CLORIOUS - Microprocessor Based Temperature Controls
CLORIOUS - Microprocessor Based Temperature Controls
07-D
for electronic pressure control GB-1
Characteristics Function
• PI and PID performance The pressure input comes via a 4-20 mA
• Easy operation signal. The measured value of the con-
• For heating, cooling and pressure trolled variable is compared with the set
systems in maritime and industrial point value and adjusted via a PI or a PID
installations control structure.
• Manual- / automatic changeover The ER 2000-P permits direct reading of
• Robust self-optimization the actual temperature value (PV) and it
• Alarm indicating a deviation from set is secured from failure in the measuring
point, positive or negative circuit, i.e. the controller can be set to give
• User-defined operation level either a closing, an opening or remain
• 2- or 3-point output for controlling the in current position command in case of
actuator sensor short circuit or sensor break. The
error message Err appears in the LED
display PV.
Applications
The ER 2000-P controller is used for
constant pressure control. It is suitable for Communication
all heating and cooling control systems. The controller is equipped with a RS 485
The controller is primarily intended for communication module.
marine installations and other industrial
applications.
Technical Data
Line voltage Displays
}
Design 230 V AC Two 4 - digit 7 segment displays,
The ER 2000-P controller is designed for 115 V AC* -15 % / +10 %, 50 / 60 Hz LED, red,
panel mounting. 24 V AC* character height = 13 mm
For easy start-up it has optimization for *- optional (please specify)
automatic determination of favourable Alarm
control parameters. The optimization Power consumption approx. 7 VA Alarm type A, B, C;
starts when changing the set point or working contact normally closed
when switching over from manual mode Weight approx. 1 kg circuit principle
to automatic control. The optimization can
be disregarded. Permissible ambient temperature Relay
For easy operation it has three keys - - Operation 0 to 50°C Switching capacity: 250 V AC / 3 A
two for scrolling or changing values and - Transport and storage -25 to + 65°C Spark quenching element
an enter key. Two digital displays show
the process variable and the set point. 3 Degree of protection Data protection
LEDs indicate actuator opens, actuator Front: IP 65 according to DIN 40050 Semi - conductor memory
closes and alarm. Terminals: IP00
The controller can be switched from auto
mode to manual mode. In manual mode Design
the actuator can be opened, closed or For control panel installation
stopped in a certain position. 96 x 96 x 135 mm (W x H x D)
Three different alarm settings are pos- panel cut out 92 x 92 mm
sible:
A: Alarm at a deviation from the set Installation position arbitrary
point SP
B: Alarm at a fixed limit value Inputs 4-20 mA
C: Alarm at leaving a band around the
set point SP. Outputs 2- or 3-point
It can operate either as a three position Option: 4-20 mA
or as a two position controller and has
adjustable proportional band, integral Measuring accuracy
action time and derivative action time. 0.1% of the measuring range Subject to changes without notice.
Wiring diagram
Microprocessor-based controller ER 2000 Pressure
_
24 or 230 V AC + 24 VDC externall supply
50 Hz
V motor No.1 MP 24 2 14 1
Dimensions in mm
92
89
81
96
92 15
96 135