Tender Drawings PDF
Tender Drawings PDF
VOLUME-IV
TENDER DRAWINGS
(This section of the Tender Document covers sample Design Drawings for reference of the Bidder.
However, the Successful bidder shall have to prepare design and drawing as per actual site
conditions and to take approval of the employer prior to start of the works)
4 iii) Layout Plan and Details of Pile Cap and Pile Shaft
iv) Layout plan for Tie Beams Plinth wall and Reinforcement details of Tie
beam
v) Layout Plan, Sectional elevation of Cable Trench and Doors and Window
Schedule
vi) Details of Roof Truss and Gabble wall
vii) Details of Septic tank and Soak Pit
5 Design and Drawing of Boundary Wall
6 Design and Drawing of RRM Boundary Wall
7 Design of Section of Switchyard Cable Trench (For New Sub-station and Terminal Bay at
DSS)
8 Design of Section of Switchyard Cable Trench (C & D Type for Terminal Bay at GSS)
9 Standard Paver Block Road
10 Design of Switchyard Gate
11 Design of Chain Linked Fencing
12 Sketch Plan of Typical Under Ground Railway Track Crossing
13 Typical Power Transformer Foundation
14 Typical Fire Protection Wall between Power Transformer
4008
3600
3600
3600
3410
3100
35mm THICK FLOOR FINISH
25mm THICK DPC
65mm THICK PCC
251
1050
1050
WALL PLASTER
134
25mm THICK DPC
50mm THICK PCC
75mm THICK FBS
2400 27
°
50mm THICK AND 750mm
WIDE APRON ALL AROUND
THE PERIPHERY
C1 C1 C3
W W W1
BATT. W2
D2
BC
1 2 3 4 5 6 7 8 9 10 110 mm dia P.V.C pipes for the 110 mm dia P.V.C pipes for the
purpose of carrying Rain water purpose of carrying Rain water
RAMP C2 from rain gutters to the nearest from rain gutters to the nearest
SEPTIC TANK
2400
5000
5000
RS run-off drain run-off drain
C4
2000 X 2500
11 KV SWITCHGEAR PANEL
STORE ROOM
2700 X 2195
W2
3
CONTROL ROOM
79.63 sqm
D2
33 KV CRP
1695 WIDE PASSAGE 3500
1 D2
C1
3800
W D3
RTCC RTCC
5000
ACDB DCDB BC
TOILET
1 2 3025 X 1650 1
W2
D1
W ACDB
1250
8000 X 1320 D3 CHAJJAH LENGTH (mm) WIDTH (mm) THICKNESS (mm) REINFORCEMENT
W 2
C1 2600 450 75 8Ø torr steel @ 140 mm c/c both ways
C1
RAMP
C2 2800 600 75 8Ø torr steel @ 140 mm c/c both ways
A
DESIGNATION OUTER DIA (mm) THICKNESS (mm) UNIT WEIGHT (kg/m)
C1 C3 1600 450 8Ø torr steel @ 140 mm c/c both ways
75
1 40 NB MEDIUM 76.1 3.6 6.42
C4 7815 600 75 8Ø torr steel @ 140 mm c/c both ways DRAWING ISSUED FOR TENDER PURPOSE ONLY
2 20 NB MEDIUM 60.3 3.6 5.03
1200 2000
DRAWING TITLE
FLOOR PLAN
FLOOR PLAN, FRONT ELEVATION, SIDE ELEVATION,
CHAJJAH SCHEDULE AND SECTIONAL ELEVATION
LAY-OUT
4000 4000 2615 2385
1 2 3 4 1 3 4
2
1, 2, 3, 4, 11, 12, 7-10 mm tor @ 133 c/c along length, bottom layer
5000
5000
5000
5000
900 x 1400 200 400
16 and 17 9- 8 mm tor @ 162 c/c along width, top layer
14 and 15 800 x 800 150 350 6-8 mm tor @ 140 c/c bothways
9
100
8
100
5 6 7 5 6 7 9
6 and 7 900 x 900 150 350 7-8 mm tor @ 133 c/c bothways
10050
2615 2385
1845
10
3800
3800
5000
5000
1905
11 12 13 12
11
50
1250
6 and 7 1000 x 1000 150 350 7-8 mm tor @ 133 c/c bothways
1 2 3 4
1 2 3 4
6 and 7 1200 x 1200 150 350 8-8 mm tor @ 157 c/c bothways
11 12 11 12
13
13
17
16 17
14 15
16
15
14
F.G.L.
400
250
50 Reinforcement
10
150 PLINTH LEVEL
D
d 75 mm thick
PCC(1:3:6)
Flat brick soling
150
950
F.G.L.
400
16 17
250
15
14
COMPACTED EARTH FILL
X FLAT BRICK SOLING
2-12 torr
E.G.L. 0.000 m
150 100
250
LAY-OUT PLAN OF FOOTINGS FOR SBC BETWEEN 80KN/m2 AND 120KN/m2 SECTION TYPE Range of X (mm) COMMENTS 2-12 torr
6Ø MS stirrups
@ 125 mm c/c FLAT BRICK SOLING
250 x 250 TIE BEAM
Only one group of tie beams will be provided as shown in Fig 1. The specification of the tie
Type A 0 beams are described in detail in drawing entitled as "LAYOUT PLAN FOR TIE-BEAMS, PLINTH
2000
a) The first group will be constructed at the level of F.G.L. and specification for the
Type C 900 and above same are described in detail in drawing entitled as"LAYOUT PLAN FOR TIE-BEAMS,
PLINTH WALL AND REINFORCEMENT DETAIL OF TIE BEAM"
b) The second group will be constructed at the level of E.G.L. and specification for the
Fig 3:TYPICAL SECTION AT 1-1 (Type C)
L
NOTE-
FOOTING PLAN Here X refers to height of compacted earth filling in millimeters for the purpose of
GENERAL NOTE FOR CONSTRUCTION
PLINTH FILLING WITH
raising low lying site locations.
RIVER SILT/ SAND
ALL RCC WORK SHALL BE CAST WITH M20 GRADE OF CONCRETE 1. E.G.L. refers to Existing Ground Level prior to raising of site by earth filling.
PLINTH LEVEL
(NOMINAL MIX OF 1:1.5:3) 2. F.G.L. refers to Finished Ground Level after raising of site by earth filling.
COARSE AGGREGATE OF 40 mm DOWN SIZE MAY BE USED IN
CONCRETE MIX FOR CASTING OF FOOTING .
950
E.G.L. 0.000 m
400
250
50 Reinforcement
150 TO MAIN STEEL OF FOOTING : 50 mm ON ALL SIDES .
D
d 75 mm thick
PCC(1:3:6)
Flat brick soling
PLINTH LEVEL FROM EXISTING G.L. = 1050.00mm.
150
350
1 2 3 4
12
35
0 0
35
16
700
A B A B
1750
11-12 TOR PLACED SYMMETRICALLY
ABOUT CENTER LINE(BOTTOM LAYER)
350 350
353
600 600 REINFORCEMENT ARRANGEMENT IN PLAN
357 357
1914 BOTTOM FACE OF PILE CAP 1
1000
AROUND SIDE FACES
800
CUT-OFF LVL. -1.000 REINFORCEMENT ARRANGEMENT IN PLAN
75
TOP FACE OF PILE CAP 1
75
5 6 7 8 9
12-12 TOR @ 150 C/C
11-12 TOR PLACED SYMMETRICALLY
ABOUT CENTER LINE
10
11 12
LAY-OUT PLAN OF PILE CAPS THE PILES SHALL BE CAST CONTINUOUSLY UP TO THE WORKING LEVEL ( EGL ).
THEREAFTER, THE PILE HEADS SHALL BE DISMANTLED UP TO THE CUT-OFF LEVEL,
THE AXIAL REINFORCEMENTS SHALL BE BENT AND TIED WITH THE PILE CAP
REINFORCEMENT AS PER DETAIL DRAWING .
CEMENT CONCRETE OF HIGH SLUMP, NOT LESS THAN 150 mm SHALL BE
USED FOR CASTING OF PILES .
354
350
C 11 D 13-12 TOR PLACED SYMMETRICALLY
ABOUT CENTER LINE(BOTTOM LAYER)
CLEAR DISTANCE FROM PILE CENTER TO CAP EDGE IS 650 mm.
1250
1950
CLEAR COVER TO REINFORCEMENT OF PILE CAP : 50 mm BOTH ON SIDES AND BOTTOM.
18
66
14 ALL PILES SHALL PROTRUDE 50 mm INTO PILE CAP, i.e. BOTTOM FACE OF PILE CAPS
SHALL BE AT -1.050 m .
350
ALL PILE CAPS SHALL BE ERECTED OVER A 100 mm THICK SOLING OF RUBBLE ( BROKEN
PILE HEADS )
396 CLEAR COVER TO REINFORCEMENT OF PILE CAP : 50 mm BOTH ON SIDES AND BOTTOM.
REINFORCEMENT ARRANGEMENT IN PLAN
THIS DRAWING IS APPLICABLE FOR BOTTOM FACE OF PILE CAP 2 FOUNDATION LEVEL : -10.000 m
LOCATIONS WITH SOIL BEARING PLAN OF PILE CAP 2
COMBINED PILE CAP FOR COLUMNS 11 & 14, 12 & 15
CAPACITY LESS THAN 60KN/m2 DETAIL OF PILE SHAFT
1000
3-12 TOR BARS TIES ALL
900
DRAWING TITLE
SECTION C-D OF PILE CAP LAYOUT PLAN AND DETAIL OF PILE CAPS AND PILE
SHAFTS
DOORS AND WINDOWS SCHEDULE
DOOR SCHEDULE
WINDOW SCHEDULE
NOTE
4000 4000 2615 2385
1 2 3 4
1100 1100
G
2-16
1100 1100 1100 1100 1300 1300 2-16 & 2-12 2-16 & 2-12
2150
2-16
5000
5000
1 2 3 4
2850
5 6 7 8 9
10050
1100 1300 1300
A: 8 TOR STIRRUP @ 160c/c
2-16 2-16 2-16
2-16 & 2-12 2-16 & 2-12
B: 8 TOR STIRRUP @ 140 c/c
ALL TIE BEAMS ARE 250 WIDE x 400 DEEP.
3000
10 E D 2-16 2-16
2-16 & 1-12 THE PLINTH BEAM IS 225mm WIDE AND 400 mm
900 A 900 900 A 900 900 A 900
DEEP
3800
B B B B B B
5000
THE INCOMING CABLE TRENCH
11 12 13
3205
4000 4000 2615 2385
1250
15 16 17 4
14 F 1 2 3
1840 G
2150
2-16 2-16
A A
10 E D
2850
5 6 7 8 9
10050
3000 3000 E D
2-16 2-16 2-16 10
2-16 &1-12 2-16 &1-12
900 A 900 900 A 900 A
900 A 900 900 A 900
B B B B
B B B B
3800
1 5 11 14 4 9 17
5000
11 12 13
3205
1250
15 16 17
14 F
1
1 65 NB MEDIUM 76.1 3.6 6.42
1
2 50 NB MEDIUM 60.3 3.6 5.03
2
1700
2 2 2 2 2
3 40 NB MEDIUM 48.3 3.2 3.56
2 2 2 2 2
3 3 3 3
1700
2 2 2 2 2
3 3 3
2 2 2 2 REPRESENTS HORIZONTAL RUNNERS ON BOTTOM CHORD OF TRUSS
696
3 3 3 3 2
3
3 3 3 3 3
3 3800 299.19 3 1 REPRESENTS PRINCIPAL RAFTER AND THE PRINCIPAL TIE OF EACH
1
3 3 TRUSS
5000
1 WALL PLATE
225mm x 225mm 2 REPRESENTS PURLINS FROM P1 TO P16
COLUMN PLATE
10000 250mm x 150mm
3 REPRESENTS PURLINS FROM P15 TO P17
ELEVATION OF TRUSS T1 225mm THICK
BRICK WALL
FOR SECONDARY TIES AND STRUTS MEMBER SPECIFICATIONS
ELEVATION OF TRUSS T2 ARE MENTIONED AGAINST THE RESPECTIVE MEMBERS
13350
TRUSS T1
TRUSS T2
431
4
225mm THICK PURLIN P1 225mm THICK 1
588
GABLE WALL GABLE WALL
225mm WIDE X 250mm DEEP
W1 RCC LINTEL
PURLIN P2
2-12Ø
6Ø @ 150mm c/c
1220
PURLIN P3
2-12Ø 115
WALL PLATE
TWISTED STEEL HOLDFAST
225mm x 225mm
2-16Ø 225mm WIDE X 300mm DEEP
500
1258
1220
456
PURLIN P4
2-16Ø
RAMP
5000
5000
800 A 800 2-16Ø
1220
B B
PURLIN P6
1190
9150
PURLIN P7
SECTIONAL ELEVATION AT A-A
PURLIN P8
1220
PURLIN P9
1 588
1
PURLIN P10 588
1220
3800
225mm WIDE X 250mm DEEP
RCC LINTEL
5000
PURLIN P11
2-12Ø
1220
6Ø @ 150mm c/c
PURLIN P12
2-12Ø
1250
PURLIN P16
RAFTER R3
RAFTER R6
RAFTER R2
RAFTER R5
RAFTER R1
REPRESENTS PRINCIPAL TIE BARS OF ROOF SECTIONAL ELEVATION AT B-B
TRUSS T1 & T2
LAY-OUT PLAN OF ROOF
225mm x 225mm
MAIN STEEL: 4-12mm torr
STIRRUP: 6Ø @ 150mm c/c
60 60
431 60 60 250mm x 150mm
960 4
960 MAIN STEEL: 4-12mm torr
5881 960
960
960 960 STIRRUP: 6Ø @ 150mm c/c
1 588
1
588 960
960 960
1700
960
960
1700
193
960
960 960
1661 PROPORTION 1:5
193
193
960
909 909 909 909 966 966 909 909 1016 761 960
60
761
398 60 909 909 909 909 966 966 909 909 909 909 60 A: 8 TOR STIRRUP @ 180c/c
568 5000 3800 398 398 B: 8 TOR STIRRUP @ 155 c/c
568 5000 5000 568 DRAWING ISSUED FOR TENDER PURPOSE ONLY
100
EGL
Turfed concrete slab 112.5 mm thick brick wall
245 150
INLET
300
75.0000
OUTLET
450.0000
Cement Mortar(1:3)
EGL 700
700.0000
12.5mm thick 110mm Ø Pipe
1000
X X
1225.0000
75 2300
RCC lintel 112.5 x 180
SECTION Y-Y FBS 75 mm thick
M15 grade cement concrete floor (1:2:4)
PLAN OF SEPTIC TANK
12.5 mm thick cement mortar (1:3)
throughout the inner surface
SECTION X-X
3550.0000
Main steel(8Ø tor-steel @ 135 c/c) Distribution steel(8Ø tor-steel @ 150 c/c)
1750.0000
Y
X X
250.0000
Section X-X showing
reinforcement detail
INLET 1000
Y
650
Distribution steel
PLAN OF SOAK PIT (8Ø tor-steel @ 150 c/c)
Stirrups for
ISA-65X65X6 angle 6mmØ bar @150mm c/c
4nos 16mmØ TS bar
600mm
2000
ISA-90X90X6
Welded by ISA-65x65x6 Stirrups for
(Brick Wall)
6mm bar @150mm C/C
20mm Thick
15mm Thick Cement Sand Plaster Prop 1:5
Cement Sand Plaster Prop 1:5
300mm x 230mm size tie beam 4nos 12mmØ TS bar
F.G.L
G.L
Wall Column Section
NOTES:
1. All Dimensions are mm
2. Columns are to be provided @ 2.50mtr. dist. c/c
of the Columns expansion gap joint to be provided 75mm thick brick flat soiling
for 65mm at every 15mtr interval weep holes to be
provided sufficiency in case of wall of higher depth
where filled earth depth is more than 600mm
Drawing Issued for Tender Purpose Only
200mm thick R.C.C 1:2:4
WALL COLUMN
DRAWING TITLE- DESIGN OF SECTION OF SWITCH YARD CABLE TRENCH
SITE BEAM
(PCC-1:3:6)
SIDE BERM
(Normal soil)
100 THK CONSOLATED
WATERBOUND MACADAM
2 LAYERS OF 100MM EACH 60MM/80MM THKPAVER BLOCK(M-35)
Note:-
1. ALL DIMENSIONS ARE IN MM.
2. CAMBER OF 1:50 SHALL BE PROVIDED.
3. EXPANSION JOINT (12MM THK) SHALL BE PROVIDED AT EVERY 10M.
EXPANSION JOINT SHALL BE PROVIDED AT CENTRE
4.THE INTERSECT BETWEEN CC BLOCK OF FILLING BY SAND.
Total Length-4000 mm
Detail A-A
Design andDrawing
Drawing forIssued
Chain Linked Tender
forFencing Purpose Only
DRAWING TITLE : SKETCH PLAN OF TYPICAL UNDER GROUND
RAILWAY TRACK CROSSING
LIGHTNING
* Length of Crossing Span may vary as per Site Condition and Directive of RLY LIGHTNING
ARRESTOR Authority ARRESTOR
DISC
INSULATOR 25.0m(Min) 25.0m(Min) DISC
INSULATOR
As per
As ite
per Sside As per S
As per ite
side
TWO POLE TWO POLE M.S.
CHANNEL
TWO
POLE
HDPE HDPE
PIPE PIPE M.S.
STAY SET
ANGLE
DANGER M.S.
BOARD DANGER DANGER CROSS ARM
C:\Users\admin\Desktop\SANJIB.jpg C:\Users\admin\Desktop\SANJIB.jpg
BOARD BOARD
CABLE CABLE
P.C.C. G.L. G.L. MARKER h h MARKER G.L. G.L. G.L.
(M-20) 3.00m(Min) C.I. PIPE HT. CABLE
2.00 2.00
P.C.C.
(M-20)
0.70M
EARTHING
P.C.C.
ELEVATION P.C.C.(M-20)
(M-20)
SIDE VIEW
SIDE VIEW
Km.P
0.15 0.219 0.15
0.15
G.L. G.L. 25.0m(Min) 25.0m(Min)
0.219
0.15
TRENCH X TWO
3.00m(Min)
TWO POLE
FOUNDATION
CI. PIPE POLE DETAIL OF E/POLE
HT. CABLE X SEC- Y-Y
0.65M
SECTION-X-X
CROSS SECTION OF
TRENCH & CI. PIPE
Km.p
1.50M
RLY. LAND BOUNDARY
0.40M
PLAN 1.20M C.C(M.20)
P.C.C(M.20)
NOT TO SCALE
FOUNDATION DETAIL
OF SIGN BOARD INDICATOR SECTION AT A-A'
Drawing Issued for Tender Purpose Only
TYPICAL DESIGN OF PTR FOUNDATION
H H
C/C
Note:
Note: The drawing is just for reference and design should be customised
for the difference between FGL and NGL as per site condition and as per
information provided in BOQ.