Trip Curve LaVergne, TN, USA
IEC-UIT-10PU(1)
Ultra Inverse Time
3000TC
k T
t d ( I ) = -------------------- × ---
10000
3000TC0707-IEC-UIT-DE50870a
⎛ ---I-⎞ – 1 β
α
⎝ I s⎠
where:
td = Operate time (sec)
1000
I = Current value
k = Coefficient values (see table)
Is = Current set point
α = Coefficient values (see table)
T = time setting (sec) at I/Is = 10 100
β = Coefficient values (see table)
NOTES:
Time in Seconds
1. The following minimum operate thresholds (I / Is)
apply:
10
SIT, VIT, LTI, EIT, UIT @ I / Is=1.2
RI, IAC-SIT, IAC-VIT, IAC-EIT @ I / Is=1.0
SIT-A, VIT-B, LTI-B, EIT-C, IEEE MI, IEEE VI, IEEE
EI @ I/ Is=1.1 12.5
2. When the monitored value is more than 20 times the 1 5
set point, the tripping time is limited to the value
2.5
corresponding to 20 times the set point.
If the monitored value exceeds the measurement capacity 1.2
of Sepam™ (40 IN for the phase current channels, 20 INr 0.8
for the residual current channels), the tripping time is 0.1
limited to the value corresponding to the largest 0.4
measurable value (40 IN or 20 INr). 0.2
0.1
0.01
1 10 100
Current I / Is
Curve Type Coefficient Values
k α β
Standard inverse / A 0.14 0.02 2.97
Very inverse / B 13.5 1 1.50
Long time inverse / B 120 1 13.33
Extremely inverse / C 80 2 0.808
Ultra inverse 315.2 2.5 1