PRICE E1203257Mrev4-20-EST-JON EPPM MARAFIQ STG 5&6 FPS OPTION 2
PRICE E1203257Mrev4-20-EST-JON EPPM MARAFIQ STG 5&6 FPS OPTION 2
Dear Sir,
Thank you for sending us referenced inquiry and giving us the opportunity to quote. We would like to
offer the following products and/or services for your consideration.
General Terms:
1- [Payment Terms: [30% down payment, 10% payment upon drawing approval, 7% payment
upon ordering of major item, 50% payment progress billing per installation progress and 3%
payment after testing and commissioning works].
2- [Quotation Currency: [Saudi Riyal (SAR)].
3- [Quotation Validity: [90 Days].
4- [Liquidated Damages are not acceptable unless agreed in writing prior to order placement.
5- [Delivery quoted is firm for the given quote validity.]
6- [Delivery is counted from the date of receiving your acceptable order and/or approval of
documentation.]
7- [Saudi Arabian customs duty is included in this quotation, if any.]
8- [Place of Delivery: Delivery Duty Paid (DDP) on site].
9- [Mode of shipment: [Sea]
10- [Delivered free on truck at ALBILAD Ex-Factory Dammam].
11- [Delivery period [To be discussed later after receipt of confirm order]
12- [ALBILAD Commercial Registration number is 2050022021].
13- [Notes: Our Offer is Engineering and design works, HCIS installation package, Supply,
Procurement, Delivery, Installation, Testing and Commissioning Works.
14- [Buyer must notify Albilad Fire Fighting Systems Limited in writing of requested changes in
the quantity, drawings, designs or specifications or scope of work. After receipt of such notice,
Albilad Fire Fighting Systems Limited will inform Buyer of any adjustments to be made in
price, delivery schedules, etc. for the whole proposal
QUOTATION
Quote:
PRE-DELIVERY SCHEDULE
If you have any clarifications, please contact Mr. Hidayat Ali at Tel. #: 03-812-1023 ext. 279 or Mobile
# +966-55-507-2863.
Thank you,
Best Regards,
Project : SUPPLY & INSTALLATION OF TWO NEW DIESEL FIRE PUMP FOR MARAFIQ-YANBU STG 5 & 6 PLANT
1.01 Pre-Assemble Fire Water Diesel Engine Driven Pumps 1 1,662,262.00 1,662,262.00 249,339.30
UL/FM Approved in accordance with NFPA 20. SKID
which include the following; ASSY.
2 Fire Pump System
unit Mount Mounting type: Mounted on base with driver
Pump
Pump model: 8AEF20
Pump listing: FM/UL/ULC Listed
Selected pump listing: FM/UL Listed
Casing material: Cast Iron
Suction flange: 125lb ANSI Flat faced
Discharge flange: 250lb ANSI Flat faced
Casing ring: Bismuth tin bronze
Impeller material: Silicon Brass
Impeller ring: Integral
Rotation: Clockwise (RH)
Bearing solution: Single row outboard grease lube bearing
Shaft material: Carbon steel
Shaft sleeve material: 304SS with O-ring
Lantern Ring: Lantern ring with seal piping
Packing type: Standard
Nameplate units: US
Performance TestsL Non-witnessed Performance Test
Hydrostatic Pressure Tests: Non-witnessed Hydrostatic Test
Export Shipment Boxing: None
Driver
Pump
Baseplate design: Drip rim
Driver Type
Engine manufacturer: All engines
Engine cooling type: Heat exchanger cooled
Pressure limiting: Yes
Pressure limiting engine type: Discharge
Emission tier: Any
Engine: Clarke JW6H-UFADD0-D, 324hp, 1760rpm, Emission tier level T0
Engine voltage: 12 Volt DC
Cooling loop: FM Steel Cooling loop
Drive shaft: UL Listed drive-shaft, flywheel adapter, companion flange, & guard
Water jacket heater voltage: 230/240 VAC
Project : SUPPLY & INSTALLATION OF TWO NEW DIESEL FIRE PUMP FOR MARAFIQ-YANBU STG 5 & 6 PLANT
Project : SUPPLY & INSTALLATION OF TWO NEW DIESEL FIRE PUMP FOR MARAFIQ-YANBU STG 5 & 6 PLANT
Main relief valve: Valve, relief angle, Cla-Val, 6" ANSI flange, 150lb ANSI,
Pilot operated, 20-200psi, 200psi MWP, UL/FM Listed
Overflow cone: 6" x 10", 125lb x 125lb
Flush Mount Test Header Assembly: None selected
Hose valve head: None selected
Hose valve: None selected
Ball valve/drain: None selected
1 Jockey pump
unit Jockey pump supply: Grundfos CR
Frequency: 60 Hz
Phase: Three
Voltage: 460 V
Flow rate: Flow rated: 40 US gpm
Total discharge head: Total discharge head: 170 psi
Jockey pump selected: CR 5-22-3ph/7.5Hp 213TC Fr
Duty point: 40 US gpm, 177.5psi
Shutoff pressure: 309.5psi, 460V, ANSI flange, HQQE
Seal type
Discharge Gauge 0-300PSI w/Fittings, Discharge Gauge
Jockey pump companion flange kit: None
Jockey Pump Controller
Jockey pump controller required: Yes
Manufacturer: Firetrol
Voltage: 440-480 V
Frequency: 60 Hz
Direct ship jockey pump controller: No
Jockey pump controller selected: Firetrol Controller FTA550E-AA,
JockeyXG, 7.5-7.5hp, 440-480V, 3Ph, 60hz
Enclosure: - NEMA 2
Enclosure type: NEMA Type 2
Anti-condensation space heaters: - None
Pressure transducers: - None
Project : SUPPLY & INSTALLATION OF TWO NEW DIESEL FIRE PUMP FOR MARAFIQ-YANBU STG 5 & 6 PLANT
1.05 OS&Y Gate valve, 200 psig, Ductile iron, Flanged end, 2
Model: 7566, Size: 18" fusion bond epoxy coated.
UL/FM Approved.
Manufacturer: Kennedy Valve, USA
1.06 OS&Y Gate valve, 200 psig, Ductile iron, Flanged end, 4
Model: 7068, Size: 8" fusion bond epoxy coated.
UL/FM Approved.
Manufacturer: Kennedy Valve, USA
1.07 OS&Y Gate valve, 200 psig, Ductile iron, Flanged end, 1
Model: 7068SS, Size: 2" fusion bond epoxy coated.
UL/FM Approved.
Manufacturer: Kennedy Valve, USA
1.08 Swing check valve, 175 psig, Cast iron, Flanged end, 2
Model: 1126A, Size: 10", rubber face disc.
UL/FM Approved.
Manufacturer: Kennedy Valve, USA
1.08 Swing check valve, 175 psig, Cast iron, Flanged end, 1
Model: 1106A, Size: 2", rubber face disc.
AWWA Approved.
Manufacturer: Kennedy Valve, USA
Project : SUPPLY & INSTALLATION OF TWO NEW DIESEL FIRE PUMP FOR MARAFIQ-YANBU STG 5 & 6 PLANT
1.13 NRS Gate valve, Model: A53, straightway pattern, forged brass, 8
solid wedge disc with tapered seat, 300 lbs. psi WP with
with red handwheel including cap and chain..
Size: 2.5" NHT inlet x 2.5" NPT outlet, For test manifold
UL/FM Approved.
Manufacturer.: Giacomini USA
1.14 Pressure sensing line, 1/2" Pipe with (4) - swing check 1
valve, 1/2", KT-403-W and (4) - ball valve, 1/2", set
KT-585-70-UL.
1.15 Fuel Oil Filling Line, 1" Pipe with (4) - swing check 1
valve, 1", KT-403-W, (2) - OS&Y gate valve, 2", T-104-O set
and (4) - Ball valve, 1", KT-585-70-UL, and Low switch
level, 403508.
1.17 Extinguisher, stored pressure type, Model: A411, 10-A:120-B:C, 2 3,018.00 6,036.00 905.40
Project : SUPPLY & INSTALLATION OF TWO NEW DIESEL FIRE PUMP FOR MARAFIQ-YANBU STG 5 & 6 PLANT
ABC Dry chemical powder, 20.0 lbs. capacity with CRCA metal
sheet wall mounted cabinet.
UL Listed.
Manufacturer: Amerex, USA
1.18 Alarm Check Valve assembly, 6" dia., Model: J-1, Flanged 1 21,500.00 21,500.00 3,225.00
end, P/N 08241 with complete set of the following; set
1 Variable pressure Vertical Galv. trim, P/N 08635
1 Retarding chamber, Model: C-1, P/N 05904B
2 Water pressure gauge, 0-300 psi, 1/4", VWATERSF
1 Pressure switch, PS102A
1 Water motor alarm and gong, Model: F-2, P/N 07862
1 Pressure relief valve, 1/2" ser 175 psi, Model: 7000
1 Water flow switch, VSRF
UL/FM Approved.
Manufacturer: Viking Corp., USA
1.19 OS&Y Gate valve, 200 psig, Ductile iron, Flanged end, 2 2,416.00 4,832.00 724.80
Model: 7068ASS, Size: 6" fusion bond epoxy coated.
Including supervisory/tamper switch, Model: OSYSU2
UL/FM Approved.
Manufacturer: Kennedy Valve, USA
1.20 Y-Strainer, 300 psig, Ductile iron, Flanged end, 1 1,673.00 1,673.00 250.95
Model: YSF0600, Size: 6" fusion bond epoxy coated.
UL/FM Approved.
Manufacturer: FireKing (Viking), USA
1.21 Microfast® Quick response upright sprinkler, glass bulb 16 16.00 256.00 38.40
type, Brass finished, 1/2" MNPT, Model: VK300, 175°F/79°C
thermal sensitivity, K-Factor = 5.6, P/N 12978AD.
UL/FM Approved.
Manufacturer: Viking Corp., USA
1.22 Test and drain valve with sight glass and stop valve, 1 1,237.00 1,237.00 185.55
for inspection, 1-1/2" size, Model: 1000, Orifice: 17/32".
UL/FM Approved.
Manufacturer: AGF, USA
1.23 Siamese connection, Cast brass, two-way inlet body with 1 4,486.00 4,486.00 672.90
double non-return flap and pin lug hose thread swivels, set
straight NPT outlet connection, Model: 156 4", Back outlet,
Project : SUPPLY & INSTALLATION OF TWO NEW DIESEL FIRE PUMP FOR MARAFIQ-YANBU STG 5 & 6 PLANT
1.24 Supply of piping material of the above sprinkler system 1 34,690.00 34,690.00 5,203.50
including pipe and fittings. Pipe shall be SMLS, A53 Gr. B, lot
S-40, Black steel, Fittings 2.5" - above shall be A234 WPB
and 2" - below shall be Class 150# NPT A105 Threaded end.
Including oil piping line. Pipe shall be painted externally
1.26 Vertical Heat Detector Weather proof, 24 VDC, 6 1,719.00 10,314.00 1,547.10
Model: 27121-20, 210ºF with backbox including
FMM-1 Monitor module and SMB-500 back box
UL/FM Approved.
Manufacturer: Fenwal, USA
Project : SUPPLY & INSTALLATION OF TWO NEW DIESEL FIRE PUMP FOR MARAFIQ-YANBU STG 5 & 6 PLANT
1.27 Horn, 28 user selectable tones, up to 120 dBA @ 10 ft., 3 4,161.00 12,483.00 1,872.45
integral volume control, 24 VDC, SS surface mounting
bracket, GRP housing and thermoplastic polyester flare
painted red, two 1/2" NPT entries, one plug, diode
polarized, Model: DB3B with FCM-1 control module and
explosion proof back box.
Class 1, Div. 2, Groups A-D, NEMA 4X
UL Listed
Manufacturer: MEDC, UK
1.29 XAL-53 Kilark Manual Station, explosion proof, 2 6,092.00 12,184.00 1,827.60
NO/NC contact with FMM-101 mini monitor
module and explosion proof back box.
UL/FM Approved.
Manufacturer: Notifier
1.27 FCM-1, Addressable Control Module with flashscan; configured 4 260.00 1,040.00 156.00
for one class A or class B NAC. With SMB-500 back Box.
UL/FM Approved.
Manufacturer: Notifier
1.28 FMM-1 Addressable Monitor Module with flashscan. Supervises 12 219.00 2,628.00 394.20
either a class A or class B circuit of N.D. dry contact
input devices. With SMB-500 backbox.
UL/FM Approved.
Manufacturer: Notifier
1.29 FRM-1 Addressable Relay Module with flashscan 2 249.00 498.00 74.70
with SMB-500 backbox.
UL/FM Approved.
Manufacturer: Notifier
Project : SUPPLY & INSTALLATION OF TWO NEW DIESEL FIRE PUMP FOR MARAFIQ-YANBU STG 5 & 6 PLANT
1.30 Supply of cables, conduit, fittings, hangers of the 1 64,935.00 64,935.00 9,740.25
above Fire pump and Fire alarm system. lot
2.03 FAT - Factory acceptance test of Fire Pump Skid assembly 1 44,340.00 44,340.00 6,651.00
including Packing/Marking/Transportation of Fire Pump lot
Skid assembly going to Marafiq - Yanbu Site
Project : SUPPLY & INSTALLATION OF TWO NEW DIESEL FIRE PUMP FOR MARAFIQ-YANBU STG 5 & 6 PLANT
2.06 Supervision works of piping outside fire pump house per day 5,000.00
Scope is from the Tie-in points in the existing potable charge
water tanks to the pumps skid suction header and from
the pumps skid discharge header to the tie-ins discharge
pipe per the communicated FEED package
3.00 NOTES:
- Our scope is technical documentation, procurement, manufacturing, packing,
storing, delivery to job site, installation/erection, supervision, testing
and commissioning for the above mentioned systems.
- For HCIS approval, Albilad will prepare the HCIS Installation package
and hand over to company representative/client for their submittal.
- Painting shall conforms with Project coating standard and specifications.
Project : SUPPLY & INSTALLATION OF TWO NEW DIESEL FIRE PUMP FOR MARAFIQ-YANBU STG 5 & 6 PLANT
4.00 DEVIATION/EXCLUSIONS:
- Fire water tank and its appurtenances
- Major civil works such as earth excavation, back filling,
thrust block, pipe trenches for road crossing, concrete
support foundation, guard post, tank/pump foundation, etc…
- Supply, installation & commission works for the Ventilation
system including all needed equipment
- Supply, installation & commission works for piping outside
the fire pump house
- Supply, installation and commission of instrumentation and
control system outside the fire pump house
- Integration of the new fire alarm system to the existing DCS
5.00 OPTIONAL
5.01 Civil works which include Construction of Fire pump 1 959,400.00 959,400.00 143,910.00
house and lighting works including concrete foundation lot
for Diesel Fire Pump skid base, Pipe support, etc..
Pump Room Approx. Size: 12L m x 10W m x 6.5H m