COMMENTS RESOLUTION SHEET
Attached the Equipment GA Dwg & Equipment load data applied in STAAD file.
In the absence of the Eqp. load data at its supporting point / level, applied loads in STAAD file can't be reviewed.
Attach the Structural GA & detail dwg in the calculation report along with connection design & details.
Basic STAAD load cases shall be added for the Equipment Empty & Operating condition.
Accordingly Load combinations shall be updated.
In Dead load case, only Permanent action loads arising due to structure self weight, fireproofing, Floor material,
Handrail, Ladder etc. only needs to be applied. Equipment load as applied in furnished STAAD file shall be applied as
mentioned in above point no-3.
Structure shall be checked for Geometric imperfection horizontal load (EHF).
Accordingly load case and combinations shall be added.
Add list of all the relevant Codes, referred during designing the structure.
Attach STAAD output report with the calculation report
Proposed location of ACHE supporting structure is at plant building Roof floor i.e. above +32.5m elevation from Ground.
Terrain roughness factor (Cr), Mean wind velocity (Vm),
Turbulence Intensity (Iv) and Wind pressure (qp) shall be calculated for the height (z) where it is proposed to place.
Updated
Updated
updated
Added
Added as Annexure
we have qualified Majority of Members within the commented utilization ratio and only
very minor members ratio is close to 0.95. since the load is factored many tmes kindly
allow the utilization ratio up to 1.
updated
updated
Taken Full Length for design, Bracings are not considered for reduction in Lengths of Main Beams
updated
updated
updated
calc updated
updated
updated
updated
updated
we have qualified Majority of Members within the commented utilization ratio and only
very minor members ratio is close to 0.95. since the load is factored many tmes kindly
allow the utilization ratio up to 1.