Tender Drawings PDF

The document contains sample design drawings for reference by bidders for a new substation tender. It lists 14 types of drawings provided, including layouts, single line diagrams, architectural plans for the control room building, foundations, fencing, and other structural elements. The successful bidder will have to prepare actual design and drawings according to site conditions for approval before starting construction work.

Uploaded by

Anfal Barbhuiya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
447 views

Tender Drawings PDF

The document contains sample design drawings for reference by bidders for a new substation tender. It lists 14 types of drawings provided, including layouts, single line diagrams, architectural plans for the control room building, foundations, fencing, and other structural elements. The successful bidder will have to prepare actual design and drawings according to site conditions for approval before starting construction work.

Uploaded by

Anfal Barbhuiya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 22

Volume-IV/ Tender Drawings

VOLUME-IV

TENDER DRAWINGS

(This section of the Tender Document covers sample Design Drawings for reference of the Bidder.
However, the Successful bidder shall have to prepare design and drawing as per actual site
conditions and to take approval of the employer prior to start of the works)

Tender Document for APDCL/DSELR/SIB/01 Procurement of Plant Page | 1


Volume-IV/ Tender Drawings

Sl No List of Available Drawings

1 Typical Layout for New Sub-Station


2 Typical Section for New Sub-Station
3 Typical Single Line Diagram (SLD) for New Sub-Station
Drawings Related to Control Room Building
i) Architectural View and layout (Floor Plan, Front Elevation, Side
Elevation, Sajjah, Schedule and Sectional elevation Layout)
ii) Lay out Plan and details of Columns and Footings

4 iii) Layout Plan and Details of Pile Cap and Pile Shaft
iv) Layout plan for Tie Beams Plinth wall and Reinforcement details of Tie
beam
v) Layout Plan, Sectional elevation of Cable Trench and Doors and Window
Schedule
vi) Details of Roof Truss and Gabble wall
vii) Details of Septic tank and Soak Pit
5 Design and Drawing of Boundary Wall
6 Design and Drawing of RRM Boundary Wall
7 Design of Section of Switchyard Cable Trench (For New Sub-station and Terminal Bay at
DSS)
8 Design of Section of Switchyard Cable Trench (C & D Type for Terminal Bay at GSS)
9 Standard Paver Block Road
10 Design of Switchyard Gate
11 Design of Chain Linked Fencing
12 Sketch Plan of Typical Under Ground Railway Track Crossing
13 Typical Power Transformer Foundation
14 Typical Fire Protection Wall between Power Transformer

Tender Document for APDCL/DSELR/SIB/01 Procurement of Plant Page | 2


1839
250
125mm WIDE AND 125mm
DEEP G.I. SHEET GUTTERS

SOFFIT OF FALSE CEILING

4008

3600
3600
3600

3410

3100
35mm THICK FLOOR FINISH
25mm THICK DPC
65mm THICK PCC
251

75mm THICK FBS 190


190 15mm THICK WATER PROOF

1050
1050

WALL PLASTER
134
25mm THICK DPC
50mm THICK PCC
75mm THICK FBS
2400 27
°
50mm THICK AND 750mm
WIDE APRON ALL AROUND
THE PERIPHERY

SIDE ELEVATION 1 SECTIONAL ELEVATION AT A-A


SIDE ELEVATION 2

4000 4000 2615 2385

C1 C1 C3

W W W1

BATTERY ROOM SOAK


PIT 125mm WIDE AND 125mm
1960 X 2195
DEEP G.I. SHEET GUTTERS

BATT. W2
D2

BC
1 2 3 4 5 6 7 8 9 10 110 mm dia P.V.C pipes for the 110 mm dia P.V.C pipes for the
purpose of carrying Rain water purpose of carrying Rain water
RAMP C2 from rain gutters to the nearest from rain gutters to the nearest
SEPTIC TANK

2400
5000
5000
RS run-off drain run-off drain
C4
2000 X 2500
11 KV SWITCHGEAR PANEL

STORE ROOM
2700 X 2195

W2
3
CONTROL ROOM
79.63 sqm
D2

33 KV CRP
1695 WIDE PASSAGE 3500
1 D2

C1

3800
W D3

RTCC RTCC

5000
ACDB DCDB BC
TOILET
1 2 3025 X 1650 1
W2
D1
W ACDB

I/C ROOM WINDOW SEGMENT


VERANDAH
D2 3010 X 3025

1250
8000 X 1320 D3 CHAJJAH LENGTH (mm) WIDTH (mm) THICKNESS (mm) REINFORCEMENT
W 2
C1 2600 450 75 8Ø torr steel @ 140 mm c/c both ways

C1

RAMP
C2 2800 600 75 8Ø torr steel @ 140 mm c/c both ways
A
DESIGNATION OUTER DIA (mm) THICKNESS (mm) UNIT WEIGHT (kg/m)
C1 C3 1600 450 8Ø torr steel @ 140 mm c/c both ways
75
1 40 NB MEDIUM 76.1 3.6 6.42
C4 7815 600 75 8Ø torr steel @ 140 mm c/c both ways DRAWING ISSUED FOR TENDER PURPOSE ONLY
2 20 NB MEDIUM 60.3 3.6 5.03

1200 2000

DRAWING TITLE
FLOOR PLAN
FLOOR PLAN, FRONT ELEVATION, SIDE ELEVATION,
CHAJJAH SCHEDULE AND SECTIONAL ELEVATION
LAY-OUT
4000 4000 2615 2385

4000 4000 5000

1 2 3 4 1 3 4
2

FOOTING SIZE EDGE DEPTH TOTAL DEPTH


FOOTING NO FOOTING SLAB REINFORCEMENT
L mm x B mm d mm D mm
8-10 mm tor @ 143 c/c along length, bottom layer
5 and 9 1100 x 1550 200 400 10-8 mm tor @ 160 c/c along width, top layer

1, 2, 3, 4, 11, 12, 7-10 mm tor @ 133 c/c along length, bottom layer
5000

5000

5000

5000
900 x 1400 200 400
16 and 17 9- 8 mm tor @ 162 c/c along width, top layer

14 and 15 800 x 800 150 350 6-8 mm tor @ 140 c/c bothways

9
100

8
100

5 6 7 5 6 7 9

6 and 7 900 x 900 150 350 7-8 mm tor @ 133 c/c bothways

10050
2615 2385
1845

10
3800

3800
5000

5000
1905

11 12 13 12
11
50

FOOTING SIZE EDGE DEPTH TOTAL DEPTH


1250

1250

14 15 16 17 16 17 FOOTING NO FOOTING SLAB REINFORCEMENT


14 15 L mm x B mm d mm D mm
50

10-10 mm tor @ 144 c/c along length, bottom layer


4000 4000 5000
5 and 9 1800 x 1400 200 400 12-8 mm tor @ 154 c/c along width, top layer
LAY-OUT OF TIE BEAMS (SECOND GROUP) TO BE EXECUTED ONLY AT LOCATIONS 9-10 mm tor @ 143 c/c along length, bottom layer
1, 2, 3, 4, 11, 12,
WHERE HEIGHT OF EARTH FILLING AT SITE IS GREATER THAN 900mm 1250 x 1500 200 400
16 and 17 10- 8 mm tor @ 140 c/c along width, top layer
LAY-OUT PLAN OF COLUMNS
14 and 15 900 x 900 150 350 7-8 mm tor @ 150 c/c bothways

6 and 7 1000 x 1000 150 350 7-8 mm tor @ 133 c/c bothways

1 2 3 4
1 2 3 4

FOOTING SIZE EDGE DEPTH TOTAL DEPTH


FOOTING NO FOOTING SLAB REINFORCEMENT
L mm x B mm d mm D mm
11-10 mm tor @ 160 c/c along length, bottom layer
5 and 9 2000 x 1700 200 400 14-8 mm tor @ 146 c/c along width, top layer

1, 2, 3, 4, 16 9-10 mm tor @ 162 c/c along length, bottom layer


1400 x 1800 200 400
5 9
5 9 and 17 12- 8 mm tor @ 154 c/c along width, top layer
6 7 6 7
8
8
11 and 12 1600 x 1600 200 400 13-8 mm tor @ 125 c/c bothways

6-8 mm tor @ 140 c/c along length, bottom layer


14 and 15 1300 x 800 150 350
10 7-8 mm tor @ 200 c/c along width, top layer
10

6 and 7 1200 x 1200 150 350 8-8 mm tor @ 157 c/c bothways
11 12 11 12
13
13

17
16 17
14 15
16
15
14

COLUMN NO COLUMN SIZE LONG. STEEL STIRRUP & ARRANGEMENT REMARKS

8 torr rectangular tie @ 150mm c/c


14 and 15 250 x 250 4-16 torr REGULAR POST
LAY-OUT PLAN OF FOOTINGS FOR SBC= 120KN/m2 AND BEYOND Outer dimension of rectangular tie: 186 x 186
LAY-OUT PLAN OF FOOTINGS FOR SBC BETWEEN 60KN/m2 AND 80KN/m2
8 torr rectangular and open ties @ 150mm c/c
1, 2, 3, 4, 11,12, REGULAR POST
250 x 350 6-16 torr Outer dimension of rectangular tie: 186 x 286
16, and 17

8 torr rectangular and open ties @ 150mm c/c


5 and 9 350 x 450 4-20 torr and 2-12 torr Outer dimension of rectangular tie: 386 x 286 REGULAR POST
PLINTH FILLING WITH
RIVER SILT/ SAND

8 torr rectangular tie @ 150mm c/c


PLINTH LEVEL 6 and 7 250 x 250 4-16 torr COLUMNS UPTO PL
Outer dimension of rectangular tie: 186 x 186
1 2 3 4

6 torr rectangular tie @ 150mm c/c


8 150 X 350 4-12 torr FALSE POST
Outer dimension of rectangular tie: 82 x 282
950

250 x 400 TIE BEAM (DETAIL ENCLOSED IN


DWG NO. CGM(H&C)/CONTROL ROOM/2019/02

6 torr rectangular tie @ 150mm c/c


10 and 13 250 x 250 4-12 torr FALSE POST
Outer dimension of rectangular tie: 182 x 182
150

F.G.L.
400
250

X COMPACTED EARTH FILL


FLAT BRICK SOLING
E.G.L. 0.000 m
5 9
6 7
8

PLINTH FILLING WITH


RIVER SILT/ SAND
2000

50 Reinforcement

10
150 PLINTH LEVEL
D
d 75 mm thick
PCC(1:3:6)
Flat brick soling
150

950

11 12 13 250 x 400 TIE BEAM (DETAIL ENCLOSED IN


DWG NO. CGM(H&C)/CONTROL ROOM/2019/02

Fig 2:TYPICAL SECTION AT 1-1 (Type B)


150

F.G.L.
400

16 17
250

15
14
COMPACTED EARTH FILL
X FLAT BRICK SOLING
2-12 torr

E.G.L. 0.000 m
150 100
250

LAY-OUT PLAN OF FOOTINGS FOR SBC BETWEEN 80KN/m2 AND 120KN/m2 SECTION TYPE Range of X (mm) COMMENTS 2-12 torr
6Ø MS stirrups
@ 125 mm c/c FLAT BRICK SOLING
250 x 250 TIE BEAM
Only one group of tie beams will be provided as shown in Fig 1. The specification of the tie
Type A 0 beams are described in detail in drawing entitled as "LAYOUT PLAN FOR TIE-BEAMS, PLINTH
2000

WALL AND REINFORCEMENT DETAIL OF TIE BEAM" 50 Reinforcement


150
Only one group of tie beams will be provided as shown in Fig 2. The specification of the tie
B Type B 0< X < 900 D
beams are described in detail in drawing entitled as "LAYOUT PLAN FOR TIE-BEAMS, PLINTH 75 mm thick
d
WALL AND REINFORCEMENT DETAIL OF TIE BEAM" PCC(1:3:6)
Two groups of tie beam will be provided as shown in Fig 3. Flat brick soling
150

a) The first group will be constructed at the level of F.G.L. and specification for the
Type C 900 and above same are described in detail in drawing entitled as"LAYOUT PLAN FOR TIE-BEAMS,
PLINTH WALL AND REINFORCEMENT DETAIL OF TIE BEAM"
b) The second group will be constructed at the level of E.G.L. and specification for the
Fig 3:TYPICAL SECTION AT 1-1 (Type C)
L

1 1 same are described in Fig 3 of this Drawing Sheet.


Reinforcement

NOTE-

FOOTING PLAN Here X refers to height of compacted earth filling in millimeters for the purpose of
GENERAL NOTE FOR CONSTRUCTION
PLINTH FILLING WITH
raising low lying site locations.
RIVER SILT/ SAND
ALL RCC WORK SHALL BE CAST WITH M20 GRADE OF CONCRETE 1. E.G.L. refers to Existing Ground Level prior to raising of site by earth filling.
PLINTH LEVEL
(NOMINAL MIX OF 1:1.5:3) 2. F.G.L. refers to Finished Ground Level after raising of site by earth filling.
COARSE AGGREGATE OF 40 mm DOWN SIZE MAY BE USED IN
CONCRETE MIX FOR CASTING OF FOOTING .
950

250 x 400 TIE BEAM (DETAIL ENCLOSED IN


DWG NO. CGM(H&C)/CONTROL ROOM/2019/02
COLUMN SHALL BE CAST WITH 20 mm DOWN SIZE COARSE
E.G.L.
AGGREGATE ONLY .
150

E.G.L. 0.000 m
400
250

CLEAR COVER TO REINFORCEMENT :


FLAT BRICK SOLING
2000

TO MAIN STEEL OF COLUMNS : 40 mm


1750

50 Reinforcement
150 TO MAIN STEEL OF FOOTING : 50 mm ON ALL SIDES .
D
d 75 mm thick
PCC(1:3:6)
Flat brick soling
PLINTH LEVEL FROM EXISTING G.L. = 1050.00mm.
150

DRAWING ISSUED FOR TENDER PURPOSE ONLY


ALL DIMENSIONS ARE IN mm AND ONLY WRITTEN DIMENSIONS SHOULD BE
Fig 1:TYPICAL SECTION AT 1-1 (Type A)
FOLLOWED.
DRAWING TITLE
LAYOUT PLAN AND DETAIL OF COLUMNS AND
FOOTINGS
406

12-12 TOR @ 150 C/C


( TOP LAYER )

350
1 2 3 4

12
35
0 0
35

16
700
A B A B

1750
11-12 TOR PLACED SYMMETRICALLY
ABOUT CENTER LINE(BOTTOM LAYER)

350 350

353
600 600 REINFORCEMENT ARRANGEMENT IN PLAN
357 357
1914 BOTTOM FACE OF PILE CAP 1

PLAN OF PILE CAP 1


COLUMNS 1, 2, 3, 4, 5, 6, 7, 9, 16, 17
12-10 TOR @ 150 C/C
(BOTTOM LAYER )

11-12 TOR PLACED SYMMETRICALLY


12-10 TOR @ 150 C/C
ABOUT CENTER LINE A B
EGL 0.000 11-12 TOR PLACED SYMMETRICALLY
ABOUT CENTER LINE(TOP LAYER)

3-12 TOR TIED ALL

1000
AROUND SIDE FACES

800
CUT-OFF LVL. -1.000 REINFORCEMENT ARRANGEMENT IN PLAN

75
TOP FACE OF PILE CAP 1

75
5 6 7 8 9
12-12 TOR @ 150 C/C
11-12 TOR PLACED SYMMETRICALLY
ABOUT CENTER LINE

SECTION A-B OF PILE CAP

10

WORKING LEVEL : EGL, 0.000 m

13 CUT-OFF LEVEL : -1.000 m

11 12

PILE DIAMETER : 300 mm


SPACING BETWEEN PILES : 1200 mm
14 15 TOTAL LENGTH OF PILE : 10.0 m
LONG REINFORCEMENT OF PILE : 7 NO. 12 mm Ø TOR BARS
16 17 TRANSVERSE REINFORCEMENT OF PILE : 6 mm Ø HOOPS AT 150 C/C
CLEAR COVER TO AXIAL REINFORCEMENT : 40 mm
WORKING LEVEL : EGL, 0.000 m
CUT-OFF LEVEL : -1.000 m
FOUNDATION LEVEL : -10.000 m

AFTER EXCAVATION TO THE REQUIRED DEPTH, THE PILES SHALL BE CAST


CONTINUOUSLY WITH HOPPER AND FULL LENGTH TREMIE PIPE . ALL
CARE SHALL BE TAKEN TO ENSURE THAT TREMIE PIPE IS NOT
WITHDRAWN OUT OF DEPOSITED CONCRETE INSIDE PILE BORE-HALL.

LAY-OUT PLAN OF PILE CAPS THE PILES SHALL BE CAST CONTINUOUSLY UP TO THE WORKING LEVEL ( EGL ).
THEREAFTER, THE PILE HEADS SHALL BE DISMANTLED UP TO THE CUT-OFF LEVEL,
THE AXIAL REINFORCEMENTS SHALL BE BENT AND TIED WITH THE PILE CAP
REINFORCEMENT AS PER DETAIL DRAWING .
CEMENT CONCRETE OF HIGH SLUMP, NOT LESS THAN 150 mm SHALL BE
USED FOR CASTING OF PILES .

MINIMUM 350 kg OF CEMENT SHALL BE USED PER Cum OF CONCRETE


USED FOR PILE CASTING .
6 mm Ø M.S. HOOPS SHALL BE TACK WELDED TO THE LONG REINFORCEMENTS.
2214 6 mm Ø M.S. HOOPS PLACED BETWEEN CUT-OFF LEVEL TO EGL SHALL BE
357 357 TIED TO AXIAL REINFORCEMENT WITH TWO STRANDS OF 22 g BLACK WIRE .
750 750
13-12 TOR @ 154 C/C
( TOP LAYER ) 40 mm CLEAR COVER TO AXIAL REINFORCEMENT SHALL BE MAINTAINED BY
USING C.C RINGS PLACED ON M.S. HOOPS .

354
350
C 11 D 13-12 TOR PLACED SYMMETRICALLY
ABOUT CENTER LINE(BOTTOM LAYER)
CLEAR DISTANCE FROM PILE CENTER TO CAP EDGE IS 650 mm.

1250
1950
CLEAR COVER TO REINFORCEMENT OF PILE CAP : 50 mm BOTH ON SIDES AND BOTTOM.

18
66
14 ALL PILES SHALL PROTRUDE 50 mm INTO PILE CAP, i.e. BOTTOM FACE OF PILE CAPS
SHALL BE AT -1.050 m .

350
ALL PILE CAPS SHALL BE ERECTED OVER A 100 mm THICK SOLING OF RUBBLE ( BROKEN
PILE HEADS )
396 CLEAR COVER TO REINFORCEMENT OF PILE CAP : 50 mm BOTH ON SIDES AND BOTTOM.
REINFORCEMENT ARRANGEMENT IN PLAN
THIS DRAWING IS APPLICABLE FOR BOTTOM FACE OF PILE CAP 2 FOUNDATION LEVEL : -10.000 m
LOCATIONS WITH SOIL BEARING PLAN OF PILE CAP 2
COMBINED PILE CAP FOR COLUMNS 11 & 14, 12 & 15
CAPACITY LESS THAN 60KN/m2 DETAIL OF PILE SHAFT

15-10 TOR @ 132 C/C


( BOTTOM LAYER )

13-12 TOR PLACED SYMMETRICALLY


15-10 TOR @ 132 C/C
13-12 TOR PLACED SYMMETRICALLY ABOUT CENTER LINE(TOP LAYER)
ABOUT CENTER LINE
EGL 0.000

1000
3-12 TOR BARS TIES ALL
900

AROUND SIDE FACES

CUT-OFF LVL. -1.000


75

REINFORCEMENT ARRANGEMENT IN PLAN DRAWING ISSUED FOR TENDER PURPOSE ONLY


75

TOP FACE OF PILE CAP 2


13-12 TOR @ 154 C/C
13-12 TOR PLACED SYMMETRICALLY
ABOUT CENTER LINE

DRAWING TITLE

SECTION C-D OF PILE CAP LAYOUT PLAN AND DETAIL OF PILE CAPS AND PILE
SHAFTS
DOORS AND WINDOWS SCHEDULE
DOOR SCHEDULE

WINDOW SCHEDULE

NOTE
4000 4000 2615 2385

1 2 3 4

1100 1100

G
2-16
1100 1100 1100 1100 1300 1300 2-16 & 2-12 2-16 & 2-12

2-16 2-16 2-16


2-16 & 2-12 2-16 & 2-12 2-16 & 2-12 2-16 & 2-12

2150
2-16

900 1950 900


3000
B A B
2-16 2-16
H I 2-16 & 1-12
900 A 900 900 A 900 900 A 900
B B B B B B 2 3

5000
5000
1 2 3 4

2850
5 6 7 8 9

10050
1100 1300 1300
A: 8 TOR STIRRUP @ 160c/c
2-16 2-16 2-16
2-16 & 2-12 2-16 & 2-12
B: 8 TOR STIRRUP @ 140 c/c
ALL TIE BEAMS ARE 250 WIDE x 400 DEEP.
3000
10 E D 2-16 2-16
2-16 & 1-12 THE PLINTH BEAM IS 225mm WIDE AND 400 mm
900 A 900 900 A 900 900 A 900
DEEP

3800
B B B B B B

THERE IS ONLY ONE PLINTH BEAM IN THE


5 6 7 9
ENTIRE BUILDING IN ORDER TO ACCOMODATE

5000
THE INCOMING CABLE TRENCH

11 12 13

3205
4000 4000 2615 2385

1250
15 16 17 4
14 F 1 2 3

1840 G
2150

LAY-OUT PLAN OF TIE BEAM 800 800


2-16 2-16
2-16 & 2-12 2-16 & 2-12 H I
5000
5000

2-16 2-16

A A

10 E D
2850

5 6 7 8 9
10050

1300 1300 1000 1000 1250


1300 1300 1300 1300
2-16 2-16 & 2-12 2-16 2-16 & 2-12
2-16 & 2-12 2-16 2-16 & 2-12
2-16 & 2-12 2-16
2-16 & 2-12

3000 3000 E D
2-16 2-16 2-16 10
2-16 &1-12 2-16 &1-12
900 A 900 900 A 900 A
900 A 900 900 A 900
B B B B
B B B B
3800

1 5 11 14 4 9 17
5000

11 12 13
3205

1250

15 16 17
14 F

2-16 2-16 2-16


1300 1300 1300 1300 1840
2-16 2-16 & 2-12
2-16 & 2-12 2-16
2-16 & 2-12

LAY-OUT PLAN OF PLINTH WALL


2-16 2-16 2-16
900 A 900 900 A 900 A 3000 3000 EXTERNAL PLINTH WALL
B B B B 2-16 &1-12 2-16 &1-12
900 A 900 900 A 900
B B B B
2 6 12 15 INTERNAL PLINTH WALL
3 7 16
1. ALL EXTERNAL PLINTH WALLS ARE 225mm
THICK AND ALL INTERNAL PLINTH WALLS ARE
112.5mm THICK BRICK WALLS IN CEMENT
MORTAR 1:5.
2. HEIGHT OF EACH PLINTH WALL= (1050-150)mm
= 900mm.
3. A LAYER OF 25mm THICK D.P.C SHOULD BE
1100 1100 1100 1100
PROVIDED ALONG THE PERIPHERY OF ALL
800 800
2-16 2-16 2-12 2-12 2-16 2-16
PLINTH WALLS.
2-16 & 2-12 2-16 & 2-12 2-16 & 2-12 2-16 & 2-12 2-16 & 2-12
4. EXTERNAL WALL LINTEL
225 mm WIDE AND 250mm DEEP
2-16 2-16 2-12 2-12 2-16 2-16
REINFORCEMENT 4-12 torr DRAWING ISSUED FOR TENDER PURPOSE ONLY
900 A 900 900 A 900 A A
A A
STIRRUP- 6Ø MS @ 150mm c/c
B B B B
5. INTERNAL WALL LINTEL
11 12 13 H I E F G H 8 225 mm WIDE AND 250mm DEEP DRAWING TITLE
REINFORCEMENT 4-12 torr
STIRRUP- 6Ø MS @ 150mm c/c LAYOUT PLAN FOR TIE-BEAMS, PLINTH WALL AND
REINFORCEMENT DETAIL OF TIE BEAM
DESIGNATION OUTER DIA (mm) THICKNESS (mm) UNIT WEIGHT (kg/m)

1
1 65 NB MEDIUM 76.1 3.6 6.42

1
2 50 NB MEDIUM 60.3 3.6 5.03
2

1700
2 2 2 2 2
3 40 NB MEDIUM 48.3 3.2 3.56
2 2 2 2 2
3 3 3 3

1700
2 2 2 2 2
3 3 3
2 2 2 2 REPRESENTS HORIZONTAL RUNNERS ON BOTTOM CHORD OF TRUSS

696
3 3 3 3 2
3
3 3 3 3 3

3 3800 299.19 3 1 REPRESENTS PRINCIPAL RAFTER AND THE PRINCIPAL TIE OF EACH
1
3 3 TRUSS
5000
1 WALL PLATE
225mm x 225mm 2 REPRESENTS PURLINS FROM P1 TO P16
COLUMN PLATE
10000 250mm x 150mm
3 REPRESENTS PURLINS FROM P15 TO P17
ELEVATION OF TRUSS T1 225mm THICK
BRICK WALL
FOR SECONDARY TIES AND STRUTS MEMBER SPECIFICATIONS
ELEVATION OF TRUSS T2 ARE MENTIONED AGAINST THE RESPECTIVE MEMBERS

13350

4000 4000 2615 2385


A
B

TRUSS T1
TRUSS T2
431
4
225mm THICK PURLIN P1 225mm THICK 1
588
GABLE WALL GABLE WALL
225mm WIDE X 250mm DEEP
W1 RCC LINTEL

PURLIN P2

2-12Ø
6Ø @ 150mm c/c

1220
PURLIN P3
2-12Ø 115
WALL PLATE
TWISTED STEEL HOLDFAST
225mm x 225mm
2-16Ø 225mm WIDE X 300mm DEEP
500
1258

RCC LINTEL 225mm WIDE X 300mm DEEP


399
RCC LINTEL
2-16Ø

1220
456

PURLIN P4

2-16Ø
RAMP

5000
5000
800 A 800 2-16Ø

PURLIN P5 B B 800 A 800

1220
B B

PURLIN P6

1190

9150
PURLIN P7
SECTIONAL ELEVATION AT A-A
PURLIN P8

1220
PURLIN P9

1 588
1
PURLIN P10 588

1220

3800
225mm WIDE X 250mm DEEP
RCC LINTEL

5000
PURLIN P11

2-12Ø

1220
6Ø @ 150mm c/c

PURLIN P12

2-12Ø

PURLIN P15 399


A 399 225mm WIDE X 300mm DEEP
225mm WIDE X 300mm DEEP
850
850

PURLIN P13 RCC LINTEL


RCC LINTEL
2-16Ø 2-16Ø

1250
PURLIN P16

PURLIN P17 2-16Ø 2-16Ø


PURLIN P14
425 1500 1500 1500 1500 1500 800 A 800 800 A 800
B B B B

REPRESENTS HORIZONTAL RUNNERS MADE OF B


40NB MEDIUM STRUCTURAL STEEL TUBE
RAFTER R4

RAFTER R3
RAFTER R6

RAFTER R2
RAFTER R5

RAFTER R1
REPRESENTS PRINCIPAL TIE BARS OF ROOF SECTIONAL ELEVATION AT B-B
TRUSS T1 & T2
LAY-OUT PLAN OF ROOF

LAY-OUT PLAN OF HORIZONTAL RUNNERS ON BOTTOM CHORD OF TRUSS


FOR THE PURPOSE OF SUSPENDING FALSE CEILING

225mm x 225mm
MAIN STEEL: 4-12mm torr
STIRRUP: 6Ø @ 150mm c/c

60 60
431 60 60 250mm x 150mm
960 4
960 MAIN STEEL: 4-12mm torr
5881 960
960
960 960 STIRRUP: 6Ø @ 150mm c/c
1 588
1
588 960
960 960

1700
960
960
1700

960 413 960 225mm THICK BRICK GABLE


WALL IN CEMENT MORTAR

193
960
960 960
1661 PROPORTION 1:5

193
193

960
909 909 909 909 966 966 909 909 1016 761 960
60
761
398 60 909 909 909 909 966 966 909 909 909 909 60 A: 8 TOR STIRRUP @ 180c/c
568 5000 3800 398 398 B: 8 TOR STIRRUP @ 155 c/c
568 5000 5000 568 DRAWING ISSUED FOR TENDER PURPOSE ONLY

GEOMETRY OF TRUSS T1 DRAWING TITLE


GEOMETRY OF TRUSS T2

DETAIL OF ROOF TRUSS AND GABLE WALL


75Ø Ventilation Pipe

225 mm thick brick wall


3 nos 450Ø cast iron cover
12.5mm thick cement mortar (1:3)
Removable pre-cast

100
EGL
Turfed concrete slab 112.5 mm thick brick wall
245 150
INLET
300
75.0000

OUTLET
450.0000

Cement Mortar(1:3)
EGL 700

700.0000
12.5mm thick 110mm Ø Pipe

INLET Honeycomb Brick lining with


150.0 dry joints OUTLET
INLET 950 1450
1800

1000
X X

FBS 75 mm thick Slope 1 in 10


500 500 500
25mm thick DPC course

1225.0000
75 2300
RCC lintel 112.5 x 180
SECTION Y-Y FBS 75 mm thick
M15 grade cement concrete floor (1:2:4)
PLAN OF SEPTIC TANK
12.5 mm thick cement mortar (1:3)
throughout the inner surface

SECTION X-X

3550.0000

Main steel(8Ø tor-steel @ 135 c/c) Distribution steel(8Ø tor-steel @ 150 c/c)
1750.0000

225 mm thick brick wall

Y
X X

250.0000
Section X-X showing
reinforcement detail

INLET 1000

PLAN OF SLAB REINFORCEMENT DETAIL


Y Y 4 nos Diagonal stitching bars around each
opening of 10Ø tor-steel
Main steel 800
(8Ø tor-steel @ 135 c/c)
1000 450 4 nos Additional reinforcement bar around
each hole of 10Ø tor-steel

Y
650
Distribution steel
PLAN OF SOAK PIT (8Ø tor-steel @ 150 c/c)

Section Y-Y showing


reinforcement detail
DRAWING TITLE
Reinforcement detail around
each opening

DETAIL OF SEPTIC TANK AND SOAK PIT


DRAWING ISSUED FOR TENDER PURPOSE ONLY
DRAWING TITLE: DESIGN AND DRAWING OF BOUNDARY WALL

Stirrups for
ISA-65X65X6 angle 6mmØ bar @150mm c/c
4nos 16mmØ TS bar

600mm

350mm Tie beam section


Lintel 150mm

250mm top of Lintel

350mm 8 Nos barbed wire Stirrups for


6mmØ bar @150mm c/c 4nos 10mmØ TS bar
125mm Thick
Brick Work
Lintel section

2000
ISA-90X90X6
Welded by ISA-65x65x6 Stirrups for

(Brick Wall)
6mm bar @150mm C/C

20mm Thick
15mm Thick Cement Sand Plaster Prop 1:5
Cement Sand Plaster Prop 1:5
300mm x 230mm size tie beam 4nos 12mmØ TS bar
F.G.L

230mm thick brick wall depth depending on site condition

G.L
Wall Column Section
NOTES:
1. All Dimensions are mm
2. Columns are to be provided @ 2.50mtr. dist. c/c
of the Columns expansion gap joint to be provided 75mm thick brick flat soiling
for 65mm at every 15mtr interval weep holes to be
provided sufficiency in case of wall of higher depth
where filled earth depth is more than 600mm
Drawing Issued for Tender Purpose Only
200mm thick R.C.C 1:2:4

75mm thick 1:3:6 PCC


75mm thick brick soiling

WALL COLUMN
DRAWING TITLE- DESIGN OF SECTION OF SWITCH YARD CABLE TRENCH

Drawing Issued for Tender Purpose Only


STANDARD R.C.C CABLE TRENCH ( C&D Type) for
Terminal Bay at Grid Sub-station Locations

DIMENSIONS FOR TOP COVER OF CABLE


TRENCH
CABLE TRENCH
TYPE
A1 A2 B1 B2
A 1500 325 400 200

B 1450 325 400 200

C 1200 325 400 200

D 650 325 400 200

FOR TENDER PURPOSE ONLY


DRAWING TITLE: STANDARD PAVER BLOCK ROAD (3.750M)

SITE BEAM
(PCC-1:3:6)
SIDE BERM
(Normal soil)
100 THK CONSOLATED
WATERBOUND MACADAM
2 LAYERS OF 100MM EACH 60MM/80MM THKPAVER BLOCK(M-35)

20mm/30mm Sand Bedding


40 MM AGGREGATE
60 MM AGGREGATE
SITE BEAM SITE BEAM
(PCC-1:3:6) (PCC-1:3:6)
SIDE BERM
SIDE BERM (Normal soil)
(Normal soil)
WELL COMPACTED LOCAL SOIL
OF 0.5% OF DRY DENSITY (PROCTOR DENSITY)

PCC PAVER BLOCK

Note:-
1. ALL DIMENSIONS ARE IN MM.
2. CAMBER OF 1:50 SHALL BE PROVIDED.
3. EXPANSION JOINT (12MM THK) SHALL BE PROVIDED AT EVERY 10M.
EXPANSION JOINT SHALL BE PROVIDED AT CENTRE
4.THE INTERSECT BETWEEN CC BLOCK OF FILLING BY SAND.

Drawing Issued for Tender Purpose Only


DRAWING TITLE: DESIGN OF SWITCH YARD GATE

Total Length-4000 mm

DESIGN & DRAWING FOR SWITCHYARD GATE

Drawing issued for Tender Purpose Only


DRAWING TITLE: DESIGN OF CHAIN LINKED FENCHING

Detail A-A

Design andDrawing
Drawing forIssued
Chain Linked Tender
forFencing Purpose Only
DRAWING TITLE : SKETCH PLAN OF TYPICAL UNDER GROUND
RAILWAY TRACK CROSSING

LIGHTNING
* Length of Crossing Span may vary as per Site Condition and Directive of RLY LIGHTNING
ARRESTOR Authority ARRESTOR

DISC
INSULATOR 25.0m(Min) 25.0m(Min) DISC
INSULATOR
As per
As ite
per Sside As per S
As per ite
side
TWO POLE TWO POLE M.S.
CHANNEL
TWO
POLE

HDPE HDPE
PIPE PIPE M.S.
STAY SET
ANGLE
DANGER M.S.
BOARD DANGER DANGER CROSS ARM
C:\Users\admin\Desktop\SANJIB.jpg C:\Users\admin\Desktop\SANJIB.jpg
BOARD BOARD

Height of steel pole


BARBED
WIRE
Height of steel pole

HDPE PIPE BARBED BARBED


WIRE SIGN BORD INDICATING PIPE LINE SIGN BORD INDICATING PIPE LINE
WIRE
4.0 CROSSING UNDER RLY TRACK CROSSING UNDER RLY TRACK
RLY LAND BOUNDARY 1.743
1.676 RLY LAND BOUNDARY

CABLE CABLE
P.C.C. G.L. G.L. MARKER h h MARKER G.L. G.L. G.L.
(M-20) 3.00m(Min) C.I. PIPE HT. CABLE
2.00 2.00
P.C.C.
(M-20)
0.70M
EARTHING
P.C.C.
ELEVATION P.C.C.(M-20)
(M-20)
SIDE VIEW
SIDE VIEW

Km.P
0.15 0.219 0.15

0.15
G.L. G.L. 25.0m(Min) 25.0m(Min)
0.219

0.15
TRENCH X TWO
3.00m(Min)
TWO POLE
FOUNDATION
CI. PIPE POLE DETAIL OF E/POLE
HT. CABLE X SEC- Y-Y
0.65M
SECTION-X-X
CROSS SECTION OF
TRENCH & CI. PIPE
Km.p

1.50M
RLY. LAND BOUNDARY

RLY. LAND BOUNDARY


0.40M
As per S
As per ite
side As per S
As per ite
side G.L G.L

0.40M
PLAN 1.20M C.C(M.20)
P.C.C(M.20)
NOT TO SCALE
FOUNDATION DETAIL
OF SIGN BOARD INDICATOR SECTION AT A-A'
Drawing Issued for Tender Purpose Only
TYPICAL DESIGN OF PTR FOUNDATION

H H

C/C

Note:

* This is a Typical Drawing for reference. The Bidder has to


design the actual foundation as per Manufacturer's GA
drawing of the offered PTR (s) for different Ratings.
* The Height "H" between FGL and NGL may vary as per site
condition and height of earth filling as mentioned in BOQ against
each sub-station location.
* C/C distance between the position of the rail shall vary as per
C/C GA drawing of the offered PTR.
DRAWING ISSUED FOR TENDER PURPOSE ONLY
DESIGN OF FIRE WALL
BETWEEN POWER TRANSFORMER

Drawing Issued For Tender Purpose Only

Note: The drawing is just for reference and design should be customised
for the difference between FGL and NGL as per site condition and as per
information provided in BOQ.