This document answers questions about the integration
of an OSIsoft® PI Server with the DeltaV™ system.
Enterprise Historian FAQs October 2015
1. Introduction
Terminology
This whitepaper answers questions about the integration of an OSIsoft PI Server with the DeltaV system. In this document, the
following terminology is used.
PI Server: the real-time data collection, archiving, and distribution engine that powers the PI System™; sold and supported
by OSIsoft.
Embedded Enterprise Historian: a PI Server installed on a DeltaV Application Station and configured for use as the
DeltaV system historian.
Integrated Enterprise Historian: a PI Server installed on a non-DeltaV PC and configured for use as the
DeltaV system historian.
Enterprise Historian: this term is used when the question or answer is applicable to both the Embedded and Integrated
Enterprise Historian.
Site PI Server: a PI Server installed on a non-DeltaV PC, at a network level above the control system, used to collect data
from multiple and various data sources and distribute this data to process engineers and business users; sold and
supported by OSIsoft.
Legacy Historian: the real-time process data system historian on all new DeltaV systems from v3.3 through v7.3, which was
based on PI Server technology. It was possible to keep the Legacy Historian on the Application Station during DeltaV system
upgrades up to and including DeltaV system v11.3.1.
DeltaV Continuous Historian: the real-time process data system historian on all new DeltaV systems from v7.4 to the
present, developed by Emerson and installed on every DeltaV workstation.
Advanced Continuous Historian: a real-time process data system historian powered by OSIsoft technology, available as an
optional historian on DeltaV Application Stations in DeltaV system v12.3.1 and later versions.
1.3. What is the difference between the Embedded and the Integrated Enterprise Historian?
The difference between the Embedded Enterprise Historian and Integrated Enterprise Historian is the location of the PI Server. In the
Embedded Enterprise Historian architecture, the PI Server is located on a DeltaV Application Station. In the Integrated Enterprise
Historian architecture, the PI Server is located on a non-DeltaV PC in a higher level network. Aside from the location of the PI Server,
the two options are identical.
www.emersonprocess.com 2
Enterprise Historian FAQs October 2015
1.7. Does the Enterprise Historian replace the DeltaV Continuous Historian?
The DeltaV Continuous Historian remains the preferred continuous historian in the DeltaV system and will continue to be installed
on each DeltaV workstation. The Enterprise Historian is an option which may be used in place of or in addition to the DeltaV
Continuous Historian.
1.8. How is the Enterprise Historian different from using a site PI Server in my system today?
The Enterprise Historian is integrated into in the DeltaV system; in much the same way as the DeltaV Continuous Historian (or the
Legacy Historian before it) is integrated into the DeltaV system. The Enterprise Historian functions as a full featured DeltaV system
historian. Once the Enterprise Historian is installed, it is configured using the DeltaV engineering tools and used by the DeltaV
historian client applications. If you are using a site PI Server in your system today, you have to configure the site PI Server using
OSIsoft configuration tools and maintain separate interfaces to collect data from the DeltaV system. The DeltaV historian client
applications may or may not be able to view history data in the PI Server depending upon the PI tag syntax and the PI Server licenses
available. The Enterprise Historian eliminates the need to use non-native DeltaV engineering tools to configure history collection
and ensures that the DeltaV historian client applications can view history data.
1.9. How is the Enterprise Historian different from the Advanced Continuous Historian?
The Enterprise Historian is a full featured PI Server with enterprise historian capability and connectivity to all PI client applications.
The Enterprise Historian can be installed on a DeltaV Application Station as the Embedded Enterprise Historian or installed on a
non-DeltaV PC as the integrated Enterprise Historian. The Advanced Continuous Historian is based on OSIsoft technology and has
the features and capabilities required for a DeltaV system historian. However the Advanced Continuous Historian allows a limited
set of PI client applications and is only available on an Application Station. Both the Enterprise Historian and Advanced Continuous
Historian are well integrated into the DeltaV system and are available as optional historian platforms in the DeltaV system; the
primary differences are the features, functionality, and price of each platform. For more details on the Advanced Continuous
Historian, refer to the Advanced Continuous Historian product data sheet and the Advanced Continuous Historian FAQ white paper
available on the Emerson DeltaV website.
www.emersonprocess.com 3
Enterprise Historian FAQs October 2015
1.12. Does the Enterprise Historian provide all the functionality of the Legacy Historian?
Yes. More details on the Enterprise Historian functionality may be found later in this document.
1.17. If I have two DeltaV Application Stations sending data to an Integrated Enterprise Historian, do I
need licenses for both Application Stations?
Yes. The Integrated Enterprise Historian requires a DeltaV OPC DA Server license and Enterprise Historian Configuration Interface
license from Emerson for each DeltaV Application Station providing data to the Integrated Enterprise Historian. In addition, you will
need a DeltaV Smart Connector license for each Application Station. Note, however, you will only need one PI Server.
www.emersonprocess.com 4
Enterprise Historian FAQs October 2015
1.18. Do I need a DeltaV Continuous Historian or Legacy Historian license to use the
Enterprise Historian?
No. The Enterprise Historian is licensed separately from the DeltaV Continuous Historian and Legacy Historian.
1.21. Who can I speak with to get more information on the Enterprise Historian options?
If you need to speak with someone regarding the Enterprise Historian options, you can find the appropriate Emerson sales and/or
support contacts for your world area at this website: http://www.emersonprocess.com/systems/support/ratecard.htm or the
appropriate OSI sales and/or support contacts at this website: http://www.osisoft.com/contactus/keycontacts. In addition, you
can email OSIsoft with technical questions at [email protected] or commercial questions at [email protected].
www.emersonprocess.com 5
Enterprise Historian FAQs October 2015
2. Architecture
2.1. Where does the Embedded Enterprise Historian reside?
The Embedded Enterprise Historian may be installed on any Application Station of a DeltaV system at version v10.3 and higher.
The recommended system architecture is to run all necessary components for the Embedded Enterprise Historian on a single
Application Station. The minimum software components required for the Embedded Enterprise Historian are the OSIsoft PI Server,
OSIsoft DeltaV Smart Connector and DeltaV OPC DA Server.
2.3. How does the Enterprise Historian collect data from the DeltaV system?
The Enterprise Historian is configured from DeltaV Explorer or DeltaV Control Studio just like history collection is configured for the
DeltaV Continuous Historian or Legacy Historian. When the Continuous Historian subsystem is downloaded, the DeltaV historian
configuration information is read by the DeltaV Asset Connector. The DeltaV Asset Connector creates the appropriate tags in the
Enterprise Historian and configures the PI OPC DA interface to retrieve data from the DeltaV OPC DA Server at the appropriate scan
rate. The PI OPC DA interface then populates data in the PI tags configured in the Enterprise Historian.
2.4. How many Embedded Enterprise Historians may I have in one DeltaV system?
You may have as many Embedded Enterprise Historian in your DeltaV system as you have DeltaV Application Stations, up to
the maximum number of supported Application Stations (for DeltaV system v10.3 and later versions the maximum number of
Application Stations is 20).
2.5. How many Integrated Enterprise Historians may I have in one DeltaV system?
You may have as many integrated Enterprise Historian in your DeltaV system as you need, but the expectation is that you will have
one Integrated Enterprise Historian per DeltaV system and even one Integrated Enterprise Historian for multiple DeltaV systems.
2.6. Can I have a DeltaV Continuous Historian and an Enterprise Historian in the same DeltaV system?
You may have one or more DeltaV Continuous Historians and one or more Enterprise Historians in your DeltaV system as long as
they reside on separate DeltaV workstations. You may not have multiple historians on any one DeltaV workstation.
2.7. Can I have an Embedded Enterprise Historian and an integrated Enterprise Historian in the same
DeltaV system?
You may have one or more Embedded Enterprise Historians and one or more Integrated Enterprise Historians in your DeltaV system
as long as the Embedded Enterprise Historian and the DeltaV Smart Connector associated with the Integrated Enterprise Historian
reside on separate DeltaV Application Stations. You may not have multiple Enterprise Historians on a single Application Station.
2.8. If I use an Enterprise Historian, do I also need to have a DeltaV Continuous Historian in the
same system?
Use of the Enterprise Historian does not require a DeltaV Continuous Historian. When the Enterprise Historian is used with the
DeltaV system, it is integrated into the Continuous Historian subsystem on the Application Station.
www.emersonprocess.com 6
Enterprise Historian FAQs October 2015
2.14. Does the Enterprise Historian collect DeltaV parameter status information?
The Enterprise Historian can be configured to collect DeltaV parameter status information, but the status parameter must be
configured for history collection separately from the parameter value. The Enterprise Historian does not have the capability to
automatically store the parameter status with the data value like the DeltaV Continuous Historian.
www.emersonprocess.com 7
Enterprise Historian FAQs October 2015
2.15. How many DeltaV parameters can I collect in the Embedded Enterprise Historian?
The recommended system architecture for the Embedded Enterprise Historian is to have all DeltaV and PI components installed on
one DeltaV Application Station, which means there is a one to one relationship between the DeltaV OPC DA Server and the DeltaV
Smart Connector. The DeltaV OPC DA Server has a capacity of 30,000 OPC data values per DeltaV Application Station. Thus, in the
recommended system architecture, the Embedded Enterprise Historian can collect up to 30,000 DeltaV parameters.
2.16. How many DeltaV parameters can I collect in the Integrated Enterprise Historian?
The Integrated Enterprise Historian receives data from the DeltaV Smart Connector configured on a DeltaV Application Station.
Each DeltaV Application Station and associated DeltaV OPC DA Server has a capacity of 30,000 OPC data values. One or more
DeltaV Smart Connectors can be configured per DeltaV system, up to 20 DeltaV Application Stations per system. In addition, the
Integrated Enterprise Historian can collect real-time data from multiple DeltaV systems. Thus, the Integrated Enterprise Historian
can collect up to 30,000 DeltaV parameters from one or more DeltaV Application Stations in one or more DeltaV systems, up to the
total capacity of the Integrated Enterprise Historian of 500,000 PI tags.
2.17. Can I consolidate data from more than one DeltaV system into one Embedded
Enterprise Historian?
The intent is for the Embedded Enterprise Historian to be used with a single DeltaV system. If consolidation of data from multiple
DeltaV systems is required, the Integrated Enterprise Historian is the preferred solution.
2.18. Can the DeltaV Smart Connector connect to a backup DeltaV OPC DA Server?
The recommended system architecture for the Enterprise Historian is to have a one to one relationship between the DeltaV OPC
DA Server and the DeltaV Smart Connector. However, it is technically possible to configure the DeltaV Smart Connector to use a
backup DeltaV OPC DA Server on another DeltaV Application Station in addition to the primary DeltaV OPC DA Server that resides
locally with the DeltaV Smart Connector. This architecture can provide a measure of redundant data collection. Since this is not the
recommend architecture, the technical and commercial details and the feasibility of this alternative architecture must be discussed
with your Emerson and OSIsoft project personnel. Any DeltaV OPC DA Server that DeltaV Smart Connector communicates with,
including a backup DeltaV OPC DA Server, must have the appropriate DeltaV OPC DA Server license.
2.19. I have an existing Legacy Historian in my DeltaV system. Can I continue to use the Legacy
Historian or do I have to upgrade to the Enterprise Historian?
The option to upgrade the DeltaV system and retain the Legacy Historian is available up to and including DeltaV v11.3.1. In DeltaV
v12.3, the Legacy Historian option is removed. For those customers using the Legacy Historian and upgrading to DeltaV v12.3,
you will have the option to upgrade to the Enterprise Historian or the DeltaV Continuous Historian, as desired. There are system
architecture and licensing implications associated with each option which must be considered prior to upgrading to DeltaV v12.3.
Users upgrading to DeltaV version 12.3.1 and higher have another option, to migrate to the Advanced Continuous Historian.
For more details refer to the Advanced Continuous Historian FAQ white paper available on the Emerson DeltaV website.
2.20. I have an existing site PI Server on my plant LAN. Can I use this PI Server as my integrated
Enterprise historian?
The integrated Enterprise Historian option allows you to use an existing site PI Server as your DeltaV system historian as long as the
existing PI Server is version 3.4.375.80 or later.
www.emersonprocess.com 8
Enterprise Historian FAQs October 2015
2.21. I am already using an existing site PI Server and PI OPC DA interface. Can I continue to collect my
DeltaV system data in this PI Server?
The existing methods for sending data from a DeltaV system to a site PI Server are still available separately from the Enterprise
Historian options. There is no reason you need to change this architecture if you are happy with it.
2.22. What are my options for sending DeltaV data to a site PI Server on my plant LAN?
The options for sending DeltaV data to a site PI Server are: (1) use the PI OPC DA interface with the DeltaV OPC DA Server to
send real-time data from DeltaV to the site PI Server; (2) use the PI OPC HDA interface with the DeltaV OPC HDA Server (and
corresponding DeltaV Continuous Historian) to send historical data from DeltaV to the site PI Server; (3) convert the site PI Server
to an integrated Enterprise Historian to send real-time from the DeltaV OPC DA Server to the PI Server, and (4) use the Advanced
Continuous Historian for real-time process data collection (available in DeltaV versions 12.3.1 and above) in combination with
a OSIsoft PI to PI interface.
2.24. If I use an Integrated Enterprise Historian with multiple DeltaV systems, how can I tell which
data is from which DeltaV system?
When you install and configure the DeltaV Smart Connector, you have the option to add a prefix to the PI tag name that is populated
by the DeltaV parameter. This PI tag prefix can be used to identify the DeltaV system where the data originated. Note this same PI
tag prefix functionality can be used even if the Integrated Enterprise Historian is only collecting data from a single data system, to
differentiate plant areas or units, by example.
www.emersonprocess.com 9
Enterprise Historian FAQs October 2015
3. Installation
3.1. Where do I install the Embedded Enterprise Historian?
The Embedded Enterprise Historian may be installed on a DeltaV Application Station, v10.3 or later.
3.5. Are the Enterprise Historian and DeltaV Smart Connector installed with the DeltaV
system software?
The DeltaV system software installation does not install the Enterprise Historian or the DeltaV Smart Connector. The Enterprise
Historian and DeltaV Smart Connector must be installed separately using installation media provided by OSIsoft. If you need
assistance installing the Enterprise Historian or DeltaV Smart Connector software, contact your local OSIsoft or Emerson sales office.
3.6. When should I install the Enterprise Historian and DeltaV Smart Connector?
The Enterprise Historian and DeltaV Smart Connector may be installed either before the DeltaV system software installation or after
the DeltaV system installation, whichever is more convenient.
3.9. Can I run other DeltaV or OSIsoft applications on the same DeltaV Application Station that is
running the DeltaV Smart Connector?
It is technically possible to run other applications on the same Application Station that is running the DeltaV Smart Connector,
but the recommendation is to dedicate the DeltaV Application Station to the task of enterprise history data collection.
www.emersonprocess.com 10
Enterprise Historian FAQs October 2015
3.10. Is the Enterprise Historian option only available for installation on new DeltaV systems?
The Enterprise Historian options may be used with new or existing DeltaV systems. If the Enterprise Historian option is used with an
existing system, ensure that the Application Station meets the PC hardware requirements and the appropriate licenses are obtained
from Emerson and OSIsoft.
3.11. If I migrate to the Enterprise Historian from the Legacy Historian or the DeltaV Continuous
Historian, can I do this without losing data collection during the DeltaV system upgrade?
When you upgrade your existing DeltaV system to a later version, there will be a period of time when history collection is
suspended during the upgrade of the DeltaV Application Station and the migration of the existing historian to the Enterprise
Historian. The length of time when history is not being collected depends upon how quickly you can upgrade the
DeltaV Application Station and migrate to the Enterprise Historian, but should be a matter of hours and not days.
4.2. How many DeltaV parameters can I configure for history collection in the Embedded
Enterprise Historian?
You can configure up to 30,000 DeltaV parameters for history collection in a single Embedded Enterprise Historian in the standard
system architecture where the DeltaV OPC DA Server and Embedded Enterprise Historian are resident on the same DeltaV
Application Station. The 30,000 parameter limit is imposed by the local DeltaV OPC DA Server which can be licensed for up to
30,000 OPC data values.
4.3. How many DeltaV parameters can I configure for history collection in the Integrated
Enterprise Historian?
You can configure up to 30,000 DeltaV parameters for history collection on each Application Station in one or more DeltaV systems
where the DeltaV Smart Connector is installed. The DeltaV Smart Connector and the DeltaV OPC DA Server are resident on the
same DeltaV Application Station and the DeltaV Smart Connector can access up to 30,000 parameters from the local DeltaV OPC
DA Server on each Application Station.
4.4. What is the maximum number of samples per second I can configure for collection in the
Enterprise Historian?
The recommended limit is 5,000 samples per second. For example, if you have a historian configuration that contains 5,000 or less
DeltaV parameters, you can configure all parameters for 1 second history collection (note 1 second is the fastest history collection
rate configurable from the DeltaV system). If you have a historian configuration that contains more than 5,000 parameters, you
must balance the history collection rate for all parameters to average 5,000 samples per second to stay within the
recommended limit.
www.emersonprocess.com 11
Enterprise Historian FAQs October 2015
4.5. When I add/delete/modify a history tag in the DeltaV system, are the changes updated in the
Enterprise Historian?
When you add/delete/modify a history tag from DeltaV Explorer or Control Studio, you simply download the changes to the
Continuous Historian. The download generates a new enterprise historian configuration file that the DeltaV Asset Connector
consumes and uses to update the Enterprise Historian. The process for modifying history tags is the same with the Enterprise
Historian as it is with the DeltaV Continuous Historian.
4.6. Is there somewhere I can see more details on what points have been added/deleted/modified in
the Enterprise Historian?
OSIsoft provides a log file (pipc.log) that records all transactions with the Enterprise Historian. The pipc.log file can be found in the
C:\Program Files\pipc\dat directory on the DeltaV Application Station where the DeltaV Smart Connector is installed. In addition, an
OSIsoft utility called PI System Management Tool (PI SMT) can be used to provide more information on the Enterprise Historian.
4.8. Which DeltaV historian client applications work with the Enterprise Historian?
The DeltaV historian client applications that were developed during the time the Legacy Historian served as the Continuous
Historian will work with the Enterprise Historian. The DeltaV historian client applications that will work with the Enterprise
Historian include the DeltaV operator applications Process History View (with the exception of the parameter status handling
features implemented in DeltaV v9.3), MPC Operate and MPC Operate Pro and the advanced control applications DeltaV Neural,
DeltaV Predict and DeltaV Predict Pro (with the exception of the parameter status handling features implemented in DeltaV v9.3).
Beginning with DeltaV version 13.3, the DeltaV application History Analysis and embedded trend objects in DeltaV Operate are
also supported. The DeltaV historian client applications that will not work with the Enterprise Historian include the DeltaV Reporter
(released in DeltaV v7.4) and History Web Service (released in DeltaV v10.3).
4.9. When I use the DeltaV historian client applications with the Enterprise Historian, is there extra
work involved to make this work?
Once the DeltaV historian client application is configured to connect to a specific workstation, the application will automatically
detect and connect to the historian without user intervention. Thus, any DeltaV historian client application that is compatible with
the Enterprise Historian will automatically connect to the Enterprise Historian once the client application is configured with the
Enterprise Historian workstation name. In a system with a Legacy Historian, a DeltaV Continuous Historian and/or an Enterprise
Historian, the same DeltaV historian client application can be used to view data from all historian databases (although data can only
be viewed from one historian at a time).
www.emersonprocess.com 12
Enterprise Historian FAQs October 2015
4.10. What should I do if I want historical data trends in my operator graphics and Enterprise
Historian functionality in my DeltaV system?
Beginning with DeltaV release 13.3, embedded trend controls in operator graphics (i.e. in DeltaV Operate) are supported by the
Enterprise Historian.
In prior DeltaV versions, to have both historical data trends in operator displays and Enterprise Historian functionality in your
DeltaV system, you will need to have both the DeltaV Continuous Historian and the Enterprise Historian in use in your system, as
the historical trend control in DeltaV Operate will only read data from the DeltaV Continuous Historian. The DeltaV Continuous
Historian is available on the Professional Plus, Operator Station or Application Station, whereas the Enterprise Historian is only
available on the Application Station or non-DeltaV PC. Thus, you could configure the historical data trends in your operator displays
to use the DeltaV Continuous Historian on your Professional Plus or Operator Stations and install the embedded Enterprise Historian
on an Application Station. In addition, you could use the DeltaV Continuous Historian on a second Application Station, which gives
you the ability to increase the historian tag count above the 250 tag limit of the Professional Plus and Operator Station. Note that in
addition to historical trends in DeltaV Operate, any time you want to use DeltaV Reporter, the parameter status viewing and analysis
enhancements available in Process History View, Predict and Neural or the Web based History Analysis application, plus also want PI
Server functionality, you will need to have both a DeltaV Continuous Historian and Enterprise Historian in your system.
4.11. Are all PI Server features available for use in the Enterprise Historian?
When you purchase a PI Server from OSIsoft (or Emerson reseller) to use as the Enterprise Historian, you are purchasing a full
featured PI Server. Emerson or OSIsoft do not limit the functionality available in the PI Server when used as the Enterprise Historian.
Emerson has not tested the operation of all PI Server features that are outside the scope of the Enterprise Historian (i.e. Emerson
has only tested those features necessary for use as a control system historian), but whatever features you license for use with the PI
Server are available for use with the Enterprise Historian.
4.12. Are the PI client applications like PI DataLink, PI ProcessBook, and PI to PI available for use with
the Enterprise Historian?
Any PI client application, interface, or feature purchased and/or licensed from OSIsoft (or Emerson reseller) are available for use with
the Enterprise Historian. This includes PI DataLink, PI ProcessBook, PI to PI and any other PI client application that is compatible with
the PI Server version 3.4.375.80 or later.
4.13. Do I need the PI Protocol Converter to use the PI client applications with the
Enterprise Historian?
You may use any of the appropriately licensed PI client applications directly with the Enterprise Historian. The PI Protocol Converter
is only required if you want to connect a PI client application to the DeltaV Continuous Historian and is only available up to and
including DeltaV system v10.3.1.
4.14. Are the PI client applications like PI DataLink, PI ProcessBook supported for use on DeltaV
Operator Stations?
Emerson has not fully tested the use of the PI client applications on a DeltaV Operator Stations and thus does not support the use of
these applications on an Operator Station. The PI client applications can be used on a DeltaV Application Station on non-DeltaV PC.
Support for these PI client applications on an Application Station is the same as it has been in the past and is true for any 3rd party
applications – these applications may be installed and used on an Application Station but support for the application is provided
by OSIsoft.
www.emersonprocess.com 13
Enterprise Historian FAQs October 2015
4.15. Can I bring 3rd party data directly into the Enterprise Historian?
With the appropriate interface licenses from OSIsoft, you may bring in as much 3rd party data directly into the Enterprise Historian
as your PI Server license allows. The DeltaV system does not place any restrictions on how much non-DeltaV data can reside in the
Enterprise Historian.
4.16. Can I use other OPC DA client applications with the DeltaV OPC DA Server configured for use
with the DeltaV Smart Connector?
It is recommended that the DeltaV OPC DA Server is dedicated to serving data to the Enterprise Historian. The DeltaV OPC DA
Server may be licensed for up to 30,000 OPC data values. If the Enterprise Historian is configured to collect less than 30,000 DeltaV
parameters, then the remainder of the 30,000 OPC data values available on the DeltaV OPC DA Server may be used by other OPC
DA client applications. You must ensure that the DeltaV OPC DA Server is licensed with enough OPC data values to accommodate all
OPC client applications, including the PI OPC DA interface, used to collect data for the Enterprise Historian. In addition, you should
determine if the Application Station hardware can handle the load applied by the PI OPC DA interfaces and any additional OPC
client applications.
www.emersonprocess.com 14
Enterprise Historian FAQs October 2015
5. Migration
5.1. Can I upgrade my existing Legacy Historian to an Enterprise Historian?
If you have a Legacy Historian running on a DeltaV Application Station you can upgrade the Legacy Historian to an Enterprise
Historian. You will need to purchase a PI Server version 3.4.375.80 (or later) and DeltaV Smart Connector from OSIsoft (or Emerson
reseller) and then manually upgrade the Legacy Historian using the upgrade procedure provided by OSIsoft. You will also need to
reconfigure the Continuous Historian subsystem to use the Enterprise Historian instead of the Legacy Historian. For more details,
refer to the Continuous Historian Upgrade Planning Guide found on the DeltaV whitepaper website.
5.2. If I upgrade my existing Legacy Historian to an Enterprise Historian, will I lose my existing
historical data?
If you want to upgrade the Legacy Historian to an Enterprise Historian and preserve your historical data, you can manually migrate
the legacy historian archive files using the legacy historian upgrade procedure provided by OSIsoft.
5.3. If I upgrade my existing Legacy Historian to an Enterprise Historian, will I need to reconfigure the
DeltaV parameters for history collection?
In terms of historian configuration, when you upgrade the Legacy Historian to an Enterprise Historian you will only need to
reconfigure the Continuous Historian subsystem on the DeltaV Application Station to use the Enterprise Historian instead of the
Legacy Historian and download the subsystem. Your existing history collection will be “transferred” to the Enterprise Historian via
the DeltaV Asset Connector.
5.4. If I upgrade my existing Legacy Historian to an Enterprise Historian, will I still have to purchase an
Enterprise Historian license?
The Enterprise Historian option is licensed separately from the Legacy Historian and the Legacy Historian licenses are not
transferable to the Enterprise Historian. However, if you upgrade your Legacy Historian to an Enterprise Historian, OSIsoft will work
with you on the license price of the PI Server and DeltaV Smart Connector. You will also require the DeltaV OPC DA Server license
and the Enterprise Historian Configuration Interface license from Emerson as discussed in Section 1.
5.5. Are there additional costs associated with migrating data from my existing Legacy Historian to
an Enterprise Historian?
When you purchase the PI Server for use as the Enterprise Historian, you will be able to upgrade your Legacy Historian and convert
the data at no additional cost. If you require assistance to perform the legacy historian upgrade, support can be provided by
Emerson and/or OSIsoft at additional cost.
5.6. Can I replace my existing DeltaV Continuous Historian with an Enterprise Historian?
Yes. If you have a DeltaV Continuous Historian running on a DeltaV Application Station you can replace it with an Enterprise
Historian if you need PI functionality. You will need to purchase the PI Server version 3.4.375.80 and DeltaV Smart Connector from
OSIsoft (or Emerson reseller) and then reconfigure the Continuous Historian subsystem to use the Enterprise Historian instead of the
DeltaV Continuous Historian.
www.emersonprocess.com 15
Enterprise Historian FAQs October 2015
5.7. If I replace my existing DeltaV Continuous Historian with an Enterprise Historian, will I lose my
existing historical data?
If you want to replace the DeltaV Continuous Historian with an Enterprise Historian and preserve your historical data, you can
use the PI OPC HDA interface to move the historical data from the DeltaV Continuous Historian (via the DeltaV OPC HDA Server)
to the Enterprise Historian. For more details, refer to the Continuous Historian Upgrade Planning Guide found on the DeltaV
whitepaper website.
5.8. If I replace my existing DeltaV Continuous Historian with an Enterprise Historian, will I need to
reconfigure the DeltaV parameters for history collection?
In terms of historian configuration, when you replace the DeltaV Continuous Historian with an Enterprise Historian you will only
need to reconfigure the Continuous Historian subsystem on the DeltaV Application Station to use the Enterprise Historian instead
of the DeltaV Continuous Historian and download the subsystem. Your existing history collection will be “transferred” to the
Enterprise Historian via the DeltaV Asset Connector. Note that once you have reconfigured and downloaded the Continuous
Historian subsystem to use the Enterprise Historian, the DeltaV Continuous Historian processes continue to run but are no longer
collecting data. On the next reboot of the Application Station, the DeltaV Continuous Historian processes will not start.
5.9. If I replace my existing DeltaV Continuous Historian with an Enterprise Historian, will I still have
to purchase a PI Server license?
The Enterprise Historian option is licensed separately from the DeltaV Continuous Historian and the DeltaV Continuous Historian
licenses are not transferable to the Enterprise Historian. You will still need to purchase a PI Server license and DeltaV Smart
Connector license from OSIsoft (or Emerson reseller). You will also require the DeltaV OPC DA Server license and the Enterprise
Historian Configuration Interface license from Emerson as discussed in Section 1.
5.10. Are there additional costs associated with migrating data from my existing DeltaV Continuous
Historian to an Enterprise Historian?
Migration of your DeltaV Continuous Historian data to the Enterprise Historian requires the DeltaV OPC HDA Server and the PI OPC
HDA interface. You will need a license for the PI OPC HDA interface which may be purchased from OSIsoft (or Emerson reseller).
Contact your local OSIsoft or Emerson sales office for more details. If you require assistance to perform the legacy historian
upgrade, support can be provided by Emerson and/or OSIsoft at additional cost.
5.11. If I replace my existing DeltaV Continuous Historian with an Enterprise Historian, can I switch
back to the DeltaV Continuous Historian?
If you replace your existing DeltaV Continuous Historian with an Enterprise Historian (or install the Enterprise Historian on a new
DeltaV system), and you want to revert back to the DeltaV Continuous Historian, you can do this by simply reconfiguring the
Application Station to use the DeltaV Continuous Historian and downloading the Continuous Historian subsystem. The DeltaV
Continuous Historian will be configured and the historian data collection processes will begin collecting data in the DeltaV
Continuous Historian. To collect more than 250 parameters, the Application Station will need a DeltaV Continuous Historian scale
up license. The Enterprise Historian will stop collecting data but will remain available for use by PI client applications. The DeltaV
historian client applications, like Process History View, can be configured to start using the DeltaV Continuous Historian. If the
Enterprise Historian is no longer needed, it must be manually uninstalled.
www.emersonprocess.com 16
Enterprise Historian FAQs October 2015