UN 5000 User's Manual: Operation
UN 5000 User's Manual: Operation
Chapter 7
Operation
7.1 Introduction
This part of the user manual describes how the excitation system has to be operated
and which points need to be observed for fault-free operation of the system. This
document mentions the necessary safety precautions and also contains a description
of the operating behaviour of the generator and the operation of the excitation system
in automatic and manual mode.
Turbine Generator
Field Generator
Current Voltage
Excitation
System
I Ug
f Synchronous
Network
Maschine
Excitation
System
D-axis
Ep
The way in which both types of machine function is essentially identical. However, if
one considers the simplified equivalent-circuit diagram in
Fig. 7-3, the following should be taken into account:
• For the Solid pole rotor design, the effective air gap in the d-axis and the q-axis is
approximately equal, thus producing the reactance's Xd ≈ Xq.
• In the case of salient-pole machines, the magnetic resistance's differ due to the
unequal air gaps, so that : Xd > Xq.
These different characteristics have a direct influence on the operating range of the
generator in network operation, as is illustrated in the following.
Basically, the same relationships apply to the operating conditions of the loaded
machines as to no-load operation . The sole difference is that the generator voltage is
the dominant regulating variable in island operation and the reactive power is the
dominant regulating variable in network operation.
The operating characteristics of the no-load machine and of the loaded machine in
network operation are examined in the following.
Ug
Saturation
Ugn
Generator
rated
voltage
No load
Ifo If
field current
∆U = Xd Ig ϕ
E Ug
p (E
MK
)
"rubber band"
T95_0154.DRW
Fig. 7-8):
ω mech
ω mech
ω mech
ω el ω el ω el
"rubber band"
T95_0154.DRW
limit of stability
Md
Μd2 ~ If2
Md1 ~ If1
drive
torque
δ2 δ1 δ
Sn
δ
-1 +1
-Q 1
xd Ifo + Q Reactive
Power
under over
excited Motor excited
2
1
Tie
Regional grid
Substation
Power station
T95_01 57.D RW
XTr Xe
G
RL UNet
In order to achieve the aims of automatic voltage regulation under stationary operating
conditions, it is necessary to partly correct the natural behaviour of machine and
network. For this purpose, the voltage regulator is influenced with a value dependent
on the current reactive current. The effect of this influence on the voltage regulation
becomes clear if one applies the analogy of the frequency and active power regulation
of the turbine.
Network Network
AVR
G Governor G R
Generator
R
T
Turbine
n,f U
P Q
T 9 5_ 01 5 8 .D R W
UG
pos. static
neg. static
-Q +Q
If = konst. S
∆U = Ig *Xd
XE
Ug Ugo
t
t=0
∆U = Ig *Xd
Ugo
t
t=0
Fig. 7-16 Reactive power surge with voltage regulation (automatic mode)
I S
PA U R0 R1
PA = .M
A I . XD
E . sin δ
PE = U . I = U .
XD U
E
Torque Equation
δ
MA- M E = . dω
dt
Inertia
speed
Fig. 7-17 Active power surge
If, by closing the circuit breaker S, the generator is now loaded with an additional
active power R1, the electrical power of the generator is immediately increased.
However, the drive power of the turbine initially remains unchanged and the balance
between mechanical drive power PA and output electrical power PE no longer exists.
The increase in the electrical power PE is primarily produced by the kinetic energy of
all rotating masses, which are coupled with the shaft. This means that the rotational
speed decreases until the rotational speed regulator has increased the shaft torque by
adjusting the quantity of gas, steam or water passing through the turbine.
Whereas under stationary conditions the electrical torque is in balance with the drive
torque MA, the moment of inertia of the entire shaft arrangement Θdω/dt plays a role
during transient events. The following dynamic equation must be fulfilled at each
instant:
MA- M E = . dω
dt
Ug
Overvoltage relay
with constant field current
with AVR (static excitation system)
Uo
IQ x Xd "
t
t=0 1 Sec.
t
t=0 1 sec
7.3.1 General
The UNITROL 5000 excitation system is an integral component of the power station
installation. It is normally operated by remote control from the control room. The local
control panel, directly on the front of the excitation system, is only used for
commissioning and test purposes or as an emergency control option. If the power
station installation features a higher-level control system, the commands to the
excitation system are given by this power station control system.
The operating personnel must be familiar with the layout of the control and display
elements and with the effects of the commands on the excitation system. Using these
control and display elements, the operating personnel are in a position to adapt the
generator, via the internal control and regulating circuits of the excitation system, to
the operating conditions of the power station and/or of the network.
The excitation system is controlled in two ways:
• REMOTE control from the control room with keyboard commands. The commands
are passed to the excitation system as binary signals.
• REMOTE control from the control room with monitor screen control. The
commands are passed to the excitation system as binary signals or via a field bus.
• LOCAL control using the local control elements integrated in the excitation system
(local control panel).
The shaded areas of the local commands mean that these only become effective if the
ENABLE key is pressed simultaneously on the local control unit.
In the following, the two forms of control REMOTE and LOCAL will be explained in
detail.
Excitation ON / OFF
The command EXCITATION ON is used to initiate the excitation of the generator. The
excitation feeds the generator rotor with field current so that the generator voltage
rapidly builds up to nominal voltage.
The On command remains without effect as long as a TRIP command is active. If the
excitation breaker is still open when the command EXCITATION ON is given, this will
be closed automatically. Only after the excitation breaker is closed is the excitation
enabled and the field current begins to flow. A typical Start/Stop sequence for
generators is shown in Fig. 7-20.
The following preconditions must be fulfilled for excitation to start successfully:
• The excitation breaker must already be in ON position.
• No Off command or Trip signal may be active.
• The rotational speed should be greater than 90% of the nominal rotational speed.
• If the converter transformer of the excitation system is supplied directly from the
generator terminals, the auxiliary voltage for build-up of excitation must be present.
The command EXCITATION OFF switches off the excitation of the generator
immediately. The converter in the excitation system is thereby switched to AC
converter operation (feedback of the field energy) and the discharge resistor is
switched parallel to the rotor winding, so that the generator discharges quickly via the
converter and the discharge resistor. Parallel with the command EXCITATION OFF,
the excitation breaker is also opened. After 60 s, the firing pulses to the converter are
blocked so that this is completely blocked and switched off.
The excitation can only be switched off remotely if the generator circuit breaker is
already opened (generator is in no-load condition).
Fig. 7-20
r.p.m.
Enable No fault ON
ABB Schweiz AG
excitation *) no alarm OFF
FCB On 1 9
ON
FCB Off OFF
2
Excitation Exc. 8
Document number
On
ON
ON / OFF
Exc. OFF
Off
4 7
Load operation (on network)
Machine
breaker
Super- Q/cos ϕ
imposed On ON
3BHS114940 E80
Regulation
Q/cos ϕ OFF
Off
ON / OFF
Reference 3
value change
Reset to 100% Synchron. system By operating Reset to 100%
Lang.
personnel 5 6
en
Higher/lower
Rev. ind.
MANUAL
Perm. reset to 90% Ifo Compensation to AUTO-Regulator Perm. reset to 90% Ifo
Super-
imposed
By operating
Sheet
regulation personnel
7-23
*) Remote operation: Enable via external locking functions
After the excitation is switched on, the generator voltage typically builds up as follows
UG
100%
rt
ta
fts
So
Field flashing
Channel I
COB / MUB
AVR AUTO
HAND
FCR
CH l
Channel Il CH lI
COB / MUB
AVR AUTO
HAND
FCR
Fig. 7-22 Dual channel system with voltage regulator and current regulator
COB / MUB
AVR AUTO
HAND
FCR
AVR AUTO
HAND
FCR
CH l
FCR
EGC Emergency
CH lI Channel Il Channel I
COB / MUB
AVR AUTO
HAND
FCR
FCR
EGC
Emergency
Channel II
Main channel
COB / MUB
AVR AUTO
MAN
FCR
FCR
EGC
Emergency Channel
raise
raise
Setpoint
Setpoint
Q/cosϕ
AVR
lower Regulator
lower
The reactive power regulator / power factor regulator features its own setpoint setting
(setpoint integrator). When the superordinated regulator is switched off, this setpoint
setting always follows the actual value (current reactive power Q / current power factor
cosPhi). This means that the transition from voltage regulator to superordinated
regulator has no immediate effect on the operating point of the generator. Only when
the setpoint (setpoint setting of the superordinated regulator) is later adjusted by
means of the HIGHER-/LOWER commands (see 7.3.2.8), does the reactive power /
power factor also change.
7.3.2.8 Higher / Lower (↑/↓) commands with feedback indications MIN / MAX
The ↑/↓ commands from the control room control the setpoints of both the operating
modes AUTO and MANUAL / AUTO, MANUAL and the superordinated regulator. A
setpoint is only adjusted by these commands if its operating mode is activated.
a) In AUTO mode
In AUTO mode, the setpoint of the generator voltage is adjusted by means of the ↑/↓
commands. In no-load operation, changing this setpoint adjusts the generator voltage,
in operation under load this adjusts the reactive power. If the operating limits of rotor
and/or generator stator have been exhausted, corresponding limiting regulators
intervene and prevent the effect of the ↑/↓ commands in the direction of limitation.
If the setpoint for the generator voltage reaches its minimum or maximum setting value,
the message "Active regulator MIN-POS / MAX-POS" appears. If the ↑- and ↓
commands are given together, no adjustment of the setpoint takes place. When the
excitation is switched on, the setpoint for the generator voltage is automatically set to
its nominal value.
4 mA
LL REF AIx LIVE ZERO
ALARM AIx FAIL
0 mA AIx LOW VALUE
-Q/COS PHI REFERENCE VALUE
8-lines display
Cursor key
By pressing the Cursor key, one of the line positions 1...8 or 1..4 on the display can be
# selected. The current line is highlighted with the channel number shown in reverse
contrast. When the last line is reached, it jumps back to the first line. The Cursor key is
only active in the (numerical or bar display) analogue signal display.
Scroll key
When the Scroll key is pressed in the (numerical or bar display) analogue signal
display, the channel number (in reverse contrast) and its analogue value
changes.
When pressed in the fault message, all fault messages in lines 2...8 move up or
down by one position. The first line showing the first fault always remains in
place.
Page key
When the Page key is pressed, the channel numbers change by 10 positions or
the fault numbers by 6 positions. Otherwise functions like the Scroll key.
In order to increase the service life of the LCD display, the display and background
illumination are switched off after 60 minutes have elapsed without a key being
pressed. The panel display is switched on again If one of the 10 function keys is
pressed or if a fault message occurs.
The shaded areas of the local commands mean that these are only effective if the
ENABLE key on the local control unit is pressed simultaneously.
Fig. 7-29
r.p.m.
Enable No fault ON
excitation *) no alarm OFF
ABB Schweiz AG
FCB On 1 9
ON
FCB Off OFF
2 8
Excitation Exc.
On
Document number
ON / OFF
Exc. OFF
Off
4 7
Load operation (on network)
Machine
breaker ON
OFF
ON / OFF
Super- Q/cos ϕ
imposed On
ON
Regulation
Q/cos ϕ OFF
Off
3BHS114940 E80
ON / OFF
Reference 3
value change
Reset to 100% Synchron. system By operating Reset to 100%
personnel 5 6
Higher/lower
Lang.
en
MANUAL
Perm. reset to 90% Ifo Compensation to AUTO-Regulator Perm. reset to 90% Ifo
Super-
Rev. ind.
imposed
By operating
regulation personnel
Sheet
7-40
7.5.3 Checks during operation
The following periodical checks should be carried out during operation:
a) In the control room:
• No limiter active.
• Setpoints of the active regulator are not at limit setting.
• Channels are balanced, ready for switchover.
• Excitation current, generator voltage and reactive power are stable.
The correct function of the field current regulator for MANUAL mode is continually
checked by means of extensive monitoring devices. Nonetheless, it is recommended
that, periodically, e.g. following start-up, this regulator be switched briefly in order to
test that it is functioning correctly.
The correct function of the inactive channel is continually checked by means of
extensive monitoring devices. Nonetheless, it is recommended that, periodically, e.g.
following start-up, this regulator be switched briefly in order to test that it is functioning
correctly.
7.5.5 Emergency-OFF
Faults in a number of peripheral devices in certain cases can lead to a situation that
neither REMOTE nor LOCAL control of the excitation system is possible. However, it
must still be possible to switch off the excitation in an emergency. An emergency
shutdown can be carried out using the local Emergency-Off pushbutton on the
excitation cabinet // "External Trip" input on terminal X21 :1-51 / X22 :1-51 (see also
Hardware schematic, sheet 904).
Note With the generator circuit breaker closed, the excitation system cannot be
switched off (by remote control) (the generator circuit breaker must be
opened beforehand).
The Emergency-OFF switch should only be used if it is impossible to
switch off using the normal Off command.