Dongula - Wadi Halfa 220 KV Transmission Line Project: Reference Drawings

This document provides design data for two types of insulators used on the Dongula - Wadi Halfa 220kV Transmission Line Project in Sudan. It lists key specifications such as material, diameter, spacing, creepage distance, and withstand voltages for 100BLP and 210B insulators. The insulators are brown glazed porcelain and meet IEC standards for electromechanical load, coupling, and impulse voltage.

Uploaded by

Sara Ramli
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
61 views3 pages

Dongula - Wadi Halfa 220 KV Transmission Line Project: Reference Drawings

This document provides design data for two types of insulators used on the Dongula - Wadi Halfa 220kV Transmission Line Project in Sudan. It lists key specifications such as material, diameter, spacing, creepage distance, and withstand voltages for 100BLP and 210B insulators. The insulators are brown glazed porcelain and meet IEC standards for electromechanical load, coupling, and impulse voltage.

Uploaded by

Sara Ramli
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Reference Drawings

Drwg. No. Title


Revisions

Name Date Notes


□ Approval □ Approved as noted □ Returned □ Approval
for correction

DATE: SIGNITURE

GOVERNMENT OF THE REPUBLIC OF THE SUDAN


NATIONAL ELECTRICITY CORPORATION(NEC)
KHARTOUM - SUDAN
CONTRACTOR SUBCONTRACTOR

Dongula - Wadi Halfa 220 kV Transmission Line Project


H P E - D W - L 1 3 T L G - N T 0 0 3
Name Date
Prepared May.28,2009
Drawn May.29,2009 Design data - Insulators
Checked May.30,2009
Approved May.31,2009
Scale: Size A4 NIEPC Reg No: REV. 0
HPE DONGLA – WADI HALFA 220kV T/L PROJECT

DESIGN DATA – INSULATORS 
 
a. Insulator 100BLP

DESCRIPTION UNITS GUARANTEED


Material Brown glazed
porcelain
Appropriate Standard IEC 383
Insulator Type
Material of insulating part Porcelain
Colour of glaze brown
Insulator manufacturer and type number
Designation according to IEC 60305 yes
Electromechanical failing load kN 100
Maximum nominal diameter of the insulating
mm 280
part
Nominal spacing mm 146
Distance between centres of units mm 146
Standard coupling according to IEC 60120 mm 16
Minimum nominal creepage distance mm 450
Mass of units(nominal weight) kg 8
Minimum dry lightning impulse withstand
kV 80
voltage
Minimum wet lightning impulse withstand
kV 45
voltage
Minimum puncture voltage kV 120

Page: 1 of 2
HPE DONGLA – WADI HALFA 220kV T/L PROJECT

b. Insulator 210B

DESCRIPTION UNITS GUARANTEED


Material Brown glazed
porcelain
Appropriate Standard IEC 383
Insulator Type
Material of insulating part Porcelain
Colour of glaze brown
Insulator manufacturer and type number
Designation according to IEC 60305 yes
Electromechanical failing load kN 210
Maximum nominal diameter of the insulating
mm 300
part
Nominal spacing mm 170
Distance between centres of units mm 170
Standard coupling according to IEC 60120 mm 20
Minimum nominal creepage distance mm 450
Mass of units(nominal weight) kg 12.5
Minimum dry lightning impulse withstand
kV 80
voltage
Minimum wet lightning impulse withstand
kV 45
voltage
Minimum puncture voltage kV 130