Hardware Interlocking and Functional Check Test Report - Feeder
Hardware Interlocking and Functional Check Test Report - Feeder
OPERATIONAL
CONDITION
STATUS
OPERATION
STATUS
NO
INSERTEDMECHANICAL HANDLE
REMOTE/BCUOFF/LOCAL/
LOCKOUTK33
INTERMEDIATE
CB SPRING
K34 TCS
POSITION
Q1/Q5
F20
Q1
Q5
WITNESS/APPROVED
TESTED BY CONTRACTOR CONSULTANT
BY
COMPANY ALPHA POWER LLC ADDC
NAME
SIGNATURE
DATE
SAT Format fro Functional Checks Page 1 of 5
PROJECT Contruction, Completion & Maintenance of 204 Villas, SWEIHAN, ALAIN.
CLIENT MUSANADA EQUIPMENT 11KV SWG. PANEL
END USER AADC FEEDER K02
CONSULTANT AL SUWEIDI
MAIN CONTRACTOR AL JABER BUILDING
SUB CONTRACTOR ALPHA POWER SCHEME NO
SUBSTATION No LOCATION AL SAAD
STATUSOPERATIONAL
CONDITION
OPERATION
STATUS
NO
INSERTEDMECHANICAL HANDLE
REMOTE/BCUOFF/LOCAL/
LOCKOUTK33
INTERMEDIATE
CB SPRING
K34 TCS
POSITION
Q1/Q5
F20
Q1
Q5
CONDITION
OPERATIO
NO STATUS OFF/LOCAL/ OPERATION STATUS
N
REMOTE
1 CLOSE OPEN L OPEN POSSIBLE
WITNESS/APPROVED
TESTED BY CONTRACTOR CONSULTANT
BY
COMPANY ALPHA POWER LLC ADDC
NAME
SIGNATURE
DATE
SAT Format fro Functional Checks Page 2 of 5
PROJECT Contruction, Completion & Maintenance of 204 Villas, SWEIHAN, ALAIN.
CLIENT MUSANADA EQUIPMENT 11KV SWG. PANEL
END USER AADC FEEDER K02
CONSULTANT AL SUWEIDI
MAIN CONTRACTOR AL JABER BUILDING
SUB CONTRACTOR ALPHA POWER SCHEME NO
SUBSTATION No LOCATION AL SAAD
Legend:
OFF Not operated/Open L Local
ON Operated/Closed R Remote
-- Not Applicable C Charged
Dis Discharge
U/H Unhealthy H Healthy
STATUSOPERATIONAL
INSERTEDMECHANICAL HANDLE
COMPARTMENT
(SLR)REMOTEOFF/LOCAL/
HV CABLE
OPERATION
MCB F11
STATUS
NO
Q0
Q5
DOOR OPEN
6
OPEN
OPEN
WITNESS/APPROVED
TESTED BY CONTRACTOR CONSULTANT
BY
COMPANY ALPHA POWER LLC ADDC
NAME
SIGNATURE
DATE
SAT Format fro Functional Checks Page 3 of 5
PROJECT Contruction, Completion & Maintenance of 204 Villas, SWEIHAN, ALAIN.
CLIENT MUSANADA EQUIPMENT 11KV SWG. PANEL
END USER AADC FEEDER K02
CONSULTANT AL SUWEIDI
MAIN CONTRACTOR AL JABER BUILDING
SUB CONTRACTOR ALPHA POWER SCHEME NO
SUBSTATION No LOCATION AL SAAD
3.EARTH SWITCH – Q5 :
(SLR)REMOTEOFF/LOCAL/
HEALTHYMCB F20
OPERATIONAL
VOLTAGE (KA51)
OPERATION
FEEDER NO
STATUS
STATUS
NO
Q0
Q1
10 -- -- -- ON -- OPEN POSSIBLE
OPEN
4.MECHANICAL INTERLOCK
WITNESS/APPROVED
TESTED BY CONTRACTOR CONSULTANT
BY
COMPANY ALPHA POWER LLC ADDC
NAME
SIGNATURE
DATE
SAT Format fro Functional Checks Page 4 of 5
PROJECT Contruction, Completion & Maintenance of 204 Villas, SWEIHAN, ALAIN.
CLIENT MUSANADA EQUIPMENT 11KV SWG. PANEL
END USER AADC FEEDER K02
CONSULTANT AL SUWEIDI
MAIN CONTRACTOR AL JABER BUILDING
SUB CONTRACTOR ALPHA POWER SCHEME NO
SUBSTATION No LOCATION AL SAAD
1 Q1 (Open, Close/Open
Q0 OPEN Y11 ON Q5 OFF
Close) Possible
2 Q5 (Open, Close/Open
Q0 OPEN Y10 ON Q1 OFF
Close) Possible
3 Q5 Closed -- Mechanical -- Opening not
lever locked Possible
6.REMARKS:
WITNESS/APPROVED
TESTED BY CONTRACTOR CONSULTANT
BY
COMPANY ALPHA POWER LLC ADDC
NAME
SIGNATURE
DATE
SAT Format fro Functional Checks Page 5 of 5