PDU Description
PDU Description
Description
Disclaimer
The contents of this document are subject to revision without notice due to
continued progress in methodology, design and manufacturing. Ericsson shall
have no liability for any error or damage of any kind resulting from the use of this
document.
Contents
1 Product Overview 1
1.1 Purpose 1
1.2 Variants 1
2 Function Description 8
2.1 PDU 01 01 8
2.2 PDU 01 03 9
2.3 PDU 01 04 10
2.4 PDU 01 05 11
2.5 PDU 01 06 11
2.6 PDU 02 01 and PDU 02 02 12
2.7 Power Distribution Control 13
3 Technical Data 18
1 Product Overview
1.1 Purpose
The main function of the PDU is to distribute −48 V DC power to DC-powered
units. The PDU receives one feeding of input voltage and distributes the input
voltage to separate fused outputs through output connectors.
The PDUs are used for either internal or external power distribution.
1.2 Variants
Table 1 lists all PDU variants.
1.2.1 PDU 01 01
PDU 01 01 is only used for internal power distribution and is placed in a power
subrack.
PDU 01 01 is available in two variants, either with R-state R4 or lower and with
R-state R5 or higher, where the R-state is the last part of the product number.
PDU 01 01
Fault Sys Volt
Test port
EC Bus
Oper
CB 1 CB 2 CB 3 CB 4 CB 5 CB 6 CB 7
H-UP <19A <16A <19A <16A <19A <16A
PCR PCR PCR PCR PCR PCR PCR
Ge0085C
+ - PDU 01 01
Sys Volt
EC Test port
1 2 3 4 5 6 7
Ge0085D
Note: PDU 01 03, PDU 01 04, PDU 01 05, and PDU 01 06, have no hold-up
channels.
1.2.2 PDU 01 03
PDU 01 03 is used for power distribution to both internal and external consumers.
Figure 3 shows the front of PDU 01 03.
+ - PDU 01 03
Sys Volt
EC Test port
Ge1727A
1.2.3 PDU 01 04
PDU 01 04 is used for power distribution to both internal and external consumers.
Figure 4 shows the front of PDU 01 04.
PDU 01 04
EC Sys Volt
+ - Test port
Ge1727D
1.2.4 PDU 01 05
PDU 01 05 is used for internal power distribution and is placed in a power
subrack. Figure 5 shows the front of PDU 01 05.
PDU 01 05
1 ON OFF
1 2
2 ON OFF
Ge1727C
1.2.5 PDU 01 06
PDU 01 06 is used for power distribution to both internal and external consumers
and is placed in a power subrack. Figure 6 shows the front of PDU 01 06.
PDU 01 06
ON
ON
I
EC
Ge8528B
1.2.6 PDU 02 01
PDU 02 01 is used for power distribution to internal consumers and is placed in a
19 inch cabinet slot. Figure 7 and Figure 8 show PDU 02 01.
11
PCR EC Bu
s
10
PCR
8
PCR 11
8
PCR 10
7 9
PCR
6 8
PCR
5 7
PC R
4
PCR 6
3 5
PCR
2
PC R 4
1 3
PCR
2
02 01 11
PC R
P DU
Ge0787A
Figure 7 PDU 02 01
Note: There are 11 Priority load, Cold-start, and Remote control (PCR)
switches under the switch cover on top of PDU 02 01 as shown in Figure
7.
PDU 02 01 1 2 3 4 5 6 7 8 9 10 11 EC Bus
1 11 EC Bus
PDU 02 01
Ge0714A
1.2.7 PDU 02 02
PDU 02 02 is used for power distribution to internal consumers and is placed in a
19 inch cabinet slot. It is identical to PDU 02 01, except that it uses a different
cable connector and different mechanics for the 19 inch subrack. Figure 9 shows
PDU 02 02.
11
PCR EC Bu
s
10
PCR
8
PCR 11
8
PCR 10
7 9
PCR
6 8
PCR
5 7
PC R
4
PCR 6
3 5
PCR
2
PC R 4
1 3
PCR
2
02 02 11
PC R
P DU
Ge1038A
Figure 9 PDU 02 02
Note: There are 11 PCR switches under the switch cover on top of PDU 02 02
as shown in Figure 9. It has no hold-up channels.
2 Function Description
2.1 PDU 01 01
PDU 01 01 has the following functions:
Figure 10 and Figure 11 show the block diagrams of PDU 01 01, R-state R5 and
PDU 01 01, R-state R4 with the maximum continuous current value.
EC bus
7×E-fuse
Ge0122D
Supervision
Control
EC bus
7×E-fuse
Ge0122D
2.2 PDU 01 03
PDU 01 03 has the following functions:
— 6 E-Fuse outputs
Figure 12 shows the block diagram of PDU 01 03 with the maximum continuous
current value.
EC Bus Supervision
Control
DC Input
6 x E-Fuse
Ge1728A
2.3 PDU 01 04
PDU 01 04 has the following functions:
— 6 E-Fuse outputs
Figure 13 shows the block diagram of PDU 01 04, with the maximum continuous
current value.
EC Bus Supervision
Control
6 x 20 A without hold-up
(output 1 to 6)
DC Input
6 x E-Fuse
Ge1728C
2.4 PDU 01 05
PDU 01 05 has the following functions:
Figure 14 shows the block diagram of PDU 01 05 with the two circuit breakers.
2 x CB
Ge1728D
2.5 PDU 01 06
PDU 01 06 has the following functions:
— Two outputs
Figure 15 shows the block diagram of PDU 01 06 with the two circuit breakers.
Supervision
EC Bus
Control
2 x CB
Ge8678A
— 11 E-Fuse outputs
Figure 16 shows the block diagram of PDU 02 01 and PDU 02 02 with the
maximum continuous current value.
DC Input
11xE Fuse
Ge0717B
Note: Modular PDUs (ECMs) use software defined PCR settings. For more
information about these settings, for example, the Class Power
Distribution, refer to Managed Object Model (MOM). For more
information about ECMs, refer to PDU Description for PDU System.
The non-modular PDUs have the following three PCR switches from left to right:
— Priority Load
— Cold Start
— Remote Control
On
Off
When a switch is set in the upper position, the PCR function is enabled (On), and
when a switch is set in the lower position, the function is disabled (Off).
The Battery Fuse Unit (BFU) continuously monitors the systemVoltage. When
the battery voltage drops below the specified level,
MainLoadUndervoltageDisconnect, the BFU sends an action signal to the PDU.
When this signal is received, the PDU disconnects all outputs where the P switch
is set in position Off (disabled).
EC Bus Supervision
BFU
Control
DC Input
Battery
string
Ge10742C
On When the P switch is set in the upper (On) position, that is,
PriorityLoadenabled, the load connected to this output will be
disconnected when the systemVoltage is below
priorityLoadUndervoltageDisconnect.
Off When the P switch is set in the lower (Off) position, that is,
PriorityLoaddisabled, the load connected to this output will
be disconnected when the During battery backup, the RBS can
use two different voltage levels where the respective selected
loads are switched off.systemVoltage is below
mainLoadUndervoltageDisconnect.
During battery backup, the RBS can use two different voltage levels where the
respectiveAll units connected to the PDU ports set in the lower (Off) position
(defined as main loads) will be disconnected at the higher voltage level, defined
by attribute mainLoadUndervoltageDisconnect.
This feature can be used to disconnect less prioritized loads, such as radio units
which are not critical during the limited time when the batteries power the node.
This means that some services can be cut off earlier than others, for example:
A very common usage is to keep the DU and link transmission alive longer than
the radio service.
The climate system in the RBS requires that the SCU, and preferably the DU are
operational as both control the fans. Hence both SCU and DU are set to,
PriorityLoadenabled. If the SCU and the DU are not defined as priority loads,
that is their outputs are set to PriorityLoadenabled, the fans will stop running
when the MainLoadDisconnect level is reached. When this happens, the
remaining capacity in the battery cannot be used since no cooling is available.
At startup, the PDU checks the input signal for the cold-start function. When
this signal is detected at startup, the PDU only turns on the outputs that are
enabled as cold outputs.
Note: For outdoor cabinets without heaters, all cold-start switches must be
enabled (upper position).
For outdoor cabinets equipped with heaters, the cold-start switches for
the following units should be enabled (upper position):
— SCU
— DC heater
The Baseband or DU can control the output when the switch in the PDU is
configured as remotely controllable. Both PDUs with PCR switches and modular
PDU variants can be controlled by software if the software supports remote
control of E-Fuses.
Note: If the R switch is set to disabled, the output E-fuse cannot be remotely
controlled. The corresponding settings for software controlled PDUs ,
that is, ECM PDUs without PCR switches are managed by attribute
modifications in the MOM, refer to Managed Object Model (MOM).
3 Technical Data
For information about the optical indicators, refer to Indicators, Buttons, and
Switches.
4.1 PDU 01 01
This section describes the interfaces on both revisions of PDU 01 01: R4 and R5.
Table 3 lists details of the external interfaces on PDU 01 01, R-state R5.
Sys Volt Test port for system voltage Hirschmann™ MBU 2, Front
Test port 931-337-000
P Priority load function switch Hardware selector Front
C Cold-start function switch Hardware selector Front
R Remote control function switch Hardware selector Front
(1) For more details about optical indicators, refer to Indicators, Buttons, and Switches.
Table 4 lists details of the external interfaces on PDU 01 01, R-state R4.
Sys Volt Test port for system voltage Hirschmann MBU 2, Front
Test port 931-337-000
P Priority load function switch Hardware selector Front
C Cold-start function switch Hardware selector Front
R Remote control function switch Hardware selector Front
(1) For more details about optical indicators, refer to Indicators, Buttons, and Switches.
4.2 PDU 01 03
This section describes the interfaces on PDU 01 03.
Sys Volt Test port for system voltage Hirschmann MBU 2, Front
Test port 931-337-000
P Priority load function switch Hardware selector Front
C Cold-start function switch Hardware selector Front
R Remote control function switch Hardware selector Front
Optical indicator, green N/A Front
(1) For more details about optical indicators, refer to Indicators, Buttons, and Switches.
4.3 PDU 01 04
This section describes the interfaces on PDU 01 04.
Sys Volt Test port for system voltage Hirschmann MBU 2, Front
Test port 931-337-000
P Priority load function switch Hardware selector Front
C Cold-start function switch Hardware selector Front
R Remote control function switch Hardware selector Front
Optical indicator, green N/A Front
(1) For more details about optical indicators, refer to Indicators, Buttons, and Switches.
4.4 PDU 01 05
This section describes the interfaces on PDU 01 05.
(1) For more details about optical indicators, refer to Indicators, Buttons, and Switches.
4.5 PDU 01 06
This section describes the interfaces on PDU 01 06.
4.6 PDU 02 01
This section describes the interfaces on PDU 02 01.
(1) For more details about optical indicators, refer to Indicators, Buttons, and Switches.
4.7 PDU 02 02
This section describes the interfaces on PDU 02 02.
(1) For more details about optical indicators, refer to Indicators, Buttons, and Switches.