000 Machine Report VVI PDF
000 Machine Report VVI PDF
This action is due to the property of the magnetic circuit. By first increasing and
then decreasing the field current a hysteresis loop is formed because of the curve
in the laboratory. The field current must always increase and should never be
decreased until maximum field current is reached. Then the current should only
be decreased and never increased until a zero value of current is reached.
Increasing or decreasing the current in order to obtain specific values will produce
small hysteresis loops and thus yield confusing results. Another problem that
arises while obtaining the magnetization curve in the laboratory is the difficulty of
maintaining a constant speed. Since the induced voltage depends upon the flux
and speed will produce a proportional variation in the induced voltage .
This is not too serious because the voltage at the desired speed may be calculated
when the induced voltage at any other speed is known.
Apparatus :
01. Generator (250 v,18 A)
02. Prime mover(synchronous machine -1480 rpm)
03. Techometer
04. Voltmeter(0-450 V)
05.Ammeter(0-2A)
retentivity of the magnetic material. Care should be taken when obtaining this
Circuit diagram:
Data table:
Shunt generator :A shunt generator has the field circuit connected directly across
the armature. Appliances, motors, light bulbs and other electrical devices
connected in parallel across the generator terminals represent a load on the
generator. The generator furnishes power to this load. As more devices are
connected in parallel , the load the generator increases , that is the generator
current increases. Because the generator current increases the terminal voltage
of the generator decreases. There are three factors that cause these decrease in
voltage armature circuit resistance , armature reaction , and reduction in field
current.
Armature circuit resistance : Like every electronic circuit , the armature circuit of
the generator contains resistance. This resistance includes the resistance of the
copper conductors of the armature winding, the commutator , contact resistance
between brushes and commutator , and the brushes themselves . When no
current flows through the armature, there is no IR drop in the armature and the
voltage at the terminals is the same as the generated voltage. However , when
there is current in the armature circuit , a voltage drop exists due to the armature
resistance and the terminal voltage is less then the generated voltage . The
terminal voltage may be calculated from the following equation:
V =Eg –IaRa
Where ,
Eg =generated voltage.
Apparatus:
3. Voltmeter (0-450V)
Circuit diagram:
Data table:
Field current 0.48 0.48 0.47 0.46 0.45 0.44 0.43 0.42 0.41
Terminal voltage 234 230 226 222 218 214 210 207 203
E=KφS
But E=Vt-IaRa
So we get
S= (Vt-IaRa)/Kφ
E=KφS
T=K φ Ia
4. The increase in torque will increase the speed and magnitude of the
counter EMF of the motor.
5. The increase in the magnitude of the counter EMF of the motor about the
reduction of the armature current.
Apparatus:
03.Ammeter(0-2A)
04. Tachometer
Circuit diagram:
DATA TABLE
Field current .615 .65 .7 .75 .8 .85 .9 .95 1
Speed 1500 1420 1351 1283 1220 1167 1122 1081 1044
When we have done the experiment we did not open the field
circuit because if we open this then the motor winding to be pulled out.
Experiment No: 07
Name of the Experiment: Open circuit test and short circuit test of a single
phase transformer.
Theory: We know that there the two types of losses of an transformer, such as
copper loss and core loss. Copper loss is a variable loss and depends on current
and core loss is a fixed loss and depends upon the voltage. Now the efficiency of a
transformer is defined as the ratio of output power to input power. Again the
input power is equals to the sum of output power and losses. The losses can be
find out with open circuit test and short circuit test. The copper loss can be
obtained by short circuit test and core loss can be obtained by the open circuit
test. For Short Circuit Test first 0 voltage is applied to high voltage side and then
the voltage is increased until for which the rated current flows in low voltage side.
Now the data or reading of the meters are taken. Again for Open Circuit Test 0
voltage is applied to low voltage side and then the voltage is increased until for
which the rated voltage is obtained from high voltage side. Now the data or
reading of the meters are taken.
Apparatus:
01.Transformer(150 V per coil,1 A)
02.Voltmeter(0-450 V)
03.Ammeter(0-2 A)
04.Wattmeter(0-1200 W)
05.Variac(0-240 V)
Circuit Diagram:
Data Table:
Test Voltage Current Power
Calculation:
For short circuit test the applied voltage is very low and core loss is negligible. So
it is assumed that current through Ro and Xo is zero.
So we can write,
Rsct=R1+R2=P/Isct2=10Ω
Zsct=Vsct/Isct=9.67Ω
Xsct=X1+X2= =2.55 jΩ
For open circuit test Cu loss is negligible i.e. loss in R1 is negligible and voltage
drop at R1 & X1 is negligible. In this case loss is assumed only in the core circuit.
Roct=Voct2/P=2857.14Ω
Goct=1/Roct=3.5×10-4mho
Zoct=Voct/Ioct=4000Ω
Yoct=1/Zoct=2.5×10-4 mho
Xoct=1/Boct= -4082.48 jΩ
% Efficiency=(input-losses) ×100/input
% Efficiency=(150-24)*100/150
=84%
Discussion: Two tests are necessary to measure the losses of a transformer. The
short circuit test, with rated current measured in either the high side or low side
windings, gives the full load copper losses. Copper losses at any other load may
then be calculated. With rated voltage impressed on either winding and the other
winding open circuited, the power supplied to the transformer then represents
the core losses at rated load conditions as well as at any other normal operating
point.