo-
also provide overvoltage protection normally open (NO). For interlocking tors are classified as totally enclosed
(Ref. 23). protection in a reversing circuit, an NC non-ventilated, fan-cooled, explosion-
auxiliary contact is wired in series with proof, dust ignition-proof, air-to-water
Interlocks: Indirect Motor the opposing motor contactor coil. cooled and air-to-air cooled.
Protection Thus, when a motor is running in the
Interlocking is used to “prevent (mo- forward direction, the forward contact References
tor) contactors from being energized coil is energized through the NC aux- 1. Miller, Rex and Mark R. Miller. Industrial
simultaneously, or closing together iliary contact. When the reverse direc- Electricity and Motor Controls, McGraw-Hill,
2008, p. 384.
and causing a short-circuit (Ref. 24).” In tion is selected, the NC contact will
2. Blackburn, J. Lewis. Protective Relaying:
this respect, interlocking is an indirect open and de-energize the forward con- Principles and Applications, CRC Press, 1998,
p. 358.
3. Electricity Association Services, Ed. Power
System Protection: Application, Vol. 3, 2nd
Ed., Institution of Electrical Engineers, 1995,
p. 164.
4. Blackburn, J. Lewis. Protective Relaying:
Principles and Applications, CRC Press, 1998,
p. 357.
5. Herman, Stephen. Industrial Motor Control,
Cengage Learning, 2009, p. 35.
6. Whitman, William C., William M. Johnson
and John Tomczyk. Refrigeration & Air
Conditioning Technology, Cengage Learning,
2004, p. 365.
7. Marston, R.M. Passive and Discrete Circuits,
Newnes, 2000, p. 84.
Everything you
Principles and Applications, CRC Press, 1998,
p. 378.
and clutches.
Mode Power Supply Handbook, 3rd Ed.,
McGraw-Hill Prof Med/Tech, 2010, pp. 1–22.
22. Dixit, J.B. and Amit Yadav. Electrical Power
Quality, Laxmi Publications, Ltd., 2010, p. 72.
23. Dixit, J.B. and Amit Yadav. Electrical Power
Quality, Laxmi Publications, Ltd., 2010, p. 73.
24. Herman, S. Electric Motor Control, Cengage
Learning, 2009, p. 165.
25. Herman, S. Industrial Motor Control,
Cengage Learning, 2009, p. 215.
26. Beaty, H. Wayne and James L. Kirtley. Electric
Motor Handbook, McGraw-Hill Professional,
1998, p. 96. • Product and Industry News • Back Issues and Article
Updated Daily Archive
• Directory of Mechanical • Calendar of Upcoming
Power Transmission Events for power
Suppliers transmission professionals
• Exclusive online content in
our e-mail newsletters
www.
powertransmission.com
JUNE 2013 Power Transmission Engineering 51