WKR Rooftop is ideal for water-deficient area as it does not work with cooling tower and
cooling pump. It could be installed on the roof of the building or on outside area as it does not
have to be installed in a specialized machine room. It is widely used in places which requires
centralized air supply for a large area, such as exhibition halls, gymnasiums, cinemas, shopping
high-efficiency scroll compressor, low-noise axial fan motor, high-accuracy electronic expansion
2. NOMENCLATURE
WK R _ /Na A -M
1 2 3 4 5 6
3.2 Appearance
Note:Picture is for reference and is subject to change without prior notification.
4. Product Data
Integral type
Model WKR105/NaA WKR115/NaA WKR140/NaA WKR180/NaA WKR190/NaA
Cooling capacity KW 105 115 140 180 190
Cooling power kw 41.5 45 52.5 72 78
Air flow m3/h 16700 23000 25200 31000 320000
Characteristics ESP Pa 480 480 480 480 480
Set temperature range 16~30℃
Power supply 380V 3N ~ 50Hz
Refrigerant R410A
backward-curved &
Blow Fan type Forward-curved & multi-blade centrifugal fan
single-plate centrifugal fan
Fan system
Blow Fan power kw 11 15 15 15 15
Fan type Low noise axial type
High & Low pressure switch, anti-frozen switch, Over-current protection
Safety Device
switch, Phase protection, Overload protection
Compressor type High efficiency scroll
Cooling system
Compressor No. 2 2 2 2 2
Evaporator type High efficiency fins and coils
Condensor type High efficiency fins and coils
Water coils connection pipe diameter DN32 DN32 DN32 DN32 DN32
W mm 4630 4630 4630 5330 5330
Outline
D mm 2050 2050 2050 2250 2250
Dimension
H mm 2310 2310 2310 2610 2610
Noise level dB(A) 71 71 72 75 75
Net weight kg 2360 2440 2630 3380 3480
Gross weight kg 2380 2460 2650 3400 3500
Split Type
Model WKR210/NaA WKR250/NaA WKR280/NaA WKR370/NaA
Cooling capacity kw 210 250 280 370
Cooling power kw 78 82.5 94.5 120
Air flow m3/h 34000 34000 40000 50000
Characteristics ESP Pa 280 280 430 430
Set temperature range 16~30℃
Power supply 380V 3N ~ 50Hz
Refrigerant R410A
Blow Fan type Blow Fan type
Fan system Blow Fan power kw 13 15 18.5 22
Fan type Fan type
High & Low pressure switch, anti-frozen switch, Over-current protection switch,
Safety Device Phase protection, Overload protection
Note:
② Rated conditions
27℃DB/19℃WB;
5 Working conditions
Indoor Air side Outdoor Air side
Item
Ambient DB temp.(℃) Ambient DB temp.(℃)
Note Please contact the sales manager if the working conditions exceed the data above.
6 Performance corrections
105
105
Cooling capacity(%)
30(22)
100
28(20)
95
27(19)
90
25(18)
85
23(16)
23 25 27 29 31 33 35 37 39 41 43
20
110
24
100
90
80
70
-5 0 5 10 15
ODU Air-inlet DB Temp.(℃)
7 AIRFLOW-ESP CORRECTIONS
8 ELECTRICAL DATA
8.1 POWER DIAGRAM
Note that the installer could refer to the power diagram stick to the unit’s control panel.