Easergy MiCOM Px30-Px40 - Catalog 2020 - NRJCAT19835EN - 180920
Easergy MiCOM Px30-Px40 - Catalog 2020 - NRJCAT19835EN - 180920
Easergy MiCOM
series 30, 40
Catalog 2020
Comprehenive range of digital protection relays
se.com/easergy
Your electrical equipment is under control.
With Easergy protection relays, you get
maximum energy availability for your
process and application.”
The flexible Easergy MiCOM protection relay range offers scalable levels of functionality and
hardware options to meet or exceed your protection functionality requirements.
660 000
Easergy MiCOM units
installed around the
The versatile hardware and common relay management software (Easergy Studio) allows simple world since 1999
configuration and installation in different applications.
Well-known user friendliness, based on a standardized user interface across the entire range
makes Easergy MiCOM suitable for any environment, from the more complex bay level control with
mimic, to the simplest LCD display with menu interrogation.
Easergy
Every Easergy MiCOM relay provides you with intuitive access to all system information in several
languages so that you can manage your electrical installation effectively. If an unpredictable
situation occurs, clear and complete information puts you in a position to make the right decisions
immediately. The electrical supply is restored without delay.
Easergy MiCOM relays maintain high energy availability thanks to their diagnostics function that
continuously monitors network status. In-depth analysis capabilities and high quality standards
mean that equipment is only de-energized when absolutely necessary. Risks are minimised and
servicing time reduced by predicting maintenance operations.
• Protection can be operated on solidly or (low-) impedance grounded, with Petersen coil resonant grounded or with isolated
neutral star point networks.
• Various hardware options with selectable 24TE, 40TE, 84TE mounting case; detachable HMI option; conversable surface/
flush mounting or the optional Pin, Ring and Hybrid terminal connection variants provide a maximum on adaptability to any
customer need or spatial constraint, by offering nearly the same protection functionality in all hardware variants.
• Full Programmable Scheme Logic (PSL) and function keys in addition to the high number of proven fixed protection
functions allow advanced protection scheme engineering
• New color 5.7" Graphical-HMI provides an enhanced flexibility for Single Line Diagram (SLD) mimics which allows you to
visualize most complex arrangements on the new display. The new 4.3" single-color Text-HMI completes the range with
simplicity of interaction.
• USB port front port provides easy to use communication with the device. No needs for external converters.
• Easy and intuitive interaction with the device thanks to the intuitive and ergonmically arranged navigation keys
• 6x fully configurable function Keys with tri-color LEDs provide direct access to your customized functions or common
operations.
• The removable paper labels provide flexibility and simplicity for maintenance.
• The well-known, powerful and user-friendly Programmable Scheme Logic (PSL), provides a maximum on functionality to
cover any protection application (from basic to really advanced ones).
• Detailed post-mortem analysis required by exigent customers is fully included thanks to its powerful disturbance and
events recording features.
• Powerful process bus board, with standardized Ethernet redundancy (PRP) for augmented reliability and availability, fully
compliant with the latest standard IEC 61869 and backwards compatible with the previous 9-2LE.
• Accurate time stamping of events is achieved thanks to the standardized time sync method IEC 61850-9-3 (PTP, 1588v2)
Upload data on-line from Enable protection Easily and quickly apply
the relay or off-line from functions protection, control, and
a data model template monitoring settings
Operation
Download
Easergy MiCOM protection devices combine best-in-class protection techniques with the latest
technology for dependability, and high quality in advanced protection applications.
Secure
For operational security, Easergy MiCOM offers Role-Based Access Control (RBAC), encrypted
passwords, port hardening, alarms, logs, monitoring, and the Security Access Tool (CAE - Cyber
Security Admin) to help your existing staff manage access without advanced skills or training.
Easergy MiCOM including operational and cybersecurity, compliant to IEC 62351. It helps to
protect installations with security based on embedded features such as Role Based Access Control
(RBAC), port hardening, security logs and access traceability. Easergy MiCOM devices by default
including RBAC with different users defined and a Security Administrator
Communicate
Local and remote communication is provided and designed for use with the Easergy Studio
software. Easergy MiCOM devices provide IEC 61850 Edition 1 & 2, IEC 60870-5-104 as well as
GOOSE messaging, Dual IP (PRP/HSR) and VLAN for physical Ethernet network segregation
and redundancy. RSTP, IEC 60870-5-104 and flexible product naming (fPN) complete the
communication capabilities. Port types, quantities, and serials protocols vary by product (see
pages 19 and 20).
Configure
Settings are defined via the Easergy Studio support package. This intuitive software lets you
manage settings for your entire Easergy MiCOM installed base, with multiple independent setting
groups. They can be activated locally, remotely, or via a dedicated input condition, which allows
different system operating conditions or adaptive relaying, and you can import IEDs into systems
from pre-configured IEC 61850 SCD files.
Measure
Easergy MiCOM devices measure and store a wide range of highly accurate values including
current, voltage, frequency, power, and others, from instantaneous or derived values. You can view
measurements on the device or transfer them via communication ports.
Record
Locally and remotely viewable, event records are generated by status changes to logic inputs,
outputs, settings, and alarms. All records are time tagged to a resolution of 1ms and are retained
even during auxiliary supply interruptions. These devices also capture information about faults
and disturbances, and oscillographic analysis using Easergy Studio provides quick analysis of
analogue and digital signals.
Control
Fully programmable function keys and programmable tri-state LEDs are available. Some
Easergy MiCOM devices provide programmable hot-keys for direct menu access (e.g. Trip/Close
command). Time synchronization can be implemented from various sources including an optional
IRIG-B port or via an IEC 61850-9-3 (PTP, 1588) time synchronization communication protocol.
The new colored Graphical- and black and white text-HMI ease the handling and perfect the
operational security to control upt to 15 switchgear units.
Scheme
You can use Easergy Studio to configure programmable scheme logic. Easergy MiCOM devices
use graphical programming or Boolean equations. Programmable graphical logic in these relays is
an extremely powerful tool. Users can customize protection and control functions or add additional
supervision or custom schemes, e.g. trip circuit supervision or frequency restoration. This logic is
event driven so that protection is not delayed. An online status monitoring feature is also available.
costly downtime
• Maximizing uptime by performing in-depth analysis and de-energizing
equipment only when absolutely necessary
ProDiag MV Relay’s unique features:
• Automatic download of all protection relay settings through drivers in
the ProDiag MV Relay manager
• Easy verification of modifications made to protection settings since
the last visit
• Easy verification of MV Relay original technical specifications
The cases are suitable for either rack or panel mounting. An option for surface mounting is also supported on the series 30
for installations with space limitations.
The 40TE case relays can be combined with the use of standard mounting accessorie to form a complete 19” rack. This
saves space and allows for a neat installation.
Dimensions (mm) A B C D E
40TE 213.4
262.7 227.9
84TE 434.8
184.5 177.5
40TE Surface 260.2
266,7 -
84TE Surface 481.6
>
>
A A E
< >
D
<
<
<
Wiring
External connections are made via pin-type terminal. Optional ring-type terminals are available.
Note: Maximum sizes for guidance only, for specific product information please check the relevant product documentation.
KEYS
Pressing the HOME key returns to the Single Line
Diagram from anywhere in the menu. If setting
mode is enabled, the setting change should be
confirmed/cancelled when pressing the HOME
key. The edited setting parameter value is
returned to its original value if the setting change
is cancelled.
Press the I-key to access a selected event
recording from either the panel level or from any
other point in the menu tree.
12 customizable
tri-color LEDs
F1 Customizable function keys
Easergy MiCOM devices are housed in specially designed cases that provide a high density of functionality within the
product. Communication ports and model/serial number information is concealed by upper and lower covers on certain
models.
Physical protection of the front panel user interface and prevention of casual access is provided by an optional transparent
front cover (selected models only), which can be fitted or omitted, since the front panel has been designed to IP52 protection
against dust and water.
The differing case widths of relays can be combined with or without the use of standard blanking plates to form a complete
19” mounting. This saves space and allows for a neat installation.
Easergy
Easergy
Case format A B C D E
40TE 206
60TE 309.6 240 270
177 157.5 max
80TE 413.2 (incl. wiring) (incl. wiring)
Wiring Easergy
The user interface and menu text is available in English, French, German, and Spanish as a standard. Other languages, e.g.
Russian and Chinese, are supported on some relays depending on the market requirements.
Note: Maximum sizes for guidance only, for specific product information please check the relevant product documentation.
2 1
3
4
6 7
1. A back-lit liquid crystal display 5. “READ” and “CLEAR” keys for viewing
and reset of alarms
2. 4 fixed function LEDs
6. Front communication port
3. Up to 18 user programmable LEDs
7. Facility for fitting a security seal
4. Menu navigation and data entry keys
8. Programmable function keys
Frequency 50/60 Hz
Dual rated 1 A / 5 A
Opto inputs max 82
Output contacts max 48
High break contacts max 16
Continuous carry 5 A / 8 A / 10 A
Short duration current 30 A for 0.5 (3 s)
LED indication (freely programmable) 23 (19)
Function keys / hot keys 6
Settings groups 4
Fault records 8
Event records 3000
Disturbance records max 32 s (max 8 rec.)
Programmable logic Fully programmable
IRIG B Option
LCD Display with USB port or RS232 Alphanumeric / Graphical (color)
Rear Port / 2nd rear port Yes / Option
Serial communication EIA(RS)485 or fibre
Courier
Modbus / DNP3 /
IEC 60870-5-103 /-101 /
Ethernet communication Wire RJ45 or fibre
IEC 60870-5-104 / DNP3oE /-
IEC 61850
IEC 61850 Process Bus -
IEC61850-9-3 (PTP, 1588) time sync *
Terminals Pin or Ring
Frequency 50/60 Hz
Dual rated 1 A / 5 A
Opto inputs max 64
Output contacts max 60
High break contacts max 8
Continuous carry 10 A
Short duration current 30 A for 3 s
LED indication (freely programmable) 22 (18)
Function keys / hot keys 10 / 2
Settings groups 4
Fault records 15
Event records 250 - 512
Disturbance records 75 s (max 10.5 s/rec.)
Programmable logic Graphical / Fully programmable
IRIG B Option
LCD Display with EIA(RS) 232 front port Alphanumeric
Rear Port / 2nd rear port Yes / Option
Courier K-Bus / EIA(RS) 485 or Ethernet (RJ45/Fibre)
Modbus EIA(RS) 485
IEC 60870-5-103 EIA(RS) 485 or Ethernet (RJ45/Fibre) *
IEC 60870-5-101 -
DNP3.0 EIA(RS) 485 or Ethernet (RJ45, fibre) *
IEC 60870-5-104 -
IEC 61850 Wire RJ45 or fibre
IEC 61850 Process Bus Wire RJ45 or fibre *
IEC61850-9-3 (PTP, 1588) time sync **
Terminals Ring
HSR/PRP *
RSTP *
* please ask for availability (depending on product) ** Except for P24x, P34x, P740
VT Inputs 4 or 5 4 or 5 3 3 3 or 4 3 or 4
Opto Inputs (max) 70 70 8 16 32 32
Output Contacts (max) 38 36 8 15 30 32
High Break Contacts (max) 16 16 4 8 8
RTDs (max) 10 10
Analogue Input / Output (max) 1/2 1/2
Function Keys / Hotkeys with new HMI with new HMI -/ -/ / /
Bay Control and Monitoring Graphical
including Interlocking
Mimic
ANSI PROTECTION FUNCTION P132 P139 P141 P142 P143 P145
25 Check synchronising
32 Directional power
32V Voltage controlled direct. reactive power
34 Master sequence device
37 Undercurrent
46 Negative sequence overcurrent
46BC Broken conductor
47 Negative sequence over voltage
48 Incomplete sequence relay
49 Thermal overload
50/51N Ground fault
50/51P 3 Phase overcurrent
50/51P/N 1 Phase or earth overcurrent
50BF Circuit breaker failure
51LR Motor
51V Voltage controlled overcurrent
59/27 Over / Under voltage
59N Residual over voltage
64 Restricted earth fault
66 Startup monitoring
67N Transient ground fault detection
67N Ground fault directional
67N Ground fault direct. pulse detection
67N Sensitive directional earth fault
67P Phase directional
67W Wattmetric earth fault
79 Auto-reclose
81 Under / Over frequency
81P Under frequency load shedding
81R Rate of change of frequency
85 Protective signalling
86 Lock-out
CTS Current transformer supervision
SOTF Switch on to fault
TCS Trip circuit supervision
VTS Voltage transformer supervision
YN Neutral admittance
Circuit breaker monitoring
Cold load pick-up
Inrush blocking
Limit value monitoring
Process Bus interface
VT Inputs 4 or 5 4 or 5 3 3 3
Opto Inputs (max) 70 70 12 16 16
Output Contacts (max) 38 36 11 16 16
RTDs (max) 10 10 10 10 10
Analogue Input / Output (max) 1/2 1/2 4/4 4/4 4/4
Function keys / Hotkeys with new HMI with new HMI -/ / /
Bay Control and Monitoring Graphical
including Interlocking
Mimic
ANSI PROTECTION FUNCTION P132 P139 P241 P242 P243
14 Speed switch input
25 Check synchronising
27LV Reacceleration
30/46/86 Unbalance / Lock out
32L/O/R Directional power
32R Reverse power
37 Loss of load
37P/37N Undercurrent
38/49 Thermal overload
40 Loss of field
46 Negative sequence overcurrent
47 Negative sequence over voltage
47N Neutral over voltage
50/51P Phase overcurrent
50BF Circuit breaker failure
50N/51N Ground fault
50S/51LR/ 51S Locked rotor
55 Out of step
59/27 Under / Over voltage
59N Residual over voltage
64N/32N Wattmetric earth fault
66/48/51 Startup monitoring
67N Ground fault directional
67N Ground fault direct. pulse detection
67N Sensitive directional earth fault
67P Phase directional
81O Over frequency
81U Under frequency
81R Rate of change of frequency
87M Motor differential
CTS Current transformer supervision
TCS Trip circuit supervision
VTS Voltage transformer supervision
Circuit breaker monitoring
Clio board
Anti Backspin
CT Inputs 5 8 8 9
VT Inputs 4 4 5 6
Opto Inputs (max) 24 32 32 32
Output Contacts (max) 24 32 32 32
High Break Contacts (max, option) 4 8 8 8
RTDs (max) 10 10 10 10
Analogue Input / Output (max) 4/4 4/4 4/4 4/4
Function keys / Hotkeys / / / /
VT Inputs 4 or 5 4 or 5 4 or 5 4 or 5 4 4 4 4 4 5
Opto Inputs (max) 70 82 36 70 8 16 32 24 16 24
Output Contacts (max) 32 48 48 28 14 21 32 46 16 32
High Break Contacts 4 4 4 16 12 4 12
RTDs (max) 1 1 1 1
Analogue Input / Output (max) 1/2 1/2 1/2 1/2
Function keys / hotkeys -/ / / / / /
Bay Control and Monitoring Graph.
including Interlocking
Mimic
ANSI PROTECTION FUNCTION P433 P435 P437 P439 P441 P442 P443 P444 P445 P446
21/21N Distance
25 Check synchronising
32 Directional power
Voltage controlled directional
32V
reactive power
46 Negative sequence overcurrent
46/67 Directional negative sequence
46BC Broken conductor
49 Thermal overload
50/27 Switch on-to fault
50/51N Earth fault
50/51P Phase overcurrent
50ST Stub bus protection
59/27 Over / under voltage
59N Residual over voltage
62/50BF Circuit breaker failure
67N Earth fault directional
67N Transient ground fault detection
67P Phase directional
67W Wattmetric earth fault
68 Out of step tripping
78 Power swing blocking
79 Auto-reclose 3 pole 1/3 p 1/3 p 3 pole 3 pole 1/3 p 1/3 p 1/3 p 3 pole 1/3 p
81 Over / under frequency
81R Rate of change of frequency
81P Under-frequency load shedding
85 Channel aided scheme logic
Capacitive voltage transformer
CVTS
supervision
TCS Trip circuit supervision
Voltage / current transformer
VTS/CTS
supervision
Delta directional comparison
YN Neutral admittance
Process Bus interface
Mutual compensation
VT Inputs 4 or 5 4 5 4 5
Opto Inputs (max) 46 8 16 16 16 32 24
Output Contacts (max) 30 7 14 14 14 32 32
High Break Contacts 16 4 4 8 12
RTDs (max)
Analogue Input / Output (max) 1/2
Function keys / hotkeys / -/ / / / / /
Bay Control and Monitoring
including Interlocking
ANSI PROTECTION FUNCTION P532 P541 P542 P543 P544 P545 P546
21 Distance
25 Check synchronising
46 Negative sequence overcurrent
49 Thermal overload
51LR Motor
50/51N Earth fault
50/51P Phase overcurrent
50BF Circuit breaker failure
59/27 Over / under voltage
64W Wattmetric earth fault
67N Earth fault directional
67N Sensitive directional earth fault
67N Transient ground fault detection
67P Phase directional
78 Power swing blocking
79 Auto-reclose 3 pole 3 pole 1/3 pole 1/3 pole 1/3 pole 1/3 pole
81 Under / over frequency
87L Line differential (terminal) 2 2/3 2/3 2/3 2/3 2/3 2/3
CTS CT supervision
TCS Trip circuit supervision
2 breaker configuration
2nd harmonic restraint
Copper wire signalling
Direct / permissive inter tripping
FO signalling
In Zone transformer
PLC signalling
SDH / Sonet networks
Vector compensation
Process Bus interface
VT Inputs 1 1 1 1 or 2 1 or 4 1 or 4
Opto Inputs (max) 4 34 40 34 12 24 24
Output Contacts (max) 14 22 30 22 12 24 24
Analogue Input / Output (max) 1/2 1/2 1/2 4/4 4/4 4/4
High Break Contacts 4 4 4 4 4 4 8
RTDs (max) 1 1 1 10 10 10
Function Keys / Hotkeys / / / / -/ / /
Bay Control and Monitoring
including Interlocking
ANSI PROTECTION FUNCTION P631 P632 P633 P634 P642 P643 P645
24 Overexcitation
46 Negative sequence overcurrent
47 Negative sequence over voltage
49 Thermal overload
50/51N Ground fault
50/51P Phase overcurrent
50BF Circuit breaker failure
59/27 Over / under voltage
59N Residual over voltage
67N Ground fault directional
67P Phase directional
81 Under / over frequency
87G/64 Restricted earth fault 2 3 3 2 3 3
87T Transformer diff. (windings) 2 2 3 4 2 3 3
CTS CT supervision
TCS Trip Circuit Supervision
VTS VT supervision
2 nd harmonic restraint
Overfluxing / 5th harmonic
Process Bus interface
CT Inputs 4 5 or 8
VT Inputs 5 4 or 5
Opto Inputs (max) 16 or 24 16 or 24 64
Output contacts (max) 15 or 24 14 or 32 60
High break contact (max) 4 16
ANSI PROTECTION FUNCTION P341 P841 P849
25 Check synchronising 1 or 2
27 Under voltage
47/27D Phase sequence voltage
50BF Breaker failure protection 1 or 2
59 Over voltage
59N Residual over voltage
64 Restricted earth fault
64N/32N Wattmetric earth fault
67P Phase directional with DLR option
79 Auto-reclose 1 or 2 CBs
81 Under / over frequency
81R Rate of change of frequency (df/dt+t)
dVq Voltage vector shift
TCS Trip circuit supervision
Tripping mode 1p / 3p
Ferroresonance detection
Process Bus interface
VT Inputs 3 2 2 1
Opto Inputs (max) 56 56 56 38
Output Contacts (max) 48 48 48 64
RTDs (max) 1 1 1 1
Analogue Input / Output (max) 1/2 1/2 1/2 1/2
Function Keys / Hotkeys / / / /
Bay Control and Monitoring
including Interlocking
© 2020 Schneider Electric. All Rights Reserved. Life Is On Schneider Electric is a trademark and the property of Schneider Electric SE, its subsidiaries and affiliated companies.
As the standards, specifications and designs develop from time to time, please contact Schneider Electric for confirmation of the information given in this document.
NRJCAT19835EN - 18 th September 2020