0% found this document useful (0 votes)
393 views1 page

Untitled - LF1S - Load Flow Report PDF

This load flow report summarizes the results of a power flow analysis of an electrical network in Riyadh, Saudi Arabia. The network contains 5 buses operating at 110kV and 11kV. Bus1 and Bus3 are voltage regulated. The analysis found normal operating conditions with minor voltage deviations and power flows within equipment ratings.

Uploaded by

ناصر صبر
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
393 views1 page

Untitled - LF1S - Load Flow Report PDF

This load flow report summarizes the results of a power flow analysis of an electrical network in Riyadh, Saudi Arabia. The network contains 5 buses operating at 110kV and 11kV. Bus1 and Bus3 are voltage regulated. The analysis found normal operating conditions with minor voltage deviations and power flows within equipment ratings.

Uploaded by

ناصر صبر
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Project: Frist Step ETAP Page: 1

Location: Riyadh 19.0.1C Date: 13-11-2020

Contract: SN:

Engineer: Nasser Sabr Revision: Base


Study Case: LF
Filename: Frist Step Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

* Bus1 110.000 100.000 0.0 3.771 -0.533 0.000 0.000 Bus2 3.771 -0.533 20.0 -99.0

Bus2 110.000 99.923 0.0 0.000 0.000 0.000 0.000 Bus1 -3.768 0.358 19.9 -99.6

Bus3 3.768 -0.358 19.9 -99.6

* Bus3 11.000 100.000 -1.5 1.000 1.964 0.000 0.000 Bus4 1.940 0.487 105.0 97.0

Bus4-1 2.820 1.024 157.5 94.0

Bus2 -3.760 0.454 198.8 -99.3

Bus4 11.000 99.979 -1.5 0.000 0.000 1.940 0.486 Bus3 -1.940 -0.486 105.0 97.0

Bus4-1 11.000 99.998 -1.5 0.000 0.000 2.820 1.024 Bus3 -2.820 -1.024 157.5 94.0
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA