Horizontal Dimensions Specifications For Variable Traveling Speed Elevator System
Horizontal Dimensions Specifications For Variable Traveling Speed Elevator System
Horizontal Dimensions <1-Door 1-Gate (1D1G)> Specifications for Variable Traveling Speed Elevator System (Optional)
Car internal Minimum hoistway <1-Door 1-Gate (1D1G) & 1-Door 2-Gate (1D2G)>
Number Rated Rated Entrance width Counter-
Code Door dimensions dimensions
of capacity speed (mm) weight Travel Minimum overhead Minimum pit depth
number type (mm) (mm) Rated speed Speeds Rated capacity
persons (kg) (m/sec) JJ position (m) (mm) (mm)
AAx BB AHxBH/car (m/sec) (m/sec) (kg)
TR OH PD
950x1300 1500x1740
P6 6 450 800 TR <
= 30 3750
1000x1200 1550x1740 1.0 1.0/1.25/1.5/1.6 ~1050 1400
2S 30< TR <
= 60 3800
800: Standard
P7 7 550 1100x1300 1650x1740
900: Optional [ Terms of the table]
900: Standard 1950x1720 • The Variable Traveling Speed Elevator System (VSE) is applicable for elevators with a rated speed of 1.0m/sec.
CO
800: Optional 1800x1720 • Except minimum overhead and pit depth dimensions (OH and PD), specifications shown in tables, “Horizontal Dimensions” and “Vertical Dimensions”,
P8 8 630 1100x1400
900: Standard on the pages 19 and 21 are applicable to the Variable Traveling Speed Elevator System.
2S 1650x1800
800: Optional
1.0 900: Standard 2025x1720
CO
1.6 800: Optional Side 1925x1720
P11 11 825 1350x1400
1.75 900: Standard 1900x1800
2S
1100: Optional 1950x1800
1100: Standard 2415x1720
CO
900: Optional 1600x1400 2215x1720 Hoistway Plan Hoistway Section
2S 1100 2215x1800
P14 14 1050 900: Standard 1965x2420
CO
800: Optional 1865x2420 Hoistway width: AH
1100x2100
900: Standard
2S 1715x2500
800: Optional
Hoistway depth: BH
Car internal
width: AA
[ Terms of the table]
Car internal
Overhead: OH
• The contents of this table are applied to standard specifications only. Please consult our local agents for other specifications.
depth: BB
• Rated capacity is calculated at 75kg per person, as required by EN81-1.
Entrance height: HH
2200 (standard)
2100 (standard)
• CO: 2-panel center opening doors, 2S: 2-panel side sliding doors.
Ceiling height
• Minimum hoistway dimensions (AH and BH) shown in the table are after waterproofing of the pit and do not include plumb tolerance. Entrance
• This table shows specifications without the fireproof landing door and counterweight safety. width: JJ
• The applicable range of the rated capacity may differ depending on the manufacturing factory. Please consult our local agents for details. Shown for CO doors
Counterweight side drop
(Capacity 630kg ~ 1050kg)
Travel: TR
Rated speed
(m/sec) (m) number (mm) (mm) floor to floor height
TR of floors OH PD (mm)
TR <
=30 3650 *1
1.0 22 1300
BB
BH
30< TR <
= 60 3650
TR <
=30 3750
1.6 30< TR <
= 60 30 3800 1400
2500
60< TR <
= 80 3850
Pit depth: PD
TR <
=30 3850
1.75 30< TR <
= 60 30 3900 1450 JJ
60< TR <
= 80 3950 Shown for 2S doors
Counterweight side drop
(Capacity 450kg ~ 1050kg)
[ Terms of the table]
• The contents of this table are applied to standard specifications only. Please consult our local agents for other specifications.
• Some specifications require more than 2500mm as a minimum floor height. Please consult our local agents if the floor height is
less than entrance height HH + 700mm, and the elevator is 1-Door 2-Gate.
• This table shows specifications without counterweight safety.
[Note] Applicable Standards
*1 Minimum overhead (OH) may vary depending on conditions.
NEXIEZ-MRL complies with EN81-1. For details of compliance with other national regulations,
please consult our local agents.
19 20
Basic Specifications Important Information on Elevator Planning
Horizontal Dimensions <1-Door 2-Gate (1D2G)> Work Not Included in Elevator Contract
The following items are excluded from Mitsubishi Electric’s elevator installation work, and are therefore the responsibility of the building owner or general
Car internal Minimum hoistway contractor:
Number Rated Rated Entrance width Counter-
Code Door dimensions dimensions
number of capacity speed type (mm) (mm) weight (mm) • Construction of the elevator machine room with proper beams and slabs, equipped with a lock, complete with illumination, ventilation and
persons (kg) (m/sec) JJ position waterproofing.
AAxBB AHxBH/car
900: Standard 1965x1860 • Access to the elevator machine room sufficient to allow passage of the control panel and traction machine.
CO
800: Optional 1865x1860 • Architectural finishing of the machine room floor, and the walls and floors in the vicinity of the entrance hall after installation has been completed.
P8 8 630
900: Standard
1100x1400
1715x1982 • Construction of an illuminated, ventilated and waterproofed elevator hoistway.
2S
800: Optional 1650x1982 • A ladder to the elevator pit.
CO
900: Standard 2090x1860 • The provision of cutting the necessary openings and joists.
P11 11 825
800: Optional
1350x1400
1925x1860 • Separate beams, when the hoistway dimensions markedly exceed the specifications, and intermediate beams when two or more elevators are installed.
1.0
2S
900: Standard 1900x1982 • All other work related to building construction.
1.6 1100: Optional Side 1965x1982 • The machine room power-receiving panel and the electrical wiring for illumination, plus the electrical wiring from the electrical room to the
1.75 1100: Standard 2415x1860 power-receiving panel.
CO
900: Optional 1600x1400 2215x1860 • The laying of conduits and wiring between the elevator pit and the terminating point for the devices installed outside the hoistway, such as the
2S 1100 2215x1982 emergency bell, intercom, monitoring and security devices, etc.
P14 14 1050
CO
900: Standard 1965x2560 • The power consumed in installation work and test operations.
800: Optional
1100x2100
1865x2560 • All the necessary building materials for grouting in of brackets, bolts, etc.
2S
900: Standard
1715x2682 • The test provision and subsequent alteration as required, and eventual removal of the scaffolding as required by the elevator contractor, and any other
800: Optional protection of the work as may be required during the process.
[ Terms of the table]
• The provision of a suitable, locked space for the storage of elevator equipment and tools during elevator installation.
• The contents of this table are applied to standard specifications only. Please consult our local agents for other specifications. • The security system, such as a card reader, connected to Mitsubishi Electric’s elevator controller, when supplied by the building owner or general
• Rated capacity is calculated at 75kg per person, as required by EN81-1. contractor.
• CO: 2-panel center opening doors, 2S: 2-panel side sliding doors. * Work responsibilities in installation and construction shall be determined according to local laws. Please consult our local agents for details.
• Minimum hoistway dimensions (AH and BH) shown in the table are after waterproofing of the pit and do not include plumb tolerance.
• This table shows specifications without the fireproof landing door and counterweight safety.
Elevator Site Requirements
• The temperature of the machine room and elevator hoistway shall be below 40˚C.
• The following conditions are required for maintaining elevator performance.
a. The relative humidity shall be below 90% on a monthly average and below 95% on a daily average.
Hoistway Plan Hoistway Section b. The machine room and the elevator hoistway shall be finished with mortar or other materials so as to prevent concrete dust.
• Voltage fluctuation shall be within a range of +5% to -10%.
Ordering Information
Hoistway width: AH
Entrance
width: JJ
Car internal
2200 (standard)
2100 (standard)
width: AA
Ceiling height
• Operation system.
Car internal
depth: BB
AH
JJ
Floor to floor height
Mitsubishi Elevator Inazawa Works has acquired ISO 9001 certification from the
AA
International Organization for Standardization based on a review of quality
BH
BB
management.
The company has also acquired environmental management system standard
ISO 14001 certification.
Pit depth: PD
JJ
Applicable Standards
NEXIEZ-MRL complies with EN81-1. For details of compliance with other national regulations,
Mitsubishi Elevator Asia Co., Ltd. has acquired ISO 9001 certification from the International Organization for Standardization based on a review of quality management.
please consult our local agents. The company has also acquired environmental management system standard ISO 14001 certification.
21 22