0% found this document useful (0 votes)
74 views127 pages

Report 2

The document provides standards and recommendations for thermography assessments according to ANSI/NETA-MTS 2007. It then lists items from a thermography survey conducted at a Sheraton Link facility. 61 items are listed with their location, observed temperature difference (dT), and a priority level of 0. The priority level of 0 indicates a recommended action of cleaning and inspection is required to maintain the component.

Uploaded by

Quraishi Mehraj
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
74 views127 pages

Report 2

The document provides standards and recommendations for thermography assessments according to ANSI/NETA-MTS 2007. It then lists items from a thermography survey conducted at a Sheraton Link facility. 61 items are listed with their location, observed temperature difference (dT), and a priority level of 0. The priority level of 0 indicates a recommended action of cleaning and inspection is required to maintain the component.

Uploaded by

Quraishi Mehraj
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 127

STANDARDS (ANSI/NETA-MTS 2007)

Thermography standard and level of acceptance is defined by ANSI/NETA-MTS 2007, this


Standard is global accepted.

Following are the acceptance/recommended actions given.

Priority wise Recommendations and actions :

[YOUR COMPANY ADRESS] | [YOUR COMPANY CONTACT DETAILS]


SUMMARY REPORT FOR SHERATON LINK

Sr. Panel name dT Priority Page


No. Number

1 LVS4/BB/1 3.6 0
2 MCCP/LL2/1 8.1 0
3 MCCP/32/2 5.1 0
LVS-4 (SECTION-B)
4 MAIN INCOMER 5.1 0
5 CAPACITOR BANK 8.4 0
6 LVS4/BB/3 4.3 0
7 LVS4/BB/4 2.8 0
8 FIRE PUMP SET 8.4 0
9 MCCP/L32/3 5.3 0
10 BUS COUPLER 5.3 0
11 UPS-L-14 6.8 0
12 SB/00/L345 4.9 0
13 SB/LL1/L67 5.8 0
14 SB/LL3/L12 5.4 0
15 MCCP/32/E1 7.0 0
16 MCCP/14/E/3 6.0 0
17 SB/34/E/1 4.6 0
18 SB/14/EP 4.1 0
19 SB/04//EP 7.1 0
20 LIFT-8 7.8 0
21 LIFT-5 (MAIN INCOMER) 3.8 0
22 CAPACITOR BANK 4.0 0
23 SDB/L15/01 5.2 0
24 SDB/L16/01 3.0 0
2 CAPACITOR BANK 7.0 0
26 LVS5/BB/1 3.4 0
27 LVS5/BB/2 5.1 0
28 LVS-PARKING (PSB) 6.0 0
29 DB-LL3/CP1 3.2 0
30 DB-LL1M-CP2 3.7 0
31 DB-LL1-CP1 6.5 0
32 DB-LL2-CP2 5.4 0
33 DB-LL2-LP3 9.5 0
34 DB-LL3-CP2 7.9 0
35 DB/LL1M/CP1 7.4 0
36 DB/LL1/CP2 5.5 0
37 DB/LL2/CP1 4.2 0
38 DR/00/P1 3.2 0
39 DB/01/P2 9.5 0
40 DB/00/VA 6.0 0
41 DR/LL1M/EX4 5.6 0
42 (FLOOR 30) SDB/30/01 5.7 0
43 (FLOOR-28) (SDB-28-01) 2.7 0
44 SDB/24/01 5.6 0
45 SDB/22/01 5.3 0
46 SDB/19/01 3.1 0
47 SDB/18/01 9.7 0
48 SDB/L15/01 2.5 0
49 SDB/15/EP 6.5 0
50 SDB/13/01 2.6 0
51 SDB/07/01 2.4 0
52 SDB/00/01 9.2 0
53 SB/01/LP 7.9 0
54 SB/01/AD 8.6 0
55 SB/01/BK 7.8 0
56 SB/00/JBK 9.6 0
57 SMDB-100/SR-2 3.8 0
58 SMDB-02-CM 4.1 0
59 SB/LL3/M1 4.5 0
60 SB/LL1/LP1 2.0 0
61 SB/LL1/L67 3.1 0
62
Equipment Name LVS4/BB/1 Date 22-12-2020
Operating Voltage 400V Load R-242.5A,Y-241.8A,B-
243.2A
Feeder OUTGOING Emissivity 0.95

FLIR1760.jpg | 22-Dec-20 | 8:43 AM

Measurements -
Spots
Bx1 Average 22.5 °C
Bx1 Maximum 25.2 °C
Bx1 Minimum 21.8 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 3.6 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name MCCP/LL2/1 Date 22-12-2020
Operating Voltage 400V Load R-10.11A,Y-8.86A,B-
12.42A
Feeder OUTGOING Emissivity 0.95

FLIR1761.jpg | 22-Dec-20 | 8:43 AM

Measurements -
Spots
Bx1 Average 22.4 °C
Bx1 Maximum 29.6 °C
Bx1 Minimum 21.9 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 8.1 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
MCCP/32/2 Date 22-12-2020
Equipment Name LVS-4 (SECTION-B)
Operating Voltage 400V Load R-0A,Y-0A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1762.jpg | 22-Dec-20 | 8:43 AM

Measurements -
Spots
Bx1 Average 22.4 °C
Bx1 Maximum 25.0 °C
Bx1 Minimum 21.9 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.1 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name MAIN INCOMER Date 22-12-2020
Operating Voltage 400V Load R-223.5A,Y-212.4A,B-
197.0A
Feeder INCOMER Emissivity 0.95

FLIR1764.jpg | 22-Dec-20 | 8:45 AM

Measurements -
Spots
Bx1 Average 22.9 °C
Bx1 Maximum 26.5 °C
Bx1 Minimum 21.7 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.1 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name CAPACITOR BANK Date 22-12-2020
Operating Voltage 400V Load R-0A,Y-0A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1765.jpg | 22-Dec-20 | 8:45 AM

Measurements -
Spots
Bx1 Average 23.1 °C
Bx1 Maximum 30.3 °C
Bx1 Minimum 22.0 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 8.4 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name LVS4/BB/3 Date 22-12-2020
Operating Voltage 400V Load R- 54A,Y-42A,B-52A
Feeder OUTGOING Emissivity 0.95

FLIR1766.jpg | 22-Dec-20 | 8:45 AM

Measurements -
Spots
Bx1 Average 22.7 °C
Bx1 Maximum 25.5 °C
Bx1 Minimum 21.9 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 4.3 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name LVS4/BB/4 Date 22-12-2020
Operating Voltage 400V Load R-64A,Y-52A,B-50A
Feeder OUTGOING Emissivity 0.95

FLIR1767.jpg | 22-Dec-20 | 8:46 AM

Measurements -
Spots
Bx1 Average 22.4 °C
Bx1 Maximum 23.3 °C
Bx1 Minimum 21.8 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 2.8 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name FIRE PUMP SET Date 22-12-2020
Operating Voltage 400V Load R-0.9A,Y-0.10A,B-
0.40A
Feeder OUTGOING Emissivity 0.95

FLIR1768.jpg | 22-Dec-20 | 8:46 AM

Measurements -
Spots
Bx1 Average 22.5 °C
Bx1 Maximum 29.0 °C
Bx1 Minimum 21.8 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 8.4 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name MCCP/L32/3 Date 22-12-2020
Operating Voltage 400V Load R-0A,Y-0A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1769.jpg | 22-Dec-20 | 8:46 AM

Measurements -
Spots
Bx1 Average 22.3 °C
Bx1 Maximum 25.3 °C
Bx1 Minimum 21.7 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.3 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name BUS COUPLER Date 22-12-2020
Operating Voltage 400V Load R-0A,Y-0A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1771.jpg | 22-Dec-20 | 8:47 AM

Measurements -
Spots
Bx1 Average 22.7 °C
Bx1 Maximum 26.1 °C
Bx1 Minimum 21.5 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.3 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name UPS-L-14 Date 22-12-2020
Operating Voltage 400V Load R-22.5A,Y-22.10A,B-
22.12A
Feeder OUTGOING Emissivity 0.95

FLIR1772.jpg | 22-Dec-20 | 8:47 AM

Measurements -
Spots
Bx1 Average 22.0 °C
Bx1 Maximum 27.8 °C
Bx1 Minimum 21.4 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 6.8 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SB/00/L345 Date 22-12-2020
Operating Voltage 400V Load R-6.5A,Y-0.74A,B-6.4A
Feeder OUTGOING Emissivity 0.95

FLIR1773.jpg | 22-Dec-20 | 8:47 AM

Measurements -
Spots
Bx1 Average 21.6 °C
Bx1 Maximum 24.1 °C
Bx1 Minimum 21.1 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 4.9 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SB/LL1/L67 Date 22-12-2020
Operating Voltage 400V Load R-4.68A,Y-2.75A,B-
7.55A
Feeder OUTGOING Emissivity 0.95

FLIR1774.jpg | 22-Dec-20 | 8:48 AM

Measurements -
Spots
Bx1 Average 21.4 °C
Bx1 Maximum 24.7 °C
Bx1 Minimum 20.8 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.8 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SB/LL3/L12 Date 22-12-2020
Operating Voltage 400V Load R-50A,Y-44A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1775.jpg | 22-Dec-20 | 8:48 AM

Measurements -
Spots
Bx1 Average 21.7 °C
Bx1 Maximum 24.6 °C
Bx1 Minimum 20.9 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.4 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name MCCP/32/E1 Date 22-12-2020
Operating Voltage 400V Load R-5.12A,Y-24.67A,B-
0.67A
Feeder OUTGOING Emissivity 0.95

FLIR1776.jpg | 22-Dec-20 | 8:48 AM

Measurements -
Spots
Bx1 Average 21.8 °C
Bx1 Maximum 26.4 °C
Bx1 Minimum 21.0 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 7.0 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name MCCP/14/E/3 Date 22-12-2020
Operating Voltage 400V Load R-2.4A,Y-2.59A,B-
2.63A
Feeder OUTGOING Emissivity 0.95

FLIR1777.jpg | 22-Dec-20 | 8:48 AM

Measurements -
Spots
Bx1 Average 21.3 °C
Bx1 Maximum 25.1 °C
Bx1 Minimum 20.7 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 6.0 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SB/34/E/1 Date 22-12-2020
Operating Voltage 400V Load R-1.6A,Y-1.4A,B-1.7A
Feeder OUTGOING Emissivity 0.95

FLIR1778.jpg | 22-Dec-20 | 8:49 AM

Measurements -
Spots
Bx1 Average 21.7 °C
Bx1 Maximum 24.0 °C
Bx1 Minimum 20.9 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 4.6 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SB/14/EP Date 22-12-2020
Operating Voltage 400V Load R-2.60A,Y-7.17A,B-
6.60A
Feeder OUTGOING Emissivity 0.95

FLIR1779.jpg | 22-Dec-20 | 8:49 AM

Measurements -
Spots
Bx1 Average 21.3 °C
Bx1 Maximum 22.7 °C
Bx1 Minimum 20.6 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 4.1 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SB/04//EP Date 22-12-2020
Operating Voltage 400V Load R-0.6A,Y-1.32A,B-
0.54A
Feeder OUTGOING Emissivity 0.95

FLIR1780.jpg | 22-Dec-20 | 8:49 AM

Measurements -
Spots
Bx1 Average 20.9 °C
Bx1 Maximum 25.5 °C
Bx1 Minimum 20.4 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 7.0 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name LIFT-8 Date 22-12-2020
Operating Voltage 400V Load R-30.12A,Y-11.5A,B-
5.42A
Feeder OUTGOING Emissivity 0.95

FLIR1781.jpg | 22-Dec-20 | 8:49 AM

Measurements -
Spots
Bx1 Average 21.1 °C
Bx1 Maximum 26.4 °C
Bx1 Minimum 20.5 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 7.8 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
LIFT-5 Date 22-12-2020
Equipment Name MAIN INCOMER
Operating Voltage 400V Load R-138.4A,Y-168A,B-
112.4A
Feeder INCOMER Emissivity 0.95

FLIR1782.jpg | 22-Dec-20 | 9:27 AM

Measurements -
Spots
Bx1 Average 21.2 °C
Bx1 Maximum 23.2 °C
Bx1 Minimum 20.6 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 3.1 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name CAPACITOR BANK Date 22-12-2020
Operating Voltage 400V Load R-0A,Y-0A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1783.jpg | 22-Dec-20 | 9:28 AM

Measurements -
Spots
Bx1 Average 21.3 °C
Bx1 Maximum 23.0 °C
Bx1 Minimum 20.9 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 4.0 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SDB/L15/01 Date 22-12-2020
Operating Voltage 400V Load R-4.78A,Y-3.83A,B-
4.02A
Feeder OUTGOING Emissivity 0.95

FLIR1784.jpg | 22-Dec-20 | 9:28 AM

Measurements -
Spots
Bx1 Average 21.1 °C
Bx1 Maximum 24.0 °C
Bx1 Minimum 20.7 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.2 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SDB/L16/01 Date 22-12-2020
Operating Voltage 400V Load R-6.04A,Y-9.42A,B-
2.06A
Feeder OUTGOING Emissivity 0.95

FLIR1785.jpg | 22-Dec-20 | 9:28 AM

Measurements -
Spots
Bx1 Average 21.5 °C
Bx1 Maximum 22.1 °C
Bx1 Minimum 21.0 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 3.0 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name CAPACITOR BANK Date 22-12-2020
Operating Voltage 400V Load R-0A,Y-0A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1786.jpg | 22-Dec-20 | 9:28 AM

Measurements -
Spots
Bx1 Average 21.6 °C
Bx1 Maximum 26.6 °C
Bx1 Minimum 20.9 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 7.0 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name LVS5/BB/1 Date 22-12-2020
Operating Voltage 400V Load R-0A,Y-0A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1787.jpg | 22-Dec-20 | 9:28 AM

Measurements -
Spots
Bx1 Average 21.6 °C
Bx1 Maximum 23.0 °C
Bx1 Minimum 21.1 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 3.4 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name LVS5/BB/2 Date 22-12-2020
Operating Voltage 400V Load R-0A,Y-0A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1788.jpg | 22-Dec-20 | 9:30 AM

Measurements -
Spots
Bx1 Average 20.6 °C
Bx1 Maximum 23.3 °C
Bx1 Minimum 20.0 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.1 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name LVS-PARKING (PSB) Date 22-12-2020
Operating Voltage 400V Load R-40.8A,Y-50.5A,B-
50.6A
Feeder OUTGOING Emissivity 0.95

FLIR1789.jpg | 22-Dec-20 | 10:33 AM

Measurements -
Spots
Bx1 Average 22.8 °C
Bx1 Maximum 27.6 °C
Bx1 Minimum 22.0 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 6.0 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name DB-LL3/CP1 Date 22-12-2020
Operating Voltage 400V Load R-5.1A,Y-2.7A,B-2.7A
Feeder OUTGOING Emissivity 0.95

FLIR1790.jpg | 22-Dec-20 | 10:34 AM

Measurements -
Spots
Bx1 Average 23.6 °C
Bx1 Maximum 24.5 °C
Bx1 Minimum 23.0 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 3.2 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name DB-LL1M-CP2 Date 22-12-2020
Operating Voltage 400V Load R-3.84A,Y-10.32A,B-
5.85A
Feeder OUTGOING Emissivity 0.95

FLIR1791.jpg | 22-Dec-20 | 10:34 AM

Measurements -
Spots
Bx1 Average 23.4 °C
Bx1 Maximum 24.8 °C
Bx1 Minimum 22.7 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 3.7 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name DB-LL1-CP1 Date 22-12-2020
Operating Voltage 400V Load R-5.6A,Y-7.2A,B-9.9A
Feeder OUTGOING Emissivity 0.95

FLIR1792.jpg | 22-Dec-20 | 10:35 AM

Measurements -
Spots
Bx1 Average 22.9 °C
Bx1 Maximum 27.0 °C
Bx1 Minimum 22.1 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 6.5 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name DB-LL2-CP2 Date 22-12-2020
Operating Voltage 400V Load R-4.5A,Y-2.7A,B-5.8A
Feeder OUTGOING Emissivity 0.95

FLIR1793.jpg | 22-Dec-20 | 10:35 AM

Measurements -
Spots
Bx1 Average 22.4 °C
Bx1 Maximum 25.6 °C
Bx1 Minimum 21.7 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.4 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name DB-LL2-LP3 Date 22-12-2020
Operating Voltage 400V Load R-0A,Y-8.6A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1794.jpg | 22-Dec-20 | 10:35 AM

Measurements -
Spots
Bx1 Average 22.4 °C
Bx1 Maximum 32.5 °C
Bx1 Minimum 21.6 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 9.5 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name DB-LL3-CP2 Date 22-12-2020
Operating Voltage 400V Load R-5.16A,Y-4.68A,B-
5.61A
Feeder OUTGOING Emissivity 0.95

FLIR1795.jpg | 22-Dec-20 | 10:35 AM

Measurements -
Spots
Bx1 Average 23.2 °C
Bx1 Maximum 28.7 °C
Bx1 Minimum 22.6 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 7.9 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name DB/LL1M/CP1 Date 22-12-2020
Operating Voltage 400V Load R-10.37A,Y-6.23A,B-
2.88A
Feeder OUTGOING Emissivity 0.95

FLIR1796.jpg | 22-Dec-20 | 10:35 AM

Measurements -
Spots
Bx1 Average 23.1 °C
Bx1 Maximum 28.3 °C
Bx1 Minimum 22.2 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 7.4 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name DB/LL1/CP2 Date 22-12-2020
Operating Voltage 400V Load R-2.8A,Y-8.2A,B-
4.28A
Feeder OUTGOING Emissivity 0.95

FLIR1797.jpg | 22-Dec-20 | 10:35 AM

Measurements -
Spots
Bx1 Average 22.7 °C
Bx1 Maximum 25.9 °C
Bx1 Minimum 22.0 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.5 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name DB/LL2/CP1 Date 22-12-2020
Operating Voltage 400V Load R-2.32A,Y-3.5A,B-4.3A
Feeder OUTGOING Emissivity 0.95

FLIR1798.jpg | 22-Dec-20 | 10:35 AM

Measurements -
Spots
Bx1 Average 22.3 °C
Bx1 Maximum 24.1 °C
Bx1 Minimum 21.5 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 4.2 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name DR/00/P1 Date 22-12-2020
Operating Voltage 400V Load R-0.10A,Y-11.8A,B-
12.5A
Feeder OUTGOING Emissivity 0.95

FLIR1799.jpg | 22-Dec-20 | 10:35 AM

Measurements -
Spots
Bx1 Average 22.7 °C
Bx1 Maximum 23.3 °C
Bx1 Minimum 22.2 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 3.2 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name DB/01/P2 Date 22-12-2020
Operating Voltage 400V Load R-0.82A,Y-0.99A,B-
1.2A
Feeder OUTGOING Emissivity 0.95

FLIR1800.jpg | 22-Dec-20 | 10:36 AM

Measurements -
Spots
Bx1 Average 22.5 °C
Bx1 Maximum 33.5 °C
Bx1 Minimum 21.9 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 9.5 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name DB/00/VA Date 22-12-2020
Operating Voltage 400V Load R-0A,Y-0A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1801.jpg | 22-Dec-20 | 10:36 AM

Measurements -
Spots
Bx1 Average 22.3 °C
Bx1 Maximum 27.3 °C
Bx1 Minimum 21.7 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 6.0 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name DR/LL1M/EX4 Date 22-12-2020
Operating Voltage 400V Load R-0A,Y-0A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1802.jpg | 22-Dec-20 | 10:36 AM

Measurements -
Spots
Bx1 Average 22.3 °C
Bx1 Maximum 25.7 °C
Bx1 Minimum 21.7 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.6 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
(FLOOR 30) Date 22-12-2020
Equipment Name SDB/30/01
Operating Voltage 400V Load R-35A,Y-10.2A,B-
18.5A
Feeder OUTGOING Emissivity 0.95

FLIR1803.jpg | 22-Dec-20 | 12:19 PM

Measurements -
Spots
Bx1 Average 26.1 °C
Bx1 Maximum 30.9 °C
Bx1 Minimum 24.7 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.7 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
(FLOOR-28) Date 22-12-2020
Equipment Name (SDB-28-01)
Operating Voltage 400V Load R-24A,Y-2.6A,B-8.6A
Feeder OUTGOING Emissivity 0.95

FLIR1804.jpg | 22-Dec-20 | 12:23 PM

Measurements -
Spots
Bx1 Average 28.1 °C
Bx1 Maximum 28.6 °C
Bx1 Minimum 27.6 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 2.5 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SDB/24/01 Date 22-12-2020
Operating Voltage 400V Load R-11A,Y-7.5A,B-7.8A
Feeder OUTGOING Emissivity 0.95

FLIR1805.jpg | 22-Dec-20 | 12:29 PM

Measurements -
Spots
Bx1 Average 26.1 °C
Bx1 Maximum 30.8 °C
Bx1 Minimum 25.4 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.6 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SDB/22/01 Date 22-12-2020
Operating Voltage 400V Load R-3.9A,Y-5.7A,B-5.5A
Feeder OUTGOING Emissivity 0.95

FLIR1806.jpg | 22-Dec-20 | 12:34 PM

Measurements -
Spots
Bx1 Average 27.4 °C
Bx1 Maximum 31.5 °C
Bx1 Minimum 25.9 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 5.3 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SDB/19/01 Date 22-12-2020
Operating Voltage 400V Load R-3.9A,Y-5.5A,B-4.7A
Feeder OUTGOING Emissivity 0.95

FLIR1807.jpg | 22-Dec-20 | 12:44 PM

Measurements -
Spots
Bx1 Average 29.8 °C
Bx1 Maximum 32.1 °C
Bx1 Minimum 28.9 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 3.1 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SDB/18/01 Date 22-12-2020
Operating Voltage 400V Load R-11.2A,Y-5.5A,B-4.2A
Feeder OUTGOING Emissivity 0.95

FLIR1808.jpg | 22-Dec-20 | 12:48 PM

Measurements -
Spots
Bx1 Average 25.5 °C
Bx1 Maximum 33.7 °C
Bx1 Minimum 23.8 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 9.7 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SDB/L15/01 Date 22-12-2020
Operating Voltage 400V Load R-0A,Y-0A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1809.jpg | 22-Dec-20 | 12:54 PM

Measurements -
Spots
Bx1 Average 28.7 °C
Bx1 Maximum 29.2 °C
Bx1 Minimum 28.3 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 2.5 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SDB/15/EP Date 22-12-2020
Operating Voltage 400V Load R-17A,Y-27A,B-24A
Feeder OUTGOING Emissivity 0.95

FLIR1810.jpg | 22-Dec-20 | 12:57 PM

Measurements -
Spots
Bx1 Average 21.0 °C
Bx1 Maximum 25.1 °C
Bx1 Minimum 20.3 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 6.5 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SDB/13/01 Date 22-12-2020
Operating Voltage 400V Load R-10.9A,Y-9.5A,B-
11.5A
Feeder OUTGOING Emissivity 0.95

FLIR1811.jpg | 22-Dec-20 | 12:59 PM

Measurements -
Spots
Bx1 Average 23.4 °C
Bx1 Maximum 23.9 °C
Bx1 Minimum 22.8 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 2.6 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SDB/07/01 Date 22-12-2020
Operating Voltage 400V Load R-9.5A,Y-14.9A,B-
12.4A
Feeder OUTGOING Emissivity 0.95

FLIR1812.jpg | 22-Dec-20 | 1:03 PM

Measurements -
Spots
Bx1 Average 26.3 °C
Bx1 Maximum 26.9 °C
Bx1 Minimum 25.8 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 2.4 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SDB/00/01 Date 22-12-2020
Operating Voltage 400V Load R-0A,Y-0A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1814.jpg | 22-Dec-20 | 1:15 PM

Measurements -
Spots
Bx1 Average 28.1 °C
Bx1 Maximum 35.1 °C
Bx1 Minimum 26.2 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 9.2 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SB/01/LP Date 22-12-2020
Operating Voltage 400V Load R-11A,Y-12A,B-11A
Feeder OUTGOING Emissivity 0.95

FLIR1815.jpg | 22-Dec-20 | 1:15 PM

Measurements -
Spots
Bx1 Average 28.1 °C
Bx1 Maximum 34.3 °C
Bx1 Minimum 26.5 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 7.9 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SB/01/AD Date 22-12-2020
Operating Voltage 400V Load R-13.2A,Y-22.8A,B-
23A
Feeder OUTGOING Emissivity 0.95

FLIR1816.jpg | 22-Dec-20 | 1:15 PM

Measurements -
Spots
Bx1 Average 28.5 °C
Bx1 Maximum 35.1 °C
Bx1 Minimum 26.6 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 8.6 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SB/01/BK Date 22-12-2020
Operating Voltage 400V Load R-0.2A,Y-0A,B-0A
Feeder OUTGOING Emissivity 0.95

FLIR1817.jpg | 22-Dec-20 | 1:19 PM

Measurements -
Spots
Bx1 Average 22.6 °C
Bx1 Maximum 28.9 °C
Bx1 Minimum 22.0 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 7.8 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SB/00/JBK Date 22-12-2020
Operating Voltage 400V Load R-8.7A,Y-1.5A,B-0.5A
Feeder OUTGOING Emissivity 0.95

FLIR1818.jpg | 22-Dec-20 | 1:23 PM

Measurements -
Spots
Bx1 Average 20.8 °C
Bx1 Maximum 28.7 °C
Bx1 Minimum 19.6 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 9.6 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SMDB-100/SR-2 Date 22-12-2020
Operating Voltage 400V Load R-23A,Y-20A,B-19A
Feeder OUTGOING Emissivity 0.95

FLIR1819.jpg | 22-Dec-20 | 1:34 PM

Measurements -
Spots
Bx1 Average 25.1 °C
Bx1 Maximum 27.3 °C
Bx1 Minimum 24.1 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 3.8 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SMDB-02-CM Date 22-12-2020
Operating Voltage 400V Load R-76A,Y-54A,B-51A
Feeder OUTGOING Emissivity 0.95

FLIR1820.jpg | 22-Dec-20 | 1:34 PM

Measurements -
Spots
Bx1 Average 24.4 °C
Bx1 Maximum 26.9 °C
Bx1 Minimum 23.0 °C
Ellipses -
Lines -
Dt1 (Ref.temp - Bx1.Max) 4.1 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SB/LL3/M1 Date 22-12-2020
Operating Voltage 400V Load R-0.14A,Y-0.15A,B-
0.22A
Feeder OUTGOING Emissivity 0.95

FLIR1821.jpg | 22-Dec-20 | 1:42 PM

Measurements -
Spots
Bx1 Average 24.5 °C
Bx1 Maximum 28.1 °C
Bx1 Minimum 23.6 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 4.5 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SB/LL1/LP1 Date 22-12-2020
Operating Voltage 400V Load R-26A,Y-32A,B-50A
Feeder OUTGOING Emissivity 0.95

FLIR1822.jpg | 22-Dec-20 | 1:49 PM

Measurements -
Spots
Bx1 Average 26.9 °C
Bx1 Maximum 27.9 °C
Bx1 Minimum 26.4 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 2.0 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits
Equipment Name SB/LL1/L67 Date 22-12-2020
Operating Voltage 400V Load R-3.5A,Y-2.4A,B-5.4A
Feeder OUTGOING Emissivity 0.95

FLIR1823.jpg | 22-Dec-20 | 1:52 PM

Measurements -
Spots
Bx1 Average 20.1 °C
Bx1 Maximum 20.6 °C
Bx1 Minimum 19.5 °C
Ellipses -
Lines -
Dt1 (Bx1.Max - Ref.temp) 3.1 °C
- -

Parameters
Emissivity 0.95
Reflected temperature 20.0 °C
Distance 1.0 m
Atmospheric temperature 20.0 °C
Relative humidity 50%
External optics temperature 20.0 °C
External optics transmission 1.00
Sl.No Analysis and Observation Recommendations

Thermal imaging was taken on Cable


1
Termination on incomer Cleaning and inspection are required to keep
the component in 0 Priority.
2 Temperature difference are in safe limits