This document explains how the DeltaV controller executes control modules by categorizing tasks into control and other tasks. Control modules have high, medium, and low priorities based on their configured scan rates, and the controller dynamically allocates CPU time between the different priority groups to ensure all modules execute while maintaining important other tasks like communications.

Uploaded by

samim_kh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
197 views

White Paper Deltav Control Module Execution en 56282

This document explains how the DeltaV controller executes control modules by categorizing tasks into control and other tasks. Control modules have high, medium, and low priorities based on their configured scan rates, and the controller dynamically allocates CPU time between the different priority groups to ensure all modules execute while maintaining important other tasks like communications.

Uploaded by

samim_kh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

DeltaV Distributed Control System White Paper

October 2016

DeltaV™ Control Module Execution

This document explains how the execution of control modules is managed in the DeltaV controller.
DeltaV Control Module Execution October 2016

Table of Contents
Introduction ..................................................................................................................................................................................... 3

Controller Task Categories ................................................................................................................................................................ 3

Module Priorities .............................................................................................................................................................................. 5

Controller Loading Recommendations ............................................................................................................................................. 6

www.emerson.com/deltav 2
DeltaV Control Module Execution October 2016

Introduction
The DeltaV controller is responsible for executing a variety of tasks. The most obvious one is the execution of the configured control
modules. However, the controller performs several other tasks, such as I/O processing, communications, and diagnostics.

All of the above tasks have to be serviced within a certain time for the controller to function optimally. A scheduler is responsible for
controlling the execution of the modules in the controller. The controller has a finite amount of resources (CPU time and memory)
to execute its tasks. This document explains how the execution of control modules is managed.

Controller Task Categories


The breakdown of all the tasks in the DeltaV controller is beyond the scope of this document. However, it is useful to generalize the
tasks into two major categories to develop an understanding of the relative priority of those categories. The two main categories
are CONTROL tasks and OTHER tasks. The main tasks in the OTHER category are redundancy management, communications,
and self-test. (See Fig.1 for the relative priority of these tasks.) There is no difference in the way the scheduler works on an MD/
MDPlus compared to an M5Plus controller. The MD has a faster CPU and a floating point co-processor. This allows it to execute more
instructions (especially floating point) per second.

If the controller is normally loaded, then all these tasks can be serviced effectively, and the priority of the tasks is not called into play.
However, it is possible to overload the controller by requiring it to perform too much configuration and communication processing.
When the controller is overloaded, lower priority tasks are paused until higher priority ones can be completed. Typically there are
two ways that a controller can be overloaded :

„„The maximum amount of CONTROLtime has been reached.


There is a fixed maximum amount of CPU time that is allocated to run the control modules. This is known as CONTROLtime.
When there is no configuration in the controller, actual CONTROLtime is 0% and the diagnostic attribute FreTim (Free Time)
reads 100%. If the configuration loaded in the controller needs to use more than the allotted CONTROLtime, the execution of
one or more modules will be slower than the configured scan rate. This condition is called ‘Slippage’.

„„Too much communications processing


If the configuration does not consume all of the CONTROLtime then there is (100% – actual CONTROLtime) left for the OTHER
operations. If the execution of the OTHER tasks requires more than (100% - actual CONTROLtime), controller operations
will systematically degrade by making lower priority operations in the controller wait until a higher priority operation has
completed. In very severe overload situations, some tasks in the controller will suspend indefinitely until the controller has been
re-configured to reduce load.

www.emerson.com/deltav 3
DeltaV Control Module Execution October 2016

Figure 1 – Relative controller task priorities.

Controller-to-controller communications are conducted via request/response messages. Most controller-to-workstation


communications (reporting of data) are conducted using unsolicited messages. Processing of request/response messages is a
higher priority task than unsolicited messages. This means that, in general, controller-to-controller communications is not affected
by controller-to-workstation communications.

In the common overload scenario, module execution will slip and the slippage indicators will indicate which priority modules are
slipping. In this overload scenario, the scheduler is still able to police module execution.

However, in certain overload conditions, the execution of Medium and Low priority control modules sometimes has to time-slice
with communications tasks. This is normally caused by a misbehaving configuration that makes the scheduler lose its ability to
fully police the execution of modules. This typically occurs when a module takes longer than 50ms to execute. This can happen if
there are too many heavy function blocks (such as calc-logic) in one module. In this case, the scheduler is inhibited from being able
to enforce the CONTROLtime limit for module execution. Since it is important that communications can still happen during this
condition, operating system time slicing allows the communications tasks to get some share of the processor, despite the mis-
behaving control module that is trying to hog CPU time. It is important to ensure that the communications with the controller are
still alive in this situation because the fault can be rectified with a download of a more suitable configuration.

I/O scanning happens in an interrupt service routine and is therefore not subject to task priorities. As far as controller loading is
concerned, the time spent scanning I/O is negligible compared with the major task categories. Most of the I/O processing occurs in
the context of control, for example when an I/O function block is executed.

If the controller does not have enough time to execute all tasks, then the major pieces of functionality to degrade will be certain
lower priority communication tasks and Low Priority Control. The initial degree of degradation causes the reporting of data to the
workstations to be sluggish. For Low Priority Control, modules will not execute on time. In an extreme case, data is not reported to
the workstation at all and Low Priority modules do not execute.

www.emerson.com/deltav 4
DeltaV Control Module Execution October 2016

Module Priorities
There are three module priorities : High, Medium, and Low. The prioritiy of a module is determined by its configured scan rate.

Scan Rate (seconds) High Priority Medium Priority Low Priority


0.1 
0.2 
0.5 
1 
2 
5 
10 
30 
60 

Figure 2 – Module priority.

The allocation of the available CPU time to the three priority groups is dynamic, within certain bounds. High priority control is not
allowed to take the entire amount of CONTROLtime. High priority modules will start slipping if total high priority control exceeds
the limit (45% of CONTROLtime) set for High priority control. This guarantees that there is some time for medium and low priority
modules to execute. Hence, it is possible to see slippage of High priority modules even when there is some overall free time in
the controller. If the modules cannot complete in the time allotted, there will be slippage. When this happens one or more of the
diagnostic attributes HPCTONTIME, MPCTONTIME, LPCTONTIME will read less than 100%. Assuming that there is some free time, all
modules will eventually execute.

The controller automatically adjusts the priority of a module when it is placed in the debug state. In v5.x, High and Medium priority
modules run at Medium priority and Low priority modules run at Low priority. In v4.2 all debug sessions run at Medium Priority.

The limits for CONTROLtime and OTHER activities in the controller are release dependent and may be changed to make optimum
use of the controller resources.

www.emerson.com/deltav 5
DeltaV Control Module Execution October 2016

Controller Loading Recommendations


„„The function block scan rate multiplier should be used to make some function blocks run slower than the configured module
scan rate if these blocks do not have to execute on every scan of the module.

„„Use the lowest practical scan rate for modules. Many process applications only need a 1 sec scan time. Level loops are often
very much slower. Temperature loops may be slow too.

„„Pay attention to the function block execution order since this will affect the actual response time of a module to a change
in the input.

„„Be aware of the relative scan rates of interacting modules to achieve the optimum response time. The execution order of
modules cannot be configured and no particular order should be assumed.

„„Use CALC blocks sparingly because the processing of structured text (expressions) creates a higher loading than an equivalent
function block would.

„„Verify, via Diagnostics, that there are no unresolved references in the configuration. Unresolved references will create
unnecessary burst loads because the controller will periodically try to resolve them.

„„In some instances the ‘Comparator’ function block may be substituted for a ‘Calc’ / ‘Condition’ block . The ‘Comparator’ block
has less flexibility than the condition block but it is more efficient.

„„It is recommended that a minimum of 10-20% free time be maintained.

„„Do not create modules with lots of function blocks, especially CALC blocks.

„„In typical configurations, redundancy management consumes (5-15%) of the CPU, depending on the amount of data that has
to be transferred to the standby controller. Keep this in mind when planning the configuration.

„„Use the latest Load Estimator utility to plan the configuration

Emerson
North America, Latin America: ©2016, Emerson Process Management. All rights reserved.
+1 800 833 8314 or
The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is a
+1 512 832 3774
mark of one of the Emerson Process Management family of companies. All other marks are the
property of their respective owners.
Asia Pacific:
65 6777 8211 The contents of this publication are presented for informational purposes only, and while every
effort has been made to ensure their accuracy, they are not to be construed as warranties or
Europe, Middle East: guarantees, express or implied, regarding the products or services described herein or their
+41 41 768 6111 use or applicability. All sales are governed by our terms and conditions, which are available on
request. We reserve the right to modify or improve the designs or specifications of our products
www.emerson.com/deltav at any time without notice.