DeltaV Distributed Control System Product Data Sheet
January 2018
DeltaV SQ Controller
Scalable controllers
Quick assembly
Easy-to-use
Field proven architecture
Designed for Electronic Marshalling
Advanced controls
The DeltaV SQ controller and the DeltaV™ I/O subsystem make rapid
installation easy.
Introduction Benefits
The DeltaV™ SQ controllers provides communication and Scalable controllers. The SQ controller complements the
control functions and integrate field devices and the other SX controller by providing a smaller controller platform at a
nodes on the control network. The SX and SQ controllers reduced price for those small to moderate applications:
provide a choice to match the controller capacity to the
Speed. The SQ controller supports all the features you’ve
requirements of the process. They also provide new ease of use
come to expect from the DeltaV system: self-addressing,
features that eliminate mounting screws and accelerate cabinet
automatic I/O detection. All these features are designed to
assembly.
make your projects execute faster—just plug and play!
Control strategies and system configurations created on
Redundant architecture. The SQ controller supports
earlier DeltaV systems can be used with this controller. The
1:1 redundancy for increased availability. Redundant SQ
SQ controller provides all the features and functions of the
controllers can be upgraded to SX controllers online—robust!
M-series controllers with the added support for CHARM
based Electronic Marshalling. Late changes. You can easily upgrade an SQ controller to
an SX to handle project scope changes late in the project.
The control languages executed in the controllers are
Simply replace the SQ with the SX and all existing
described in the control software product data sheet.
configuration, documentation and hardware design
remain the same —forgiving.
DeltaV SQ Controller January 2018
Quick assembly. The S-series hardware has been designed for
speed of project execution. Carriers snap to standard DIN rails
and controllers and S-series I/O snap into position without the
use of retaining screws.
Easy to use. Controllers are also easy to configure. Simply
connect the SQ to the DeltaV network and Auto-Sense it from
DeltaV Explorer. Add the controller and all its I/O interfaces to
the system database and all components are automatically
addressed and communicating. There are no dip switches
or jumpers to set.
Control strategies are developed using IEC-61131
programming techniques: Function Blocks, Sequential
Function Charts and Structured Text.
Automatic diagnostic and event reporting with time stamps
applied in the controller.
Set control execution to match process dynamics and
controller scheduling adjusts automatically.
Reference any parameter by its module name, regardless
of its location in the system. The SQ controller.
Synchronized system clock for consistent time based event
driven actions across the system. Advanced controls. The SQ controller supports all the
advanced control features that are expected in a world class
Online expandable I/O carriers allow new cards to be added Distributed Control System:
online, with autosense capability, for modular system growth.
Batch Software
Hardware redundancy is automatically detected with zero
configuration effort. Model Predictive Control
Field proven architecture. The SQ controller is an evolution Neural Networks
of the DeltaV MQ controller. The new design delivers
installation and robustness enhancement while still using the Product Description
same processor and OS that has proven itself in the field. All
S-series I/O cards run the latest software enhancements of The SQ controller executes control logic based on the
corresponding M-series I/O cards and deliver the same field process signals derived from the I/O subsystem and provides
proven, reliable operation. communication to the rest of the DeltaV control system for
operator interaction and data collection.
Designed for Electronic Marshalling. The SQ controller
have highly distributable I/O capabilities with CHARMs based Each controller node can be installed as a simplex or redundant
Electronic Marshalling. Electronic Marshalling I/O can be node. Redundancy is provided by adding a second controller
mounted anywhere, facilitating system design and expansion and power supply mounted adjacent to the primary controller.
while reducing overall system footprint over traditional The controllers are connected to the I/O carriers, which are
marshalled I/O Subsystems. mounted to the right of the controller carriers. Up to 8 carriers
with 8 cards each can be connected to the local bus I/O, for a
total of 64 traditional I/O cards. In addition to the 8 local I/O
carriers, each controller can communicate with an additional
16 Remote I/O units hosting traditional card based I/O.
[Link]/deltav 2
DeltaV SQ Controller January 2018
In addition to traditional I/O cards, the local bus supports The WirelessHART I/O card (WIOC) provides redundant
fieldbus technologies, including Foundation fieldbus, Profibus DP, communication for up to 100 WirelessHART devices, providing
DeviceNet and AS-I protocols. The I/O subsystem also supports high availability and reliability of wireless data. Up to 16
Serial interface cards as well as the Ethernet I/O interface. These WirelessHART I/O cards can communicate to one controller,
various I/O products provide a wide range of interfaces to meet each providing up to 100 signals.
the needs of your control application.
Control modules are automatically scheduled by the controller,
The SQ controller also supports CHARMs and WirelessHART I/O based on their assigned scan rates. This allows each control
cards. The CHARM I/O Card (CIOC) connects via the redundant function to be optimized based on the process dynamics.
Ethernet ports of the controller to provide a highly distributed Modules scan times can be set as fast as 100 ms, and as slow
and flexible I/O solution called Electronic Marshalling. Up to 16 as 60 seconds. The number of control modules that can be
CIOC’s can communicate to one controller, each providing up to assigned to a controller depends on the complexity and scan
96 individually configurable signal types. rate of each module, and the available CPU and memory. The
SQ controller should be used for small to medium applications
The capacity limits of the SQ controller may vary depending on
with a maximum of 750 individual I/O signals.
the particular application, amount of CHARM I/O Signals and
as well control performance requirements. Enhanced memory The SQ controller is designed for harsh environments and
handling and hardware alerts covering capacity and memory, is rated for G3 corrosive environments, with an operating
via indexes, got added to the diagnostic information’s of the temperature range from -40 to 70°C. It is ideally suited for
SQ controller. remote installation, close to the process equipment. For more
traditional installations with central marshalling cabinets,
CHARM I/O Cards can be mounted in standard I/O cabinets
providing Electronic Marshalling. CHARM I/O Cards can also
be used for highly distributed I/O applications.
DeltaV SQ controller hardware dimensions.
[Link]/deltav 3
DeltaV SQ Controller January 2018
Hardware Specifications
Specifications for the SQ Controller
DST Limit 750
SCADA Tags 3200
Max Data Values Sent 2000/second
Max Data Values Received 250/second
Max Unsolicited Client Nodes 64
Module Execution Rates 100ms, 200ms, 500ms, 1s, 2s, 5s, 10s, 30s, 60s
User Memory 48 MB
Fuse Protection (Internal) 3.0 A, non-replaceable fuses
Power Dissipation 5.0 W typical, 7.0 W maximum
Environmental Specifications
Operating Temperature* -40° to 70°C (-40° to 158°F)
Storage Temperature -40° to 85°C (-40° to 185°F)
Relative Humidity 5 to 95%, non-condensing
Protection Rating IP 20
ISA-S71.04-1985 Airborne Contaminants Class G3
Airborne Contaminants
Conformal coating
Shock (Normal Operating Conditions) 10 g ½-sine wave for 11 ms
Vibration (Operative Limit) 1 mm peak-to-peak from 5 Hz to 13.2 Hz, 0.7 g from 13.2 Hz
to 150 Hz
LED Indicators
Green – Power Indicates DC power is applied.
Red – Error Indicates an error condition.
Indicates that the controller is operating as the
Green – Active
primary controller.
Green – Standby Indicates that the controller is operating as a backup controller.
Yellow flashing – Pri. CN Indicates valid primary control network communication.
Yellow, flashing – Sec. CN Indicates valid secondary control network communication.
External Connections
Primary Control Network 8-pin RJ-45 connector
Secondary Control Network 8-pin RJ-45 connector
*Operating any electronics at the higher end of its temperature range for long periods of time will shorten its expected lifetime,
see Effects of Heat and Airflow Inside an Enclosure White Paper for more information.
[Link]/deltav 4
DeltaV SQ Controller January 2018
Certifications Hazardous Area/Locations
The following certifications are available on the DeltaV
SQ controller. The DeltaV SQ controller can be installed and used based on the
following Standards:
CE:
FM (USA):
EMC- EN 61326-1
Class I, Division 2, Groups A, B, C, D, T4
FM:
cFM (Canada):
FM 3600
Class I, Division 2, Groups A, B, C, D, T4
FM 3611
ATEX:
CSA:
II 3 G Ex nA IIC Gc
CSA C22.2 No. 213-M1987
IEC Ex:
CSA C22.2 No. 1010-1
Ex nA IIC T4 Gc
ATEX:
Regarding the installation instructions please refer to the following documents:
ATEX 94/9/EC Class 1 Division 2 Installation Instructions DeltaV S-Series (12P5402)
Zone 2 Installation Instructions DeltaV S-series (12P5404)
EN 60079-0
EN 60079-15
IEC Ex:
IEC60079-0
IEC60079-15
Marine Certifications: IACS E10
ABS Certificate of Design Assessment
DNV-GL Type Approval Certificate
Wurldtech:
Achilles Communications Certification Level 1 (v12.3)
Achilles Communications Certification Level 2 (v13.3.1
& v14.3)
[Link]/deltav 5
DeltaV SQ Controller January 2018
Ordering Information
Description Model Number
SQ controller SE3008
Prerequisites
For each controller you will need a Power/controller carrier. The SQ controller requires v12.3 or later DeltaV software.
Please refer to the S-series I/O Carrier product data sheet
The SQ controller can be used on a v11.3.1 System by
for details.
applying an HotFix to the DeltaV system.
Each controller requires a dedicated system power supply.
Please refer to the S-series Power Supplies product data
sheet for details.
Emerson
North America, Latin America: ©2018, Emerson. All rights reserved.
+1 800 833 8314 or
The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is
+1 512 832 3774
a mark of one of the Emerson family of companies. All other marks are the property of their
respective owners.
Asia Pacific:
+65 6777 8211 The contents of this publication are presented for informational purposes only, and while every
effort has been made to ensure their accuracy, they are not to be construed as warranties or
Europe, Middle East: guarantees, express or implied, regarding the products or services described herein or their
+41 41 768 6111 use or applicability. All sales are governed by our terms and conditions, which are available on
request. We reserve the right to modify or improve the designs or specifications of our products
[Link]/deltav at any time without notice.