Design - Underground Raft FDN - R0
Design - Underground Raft FDN - R0
BHAIRAHAWA, NEPAL
DOCUMENT TITLE: CIVIL DESIGN CALCULATION FOR
70 KL UG TANK
(2.75 M I.D x 13.0 M LG) FOUNDATION
CONTRACTOR DOC. NO: NOC:/ATF/GEC/70KL/02
RAFT PLAN
0.75
X
3.75
14.5
RAFT ELEVATION
GL
3.662
0.3
Horizontal Seismic Coefficient Ah = (ZI/2R)X(Sa/g) = 0.070 Sa/g (Cl. 6.4.2 , IS:1893,2002 Pt. 1)
Sa/g = Average response acceleration Coefficient (Cl. 6.4.2 , IS:1893,2002 Pt. 1)
Seismic Weight of structure (W) = DL+0.5IL = 80.03 T Say 81 T
Where , DL = Dead Load & IL = Imposed Load i.e Live Load in this case
(Refer Cl. 7.3 of IS:1893,2002 Pt. 1)
Base shear calculation based on Fundamental Natural period(Ta) as per Cl. 7.6.1 of IS:1893,2002 Pt. 1
0.75
Ta = 0.075h = 0.20 ( h = height of structure)
So, Sa/g = = 2.50 …Cl. 6.4.5 of IS:1893, 2002 Pt. 1
Ah = 0.175
Hence Base Shear = 14.18 T 14175 KG
Moment created by Base shear (Base Shear X Height of Structure ) M = 51.91 T.m
3
Section Modulus along X axis Zx = 33.98 m
2
σmax = P/A + M/Zx = 3.877 T/m HENCE OK
2
σmin = P/A - M/Zx = 1.933 T/m HENCE OK
The tank is safe against flotation from 100% saturated soil buoyancy.
= 77214.46 liter
Weight of fluid = 77214.46 kg
Excluding selfweight of tank = 66214.46 kg
No. of Bolts holding Tank = 16
PAGE 4 OF 5
GAUTAM BUDHA INTERNATIONAL AIRPORT,
BHAIRAHAWA, NEPAL
DOCUMENT TITLE: CIVIL DESIGN CALCULATION FOR
70 KL UG TANK
(2.75 M I.D x 13.0 M LG) FOUNDATION
CONTRACTOR DOC. NO: NOC:/ATF/GEC/70KL/02
PAGE 5 OF 5