Chapter 5 Rev1
Chapter 5 Rev1
Chapter: 5 Pagina - 1 di 17
Titolo: HMI Chapter 5.doc
5.1 Introduction
The TTS4 Display and Monitoring System is a Human Machine Interface (HMI) product
developed by Solar Turbines Incorporated specifically for turbomachinery control applications.
The HMI application (TT4000) displays and stores data and provides a range of control interface
capabilities. The local HMI is provided as a separate industrial PC. Due to the larger data
storage requirements, the HMI is provided with a rotating hard disk.
TT4000 is a flexible and expandable product. With the following features, TT4000 is consistent
with current industry software standards:
• The system runs under the Windows 2000 or XP operating system.
• The system is compliant with Transmission Control Protocol and Internet Protocol (TCP / IP)
to permit easy transmission of data between TT4000 and other programs.
• The system is compliant with Object Linking and Embedding for Process Control (OPC)
standards. This facilitates integration with other compliant software systems.
• Historical data are readily viewable within the program. Also, files in Comma Separated
Value (csv) format can be created for easy export to other programs such as Microsoft
Excel.
• The program supports Active-X controls.
The HMI provides a window into the package control system. It shows engine conditions, stores
information, alarms, shutdowns, and events, and can permit varying levels of control. While
beneficial to an operator, the HMI is not essential for the control of the package, since that
responsibility rests with the package control system.
In acting as an information server and not as a critical engine controller, the complexity of
communications protocols is simply handled through the Microsoft Windows 2000 and HMI
package software using commercially available drivers. This design removes complex
communications from the primary controller level, which in turn maximises the simplicity and
integrity of the overall system.
The HMI interfaces with, but is separate from, the package control system. This allows the
TT4000 application to perform multiple tasks without interfering with the critical control and
protection functions handled by the control system. The HMI communicates with the primary
controller over Ethernet using a TCP communications protocol.
The communications server feeds an OPC server imbedded on the same HMI PC. The OPC
server is the primary method for the TT4000 application or a client DCS system to acquire data
from the primary controller and field instrumentation.
Chapter: 5 Pagina - 2 di 17
Titolo: HMI Chapter 5.doc
5.2 HMI Displays
When the HMI PC is switched ON, the TT4000 HMI is automatically launched.
The Microsoft Internet Explorer web browser is the standard web browser that is used for
TT4000. It is available on any Windows 2000/XP system and supports both scripting and
ActiveX controls. The browser is used for both local operation and for remote access.
TT4000 is a self-contained web site from which html web pages are served up using standard
HTTP and HTTPS protocols through TTServers built-in web server interface.
TT4000 display screens provide the operator a window into the operation of the equipment.
The page is divided in 4 parts: “Page Header”, “Navigation tree”, “Alarm Banner” and “Main
screen”.
The major portion of each display screen is dedicated to showing the current view.
Chapter: 5 Pagina - 3 di 17
Titolo: HMI Chapter 5.doc
5.2.1.1 “Page Header”
On the “Page Header” (top of the page) the majors engine parameters and status are always
displayed.
The following onscreen buttons may be selected:
• Quite - Selecting this onscreen button will acknowledge any active alarm or shutdown.
• Reset - Selecting this onscreen button will clear inactive alarms or shutdowns that have been
acknowledged, and reset the control system.
The “Navigation thee”, appears on the left side of the display screen. This provides quick
navigation to all of the projects views, reports, or additional applications.
On the “Alarm Banner”, on the page bottom, are listed the pending alarms.
If needed, the scroll bar on the right side is activated, in order to scroll down the list.
Chapter: 5 Pagina - 4 di 17
Titolo: HMI Chapter 5.doc
5.2.2 Starting application
In order to start the TT4000 HMI application, please click TT4000Launch, on the Start menu, or
following the path “Start – Programs – Solar Turbines”.
Chapter: 5 Pagina - 5 di 17
Titolo: HMI Chapter 5.doc
5.2.3 Page Descriptions
The Operation Summary display screen displays a summary of engine, enclosure, lube oil
system, actuators, fuel system and generator operating values, and engine status indications.
This display screen also displays control system supply voltage, system control selections,
operation modes, stop sequences, and control modes. Operation modes, stop sequences,
control modes, system control selections, and status indications appear highlighted when active.
Data is presented in real time and is continually updated.
Chapter: 5 Pagina - 6 di 17
Titolo: HMI Chapter 5.doc
5.2.3.2 Operation Commands
The Operation Commands screen, displays the engine status and the different timers related to
the main sequences.
The following optional commands may be given from this display screen:
• Engine (Start / Stop)
• Power Setpoint
• Syncronization (Start / Stop )
• Syncronization Mode (Auto / Manu)
Chapter: 5 Pagina - 7 di 17
Titolo: HMI Chapter 5.doc
5.2.3.3 Lube System
The Lube System display screen, displays lube oil system temperatures, pressures, pump and
heater status indications.
Chapter: 5 Pagina - 8 di 17
Titolo: HMI Chapter 5.doc
5.2.3.4 Fuel Gas
The fuel gas display screen shows the trip, relief and control valve actuation. Also displayed are
the fuel line pressures.
Chapter: 5 Pagina - 9 di 17
Titolo: HMI Chapter 5.doc
5.2.3.5 Alarm Summary
Process alarms and events are viewed through the Alarm Summary. The application displays all
events in chronological order. All alarms and events are time stamped by the primary controller
in the order they are received.
Display screens can be displayed in two or more languages. To view a display screen in an
alternate language, select the desired language on the pull down menu (on the top of the
“Navigation tree”), and click the “Go” button.
A new display screen will open and the display screen text will appear in the selected alternate
language. In addition to the display screen text, Help menu files accessed from an alternate
language display screen will also appear in the selected alternate language.
Chapter: 5 Pagina - 10 di 17
Titolo: HMI Chapter 5.doc
5.3 Historical Data Analyser
The Historical Data Analyzer tool allows users to review historical data collected by TT4000
computer in a strip chart or a data table.
Click “Start” on the Windows Taskbar and choose Programs, Solar Turbines, and TT4000
Historical Data Analyzer.
Chapter: 5 Pagina - 11 di 17
Titolo: HMI Chapter 5.doc
5.3.1 Analyze Data Logs
Click the data log file to evaluate. Tags will appear in Available Tags listing.
For multi-language projects, a language can be selected from the Select Language pull down
list.
Select Filter by Tag Group/Custom:
• All Tags
• Analogs
• Other
• Status
• Alarms
• Shutdowns
To search for tags containing specific text strings, Select/deselect “And Contains” and type
desired text. Available Tags will list tags containing the text that is specified.
Chapter: 5 Pagina - 12 di 17
Titolo: HMI Chapter 5.doc
When satisfied with the selected tags and associated date time range click the “Get Tag Data”
button.
Chapter: 5 Pagina - 13 di 17
Titolo: HMI Chapter 5.doc
Historical Data Analyzer Strip Chart
Chapter: 5 Pagina - 14 di 17
Titolo: HMI Chapter 5.doc
Historical Data Analyzer X/Y Plot
Chapter: 5 Pagina - 15 di 17
Titolo: HMI Chapter 5.doc
5.3.2 Data Review/Export
Review the data on the screen or save it to a comma separated value (CSV) file format. A CSV
file format is a standard data storage format that is readily usable by applications like Microsoft
Excel.
To save the data, click the Create CSV File to export tag data to a comma-separated-value
format file.
When prompted for a file name and location either accept the default or specify an alternate file
name and location and click Save.
Chapter: 5 Pagina - 16 di 17
Titolo: HMI Chapter 5.doc
5.3.3 Analyze Event Logs
Chapter: 5 Pagina - 17 di 17