00 - MS - Fire Alarm System Installation
00 - MS - Fire Alarm System Installation
FOR
FIRE ALARM SYSTEM INSTALLATION
TABLE OF CONTENTS
1. SCOPE
2. DEFINITIONS
4. OPERATION
6. RESPONSIBILITIES
7. MANPOWER REQUIRED
8. MATERIALS REQUIREMENTS
9. EQUIPMENTS REQUIREMENTS
13. DISTRIBUTION
1. SCOPE
This procedure to clear the method of the supply, installations of Fire
Alarm system for the project.
This document details the Fire Alarm system Installation:
1. Preparation of work.
2. Delivery and inspection upon arrival of material at site.
3. Installation of the system.
2. DEFINITIONS
PQP : Project Quality Plan
MS : Method Statement
Specific safety measures have to follow as applicable, and all the safety
measures are covered separately in the project safety plan.
4. OPERATION
Material:
Make sure that civil clearance done prior to start the installation.
Installation will be carried out as per manufacturer recommendations
Approved shop drawings and project specifications.
Installation:
Verify that hardware and devices are NRTL listed for use with fire-
alarm system before making connections.
Make addressable connections with a supervised interface device to
the following devices and systems.
Install the interface device less than 3 feet (1 m) from the device
controller.
Make an addressable confirmation connection when such feedback is
available at the device or system being controlled as follows :
1. Alarm-initiating connection to smoke-control system (smoke
management) at fire-fighter smoke-control system panel.
2. Alarm-initiating connection to stairwell and elevator-shaft pressurization
systems.
3. Smoke dampers in air ducts of designated air-conditioning duct
systems.
4. Alarm-initiating connection to elevator recall system and components.
5. Alarm-initiating connection to activate emergency lighting control.
6. Alarm-initiating connection to activate emergency shutoffs for gas and
fuel supplies.
7. Supervisory connections at valve supervisory switches.
8. Supervisory connections at low-air-pressure switch of each dry-pipe
sprinkler system.
9. Supervisory connections at elevator shunt trip breaker.
10. Supervisory connections at fire-pump power failure including a dead-
phase or phase reversal condition.
11. Supervisory connections at fire-pump engine control panel.
Installation of Components:
The devices/peripherals (Smoke detectors, heat detectors, break glass,
duct detectors, beam detectors, control and monitoring modules) are
connected in Class A circuit with the Control panels.
The speakers & speaker with strobes are connected in Class A circuit
with the Control panels.
2 Core 1.5mm2 FP 200 cable to be used for cabling the Initiating
Device Circuits (IDC) to the panel, additional 2c x 2.5mm2 FP200 cable
is required for the smoke detector with sounder base for the activation
of the sounders units.
2 core 1.5mm2 FP 200 cable to be used for cabling the Speakers with
the panel, additional 2c x 2.5mm2 FP200 cable is required from the
FACP for the speaker with strobe for the activation of the strobe unit
allied in vertical walls the run of conduit will be kept straight.
Comply with NFPA 72 for installation of fire-alarm equipment.
Smoke-Detector OR Heat-Detector
Comply with NFPA 72, “Smoke-Sensing Fire Detectors” & “Heat-
Sensing Fire Detectors”.
Smooth ceiling spacing shall not exceed 30 feet (9 m).
Fire-Alarm Control Unit: Surface mounted, with tops of cabinets not
more than 72 inches (1830 mm) above the finished floor.
Annunciator: Install with top of panel not more than 72 inches (1830
mm) above the finished floor.
Installation of Wires:
Grounding:
Identification:
Programming
After making sure all the system installed in correct way from
Subcontractor and supplier, programming of the system must
take place before final testing and commissioning accourding
to Consultant requirement and senario of the system.
Testing and commissioning of the system submitted separetly
for this system mentioned all the procedure of Testing of the
system and commissioning it.
Technical Assistance:
PROJECT MANAGER
1. To ensure that all the preparation and application works are
carried out according to the Contract Specification and with the
approved drawings.
SITE ENGINEER
1. To ensure that the works are carried out according to the
Contract Specification, approved method statement and the
shop drawings.
FOREMAN
1. The foreman will carry out his duties by maintaining continuous
coordination with the site engineer on daily basis, and ensure
proper distribution of the work force on the required and planned
locations.
SAFETY ENGINEER
1. Ensure the implementation of all the safety measures in
accordance with the HSE plan and everybody aware of it for it’s
proper implementation.
3. Inspect all the site activities and train the person to prevent
accidents and it’s proper implementation.
7. MANPOWER REQUIRED
Charge hand and Experienced Technicians
8. MATERIALS REQUIREMENTS
FAS Components and Accessories.
9. EQUIPMENTS REQUIREMENTS
The Equipment that will be engaged for Fire Alarm System Installation will
be as follows:
1. Power source
2. Drilling machine
3. Tool Box
4. Measuring Tape
5. Calibrated Ohm Meter / Multi meter
6. Ladders / Scaffoldings
7. Hammer
8. Safety requirements tools such as safety shoes, safety helmet, safety
glasses, fluorescent vest, and safety gloves to ensure maximum ability
of safe work and dust mask when required.
13. DISTRIBUTION
Copy of this method statement shall be issued to the following for
information/ action/ comments:
1. Project Manager
2. Site Engineer
3. Foremen
4. Safety Engineer
6. Store Keeper