MU250 3-Phase Voltage Relay User's Guide: 7. Technical Data Brief Overview
MU250 3-Phase Voltage Relay User's Guide: 7. Technical Data Brief Overview
Technical Data
MU250 3-Phase Voltage Relay User's Guide
Brief Overview The Data LED showing value. Press “UP” or
Setting Ranges
Undervoltage : 1% – 25% “DOWN” to scroll through the parameters as
Time delay for undervoltage : 0.1s – 30s shown in Figure 2 and 3 (depends on L-L or L-N
Overvoltage : 1% – 20% h a setting).
Time delay for overvoltage : 0.1s – 30s g
Unbalance : 5% – 20%
Time delay for unbalance : 0.1s – 30s
b
Phase loss : Fixed time <0.1s
Phase sequence : Fixed time <0.1s U 12
Start time delay : 0s – 999s
c
f d
Power Supply Input
Phase to phase voltage : 380V(-25%) - 415V(+20%) AC e U 23
Supply frequency : 45Hz to 65Hz
Maximum power consumption : 3VA Figure 1: Front panel overview
Contacts
Contact arrangement : Change-over U 31
Contact rating : 5A, 250V AC (cos j=1)
Contact material : Silver alloy
Operating time : 15 ms max.
Expected electrical life : 100,000 operations at rated current
6
Expected mechanical life : 5 x 10 operations Frequency
Mechanical
Mounting : Din rail mounted
Approximate weight : 0.31kg U 1N
Accuracy
Protection thresholds : ±3%
Time delay : 0-0.5s, ± 15% with a minimum of 40ms
: 0.6s and above, ± 3% 1. General Description
U 2N
Measurements : ± 3%
MU250 is a voltage relay that combines overvoltage,
undervoltage, unbalance, phase loss, phase sequence
and delay start functions. It can be connected with or
without neutral wire.
U 3N
8. Case Dimensions MU250 incorporates a 4-digit LED display which
allows direct numerical readout of set values, actual
measured value and system indication.
71 mm 70 mm
MU250 has 2 relay outputs (R1 and R2). R1 is On Frequency
20 mm under normal operating condition. R2 can be
programmed to on during trip state or during pickup Figure 3: Display for L-N setting. 240V and
and trip state. 50.0Hz shown as example
85 mm
45 mm
Front Side
2. Voltage and Frequency Display a) Auto Scroll
20 mm Auto scroll let the display to scroll to the next
During power up, when the relay is not under tripped
condition, the display will show voltage and frequency available parameter every 10 seconds. To toggle
30 mm 20 mm 20 mm auto scroll mode, press "UP" and "DOWN"
reading. The Function LED indicates which line/phase
Figure 6: Case Dimensions simultaneously.
of voltage is being displayed or shows 'F' when
frequency is being displayed.
4 1
3. Settings c) Undervoltage b) Trip Reset
a) Setting Display Undervoltage pickup occurs when any line to line or During trip condition, press “RESET/MODE” to reset
Voltage/Frequency Display line to neutral voltage is less than [nominal voltage - the relay, the relay will reset if condition permits. If
When the relay is not under tripped condition, U<< %], relay trips when delay time is elapsed. relay is set to Auto reset, the relay will reset
pressing “RESET/MODE” will scroll through various automatically if the condition is 5% below trip
Trip History
settings. Function LED showing number or alphabet to d) Overvoltage condition.
indicate which setting is being view as shown in
1 U<< Undervoltage % Undervoltage pickup occurs when any line to line or c) Trip Test
Figure 4. Table 1 gives description of each setting.
line to neutral voltage is more than [nominal voltage +
Tip: To quickly jump back to voltage display during 2 t << Undervoltage time delay U>> %], relay trips when delay time is elapsed. Press “TEST” button to simulate a trip condition.
setting display, press and hold “RESET/MODE” for “tESt” will blink, R1 off and R2 on. Press
more than 1.5 seconds. e) Unbalance “RESET/MODE” to reset.
3 U>> Overvoltage %
b Phase Phase Sequence trip occurs when the phase To disable tripping due to incorrect setting, press
Step 3: Press “UP” or “DOWN” to select the desired “RESET/MODE” and “TEST” simultaneously during
sequence in any 2 or all of the lines are reversed. No
value. power up. The Trip LED slow blink to indicate Trip
additional delay for phase sequence detection.
c Nominal voltage Bypass Mode. Go into programming mode to correct
Step 4: To save the selected value, press “UP” and the setting. Power off and on to reset the relay.
Phase Loss trip occurs when any voltage is less than
“DOWN” simultaneously again. It will exit the d Relay R2 70% of nominal. No additional delay for phase loss
programming mode with the Data LED displaying the
detection.
newly set value.
E Auto/Manual reset 5. Output Contacts
To exit programming mode without saving the selected f) Starting Delay
setting, press “RESET/MODE” once. MU250 has 2 relay outputs (R1 and R2). R1 is On
Starting delay is the delay time for R1 to turn on during under normal condition. R2 can be programmed to
power up under normal condition. on during trip state or during both pickup and trip
state.
4. Trip
Setting Function Setting Range Description 6. Typical Application Diagram
1 U<< Undervoltage 1-25 % Undervoltage % from nominal voltage a) Trip Display
L1
2 t<< Undervoltage delay 0.1-30 s Time delay for undervoltage L2
3 U>> Overvoltage 1-20 % Overvoltage % from nominal voltage During pickup, Trip/Pickup LED blinks, Relay R2 on if L3
it is set to 1-Pickup. During trip condition, Trip/Pickup N
4 t>> Overvoltage delay 0.1-30 s Time delay for overvoltage LED on. Function LED and Data LED blinks with trip (OPTIONAL)
d Relay R2 0=Trip, 1=Pickup Trip: R2 on during trip 5 PS Phase sequence trip Neutral connection is optional when Phase
Pickup: R2 on during pickup and trip t EST Test option is set to L-L. Neutral connection is
E Auto/Manual resetting 0=auto, 1=manual auto: auto reset when trip condition clear required when Phase option is set to L-N. (refer
manual: press “RESET/MODE” to reset Table 2: Trip display to Setting b - Phase)
2 3