0% found this document useful (0 votes)
132 views10 pages

100 617 - DE - Booster - 3pump - Standby - Submittal PDF

The document is a submittal for a design envelope pump package including 3 duty pumps, 1 standby pump, and a control panel for a domestic water booster system. It includes pump design data, motor design data, control panel specifications, optional equipment, pump performance curves, and dimensional drawings of the pump models. The package is capable of a maximum combined flow of 227.5 USgpm and maximum combined head of 790.1 feet.

Uploaded by

Efrain Corro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
132 views10 pages

100 617 - DE - Booster - 3pump - Standby - Submittal PDF

The document is a submittal for a design envelope pump package including 3 duty pumps, 1 standby pump, and a control panel for a domestic water booster system. It includes pump design data, motor design data, control panel specifications, optional equipment, pump performance curves, and dimensional drawings of the pump models. The package is capable of a maximum combined flow of 227.5 USgpm and maximum combined head of 790.1 feet.

Uploaded by

Efrain Corro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

DE S IG N E NVE LO PE 6 80 0 G 3 DU T Y PUMP | File No: 100.

617

AN D 1 STAN DBY, DOMESTIC WATER BOOSTER WITH


Date: april 19, 2019
Supersedes: 100.617

STANDBY | N 3 3 0 2 0 2s — N 3 9 0 3 0 2s | S U B M I T T A L
Date: june 27, 2017

Job: Representative:

Order by: Date:

Engineer: Submitted by: Date:

Contractor: Approved by: Date:

pump de sig n data moto r de sig n data


No. of pumps: Tag: hp: rpm: 3600
Total package capacity: USgpm (L/s) Frame size: Enclosure:  odp  tefc
Pump capacity: USgpm (L/s) Head: ft (m) Volts: Hertz: 60 Hz Phase: 3
Liquid: Viscosity: Efficiency: nema premium 12.12
Temperature: °f (°c) Specific gravity:

note: Test tolerance according to iso 9906 Grade 2b


±8% on measured flow and ±5% on measured head

o p tio nal h e ader fl an g e co n n ec tio n s co ntro l pan el s pecific atio n s


Suction  ansi 125/150 nema 4 type enclosure
Discharge  ansi 125/150  ansi 250/300 Low suction shutdown and auto re-start
Main disconnect with interlock
Fused motor protection
co n n ec tio n o rientatio n Fused control circuit transformer
Power on indication
Suction  Right
 Left
Motor run indication
Discharge  Right
 Left
Virtual h-o-a for each pump
No-flow shutdown and automatic alternation
Soft fill mode
drive data
Pressure setback mode
Enclosure: ul type 12 ul or csa labeled
emi/rfi control: Integrated filter designed to meet en61800-3 Field adjustable set points, alarms and timers
Harmonic suppression: Integrated dc link reactors Flash memory storage
Cooling: Fan-cooled through back channel No-flow pressure optimization
Ambient temperature: -10°c to +45°c up to 1000 meters
above sea level
(-14°f to +113°f, 3280 ft)
o p tio nal equipment
su bmi tta l Design envelope 6800 g
n330202s - n390302s 3 duty pumps & 1 standby, Domestic water booster with standby

design envelope capability data


envelope curve max flow max head best eff % each motor frame size
pump
number usgpm (L/s) ft (m) point (bep) motor hp odp tefc
 N3 3 0 2 0 2S VMS-10 02B 226.2 (14.27) 97.6 (29.7) 67.60% 2 — 5 6C
 N3 3 0 4 0 2S VMS-1004BE 206.2 (13.01) 196.4 (59.9) 67.60% 3 — 18 4TC
 N3 3 0 6 0 2S VMS-1006B 218.5 (13.79) 294.6 (89.8) 67.60% 5 — 18 4TC
 N3 3 0 9 0 2S VMS-1009B 218.3 (13.77) 444.4 (135.5) 67.60% 7.5 18 4TC —
 N3 312 0 2S VMS-1012B 218.3 (13.77) 592.6 (180.6) 67.60% 10 — 215TC
 N3 316 0 2S VMS-1016B 227.5 (14.35) 790.1 (240.8) 67.60% 15 215TC —
 N3 5 010 2S VMS-3201 556.5 (35.11) 88.6 (27.0) 68.70% 5 — 18 4TC
 N3 5 0 222S VMS-3202-2 556.5 (35.11) 148.8 (45.4) 68.70% 7.5 18 4TC —
 N3 5 0 3 22S VMS-3203-2 558.1 (35.21) 237.0 (72.2) 68.70% 10 — 215TC
 N3 5 0 4 3 2S VMS-3204-3 558.1 (35.21) 314.6 (95.9) 68.70% 15 215TC —
 N3 5 0 5 0 2S VMS-3205 549.2 (34.65) 449.9 (137.1) 68.70% 20 — 2 5 6TC
 N3 5 0 6 0 2S VMS-3206 555.9 (35.07) 546.1 (166.5) 68.70% 25 — 2 8 4TSC
 N3 6 010 2S VMS-4501E 833.3 (52.57) 116.7 (35.6) 83.10% 7.5 — 215TC
 N3 6 0 212S VMS-4502-1 839.6 (52.97) 200.4 (61.1) 83.10% 15 215TC —
 N3 6 0 3 22S VMS-4503-2 846.8 (53.42) 290.2 (88.5) 83.10% 20 — 2 5 6TC
 N3 6 0 5 0 2S VMS-4505 830.1 (52.37) 611.3 (186.3) 83.10% 40 — 3 24TSC
 N37010 2S VMS-6401E 1177.8 (74.31) 123.2 (37.6) 84.70% 10 — 215TC
 N370 212S VMS-6402-1 1217.5 (76.81) 226.6 (69.1) 84.70% 20 — 2 5 6TC
 N370 3 22S VMS-6403-2 1217.5 (76.81) 339.1 (103.4) 84.70% 30 — 2 8 6TSC
 N370 422S VMS-6404-2 1196.7 (75.50) 475.2 (144.8) 84.70% 40 — 3 24TSC
 N3 8 010 2S VMS-1501B 350.5 (22.11) 62.6 (19.1) 72.50% 2 5 6C —
 N3 8 0 3 0 2S VMS-1503BE 352.7 (22.25) 189.8 (57.9) 72.50% 5 — 18 4TC
 N3 8 0 4 0 2S VMS-1504BE 352.7 (22.25) 253.1 (77.1) 72.50% 7.5 — 215TC
 N3 8 0 5 0 2S VMS-1505B 350.7 (22.13) 316.4 (96.4) 72.50% 10 — 215TC
 N3 8 070 2S VMS-1507B 352.7 (22.25) 442.9 (135.0) 72.50% 15 215TC —
 N3 810 0 2S VMS-1510B 354.7 (22.38) 639.9 (195.0) 72.50% 20 — 2 5 6TC
 N3 9 0 2 0 2S VMS-2002B 393.8 (24.84) 143.5 (43.7) 73.00% 5 — 18 4TC
 N3 9 0 3 0 2S VMS-2003B 394.0 (24.86) 216.5 (66.0) 73.00% 7.5 18 4TC —

Notes:
1 nsf 61 and nsf 372 certified complete package assembly.
2 Standard right hand connection orientation illustrated, please
indicate alternate connection orientation, if required.
3 All pumps are equal.
4 Standard grooved header connections.
Optional flanged ansi 150# or 300# connections available.
5 Optional tank shipped loose, installed by others.
Design envelope 6800 g submit ta l
3 duty pumps & 1 standby, Domestic water booster with standby n330202s - n390302s

max working
booster a b c max d e f g h j j1 weight
pressure
model
inches (mm) psi (bar) lbs (kg)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
 N3 3 0 2 0 2S 232 (16) 1034 (469)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
 N3 3 0 4 0 2S 232 (16) 1123 (509)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
 N3 3 0 6 0 2S 232 (16) 1136 (515)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
 N3 3 0 9 0 2S 232 (16) 1374 (623)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 8.25
 N3 312 0 2S 363 (25) 1746 (792)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (210)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 8.25
 N3 316 0 2S 363 (25) 1914 (868)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (210)
96.48 39.63 62.70 8.06 86.61 22.72 7.87 31.50 9.00 9.00
 N3 5 010 2S 232 (16) 1722 (781)
(2451) (1007) (1592) (205) (2200) (577) (200) (800) (229) (229)
96.48 39.63 62.70 8.06 86.61 22.72 7.87 31.50 9.00 9.00
 N3 5 0 222S 232 (16) 1883 (854)
(2451) (1007) (1592) (205) (2200) (577) (200) (800) (229) (229)
96.48 39.63 62.70 8.06 86.61 22.72 7.87 31.50 9.00 9.00
 N3 5 0 3 22S 232 (16) 2407 (1092)
(2451) (1007) (1592) (205) (2200) (577) (200) (800) (229) (229)
96.48 39.63 62.70 8.06 86.61 22.72 7.87 31.50 9.00 9.00
 N3 5 0 4 3 2S 232 (16) 2487 (1128)
(2451) (1007) (1592) (205) (2200) (577) (200) (800) (229) (229)
96.48 41.63 62.70 8.06 86.61 22.72 7.87 31.50 9.00 10.00
 N3 5 0 5 0 2S 363 (25) 2942 (1334)
(2451) (1057) (1592) (205) (2200) (577) (200) (800) (229) (254)
96.48 41.63 63.40 8.06 86.61 22.72 7.87 31.50 9.00 10.00
 N3 5 0 6 0 2S 363 (25) 3795 (1722)
(2451) (1057) (1610) (205) (2200) (577) (200) (800) (229) (254)
96.78 43.85 62.70 9.44 86.61 22.72 7.87 31.50 13.50 13.50
 N3 6 010 2S 232 (16) 2104 (954)
(2458) (1114) (1592) (240) (2200) (577) (200) (800) (343) (343)
96.78 43.85 62.70 9.44 86.61 22.72 7.87 31.50 13.50 13.50
 N3 6 0 212S 232 (16) 2682 (1216)
(2458) (1114) (1592) (240) (2200) (577) (200) (800) (343) (343)
96.78 43.85 62.70 9.44 86.61 22.72 7.87 31.50 13.50 13.50
 N3 6 0 3 22S 232 (16) 3123 (1416)
(2458) (1114) (1592) (240) (2200) (577) (200) (800) (343) (343)
96.78 45.85 69.73 9.44 86.61 22.72 7.87 31.50 13.50 15.00
 N3 6 0 5 0 2S 363 (25) 5094 (2311)
(2458) (1165) (1771) (240) (2200) (577) (200) (800) (343) (381)
96.78 48.87 62.70 9.44 86.61 22.72 7.87 31.50 13.50 13.50
 N37010 2S 232 (16) 3193 (1448)
(2458) (1241) (1592) (240) (2200) (577) (200) (800) (343) (343)
96.78 48.87 62.70 9.44 86.61 22.72 7.87 31.50 13.50 13.50
 N370 212S 232 (16) 3680 (1669)
(2458) (1241) (1592) (240) (2200) (577) (200) (800) (343) (343)
96.78 48.87 62.70 9.44 86.61 22.72 7.87 31.50 13.50 13.50
 N370 3 22S 232 (16) 4576 (2076)
(2458) (1241) (1592) (240) (2200) (577) (200) (800) (343) (343)
96.78 51.44 66.03 9.44 86.61 22.72 7.87 31.50 13.50 15.00
 N370 422S 363 (25) 5554 (2519)
(2458) (1307) (1677) (240) (2200) (577) (200) (800) (343) (381)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
 N3 8 010 2S 232 (16) 1014 (460)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
 N3 8 0 3 0 2S 232 (16) 1165 (529)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
 N3 8 0 4 0 2S 232 (16) 1319 (598)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
 N3 8 0 5 0 2S 232 (16) 1669 (757)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
 N3 8 070 2S 232 (16) 1836 (833)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 8.25
 N3 810 0 2S 363 (25) 2249 (1020)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (210)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
 N3 9 0 2 0 2S 232 (16) 1085 (492)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)
85.65 30.70 61.42 6.19 78.74 16.81 3.94 27.56 7.50 7.50
 N3 9 0 3 0 2S 232 (16) 1307 (593)
(2176) (780) (1560) (157) (2000) (427) (100) (700) (191) (191)

Note:
All dimensions are inches (mm), tolerances are (+/-) ½" (12 mm) unless otherwise specified.
su bmi tta l Design envelope 6800 g
n330202s - n390302s 3 duty pumps & 1 standby, Domestic water booster with standby

performance curve - vms 10b

q [l/min]
0 50 100 150 200 250 300 400
280
900
p h h
[psi] [ft] vms 1016/15 hp vms 10b - 60 hz - 3450 rpm [m]
348 800 vms 1015/15 hp 240

vms 1014/15 hp
700
290
200
vms 1012/10 hp
600
vms 1011/10 hp

232 vms 1010/10 hp 160


500
vms 1009/7.5 hp

vms 1008/7.5 hp
174 400 120
vms 1007/7.5 hp

vms 1006/5 hp
300
116 vms 1005/5 hp 80

vms 1004/5 hp
200
vms 1003/3 hp
58 40
100 vms 1002/2 hp

vms 1001/1 hp

0 0 0
0 10 20 3 40 50 60 70 80 U.S.g.p.m.

0 2 4 6 8 10 12 14 16 18 20 q [m3/h]
80
1.5
% 60 [%]
p2 1
[hp] Single Impeller hp
0.5 40

0 20
0 10 20 3 40 50 60 70 80 U.S.g.p.m.
8
20
npsh npsh
[ft] 10 4 [m]

0 0
0 10 20 3 40 50 60 70 80 U.S.g.p.m.

note: Pump curves are shown for information purpose only and should not be used for selection. Individual pump curves don’t represent the performance of a complete package
as they ignore losses and control constraints. Please refer to Curves and diagrams on Armstrong’s website for a detailed performance envelope for the specific booster model.
Design envelope 6800 g submit ta l
3 duty pumps & 1 standby, Domestic water booster with standby n330202s - n390302s

performance curve - vms 15b

q [l/min]
0 100 200 300 400 500
280
900
p h h
vms 1512b/25hp [m]
[psi] [ft] vms 15b - 60 hz - 3500 rpm
348 800
vms 1511b/25hp 240

vms 1510b/20hp
700
290
200
vms 1509b/20hp

600
vms 1508b/20hp
232 160
500 vms 1507b/15hp

vms 1506b/15hp
174 400 120
vms 1505b/10hp

300
vms 1504b/10hp
116 80

vms 1503b/7.5hp
200

vms 1502b/5hp
58 40
100
vms 1501b/2hp

0 0 0
0 20 40 60 80 100 120 U.S.g.p.m.

0 5 10 15 20 25 q [m3/h]
80
2.5
%
60 [%]
p2 2
[hp]
1.5 40
Single impeller hp
1 20
0 20 40 60 80 100 120 U.S.g.p.m.
8
20
npsh 4
npsh
[ft] 10 [m]
0 0
0 20 40 60 80 100 120 U.S.g.p.m.

note: Pump curves are shown for information purpose only and should not be used for selection. Individual pump curves don’t represent the performance of a complete package
as they ignore losses and control constraints. Please refer to Curves and diagrams on Armstrong’s website for a detailed performance envelope for the specific booster model.
su bmi tta l Design envelope 6800 g
n330202s - n390302s 3 duty pumps & 1 standby, Domestic water booster with standby

performance curve - vms 20b

q [l/min]
0 100 200 300 400 500 600
280
900
p h h
[psi] [ft] vms 20b - 60 hz - 3450 rpm [m]
348 800 vms 2010/25 hp
240

vms 2009/25 hp
700
290
vms 2008/20 hp
200

600
vms 2007/20 hp
232 160
500
vms 2006/15 hp

174 400 vms 2005/15 hp


120

vms 2004/10 hp
300
116 80
vms 2003/7.5 hp

200
vms 2002/5 hp
58 40
100 vms 2001/3 hp

0 0 0
0 20 40 60 80 100 120 140 U.S.g.p.m.

40q [m /h]
3
0 5 10 15 20 25 30
3 80

%
60 [%]
p2 2.5
[hp]
2 40
Single Impeller hp
1.5 20
0 20 40 60 80 100 120 140 U.S.g.p.m.
12
30
npsh 8 npsh
20
[ft] 4
[m]
10
0 0
0 20 40 60 80 100 120 140 U.S.g.p.m.

note: Pump curves are shown for information purpose only and should not be used for selection. Individual pump curves don’t represent the performance of a complete package
as they ignore losses and control constraints. Please refer to Curves and diagrams on Armstrong’s website for a detailed performance envelope for the specific booster model.
Design envelope 6800 g submit ta l
3 duty pumps & 1 standby, Domestic water booster with standby n330202s - n390302s

performance curve - vms 32

335 1100
H H
(m) (ft) vms 32 - 60 hz - 3500 rpm
304 1000 vms 3210-1
min. flow

274 900 vms 3209

244 800
vms 3208-3

vms 3207
213 700

vms 3206
183 600

vms 3205
152 500

122 400 20 6
vms 3204-3

vms 3203
91 300 15 4.5

nsph(m)
nsph(ft)
vms 3203-2

61 200 vms 3202-2 10 3

vms 3201
30 100 5 1.5
npsh
0 0 0 0
0 20 40 60 80 100 120 140 160 180 200
us gpm

0 5 9 14 18 23 27 32 36 41 45
q m3/h
80
70
60
50
eff.% 40
30
20
10
0
0 20 40 60 80 100 120 140 160 180 200
us gpm

note: Pump curves are shown for information purpose only and should not be used for selection. Individual pump curves don’t represent the performance of a complete package
as they ignore losses and control constraints. Please refer to Curves and diagrams on Armstrong’s website for a detailed performance envelope for the specific booster model.
su bmi tta l Design envelope 6800 g
n330202s - n390302s 3 duty pumps & 1 standby, Domestic water booster with standby

performance curve - vms 45

274 900
H H
(m) (ft)
vms 4507-2 vms 45 - 60 hz - 3500 rpm
244 800 min. flow

vms 4506

213 700

vms 4505
183 600

152 500
vms 4504-1

122 400 20 6
vms 4503

vms 4503-2

91 300 15 4.5

nsph(m)
nsph(ft)
vms 4502-1

61 200 10 3

vms 4501 npsh


30 100 5 1.5
vms 4501-1

0 0 0 0
0 50 100 150 200 250 300
us gpm

0 11 13 34 45 57 68
q m3/h
90
80
70
60
eff.% 50
40
30
20
10
0
0 50 100 150 200 250 300
us gpm

note: Pump curves are shown for information purpose only and should not be used for selection. Individual pump curves don’t represent the performance of a complete package
as they ignore losses and control constraints. Please refer to Curves and diagrams on Armstrong’s website for a detailed performance envelope for the specific booster model.
Design envelope 6800 g submit ta l
3 duty pumps & 1 standby, Domestic water booster with standby n330202s - n390302s

performance curve - vms 64

183 600
H H vms 64 - 60 hz - 3500 rpm
(m) (ft) vms 6404 min. flow

152 500 vms 6404-2

vms 6403
122 400

vms 6403-2

91 300
vms 6402

vms 6402-1

61 200 20 6

vms 6401
15 4.5

nsph(m)
nsph(ft)
vms 6401-1
30 100 10 3

5 1.5
npsh

0 0 0 0
0 50 100 150 200 250 300 350 400 450
us gpm

0 11 13 34 45 57 68 80 91 102
q m /h 3

90
80
70
60
eff.% 50
40
30
20
10

0 50 100 150 200 250 300 350 400 450


us gpm

note: Pump curves are shown for information purpose only and should not be used for selection. Individual pump curves don’t represent the performance of a complete package
as they ignore losses and control constraints. Please refer to Curves and diagrams on Armstrong’s website for a detailed performance envelope for the specific booster model.
su bmi tta l Design envelope 6800 g
n330202s - n390302s 3 duty pumps & 1 standby, Domestic water booster with standby

10

4
3 11 6
2
discharge
j1 connection
grooved
standard

c max 7
b
8
9 f
5
d
j
g suction
h 10 a connection
1 grooved
e standard

11
Models N330202S - N390302S

item description
1 Stainless steel suction header
12 2 Stainless steel discharge header
3 Pump with integrated ivs controls
4 Control panel with plc
5 Suction isolation valve
6 Grooved connection
7 Pressure gauge
8 Pressure transducer
9 Pressure gauge isolation valve
toronto
10 Stainless steel base and panel support
+1 416 755 2291
11 Plug pipe
buffalo
12 Flo-Trex valve
+1 716 693 8813

birmingham
+44 (0) 8444 145 145

manchester
+44 (0) 8444 145 145

bangalore
+91 (0) 80 4906 3555

shanghai
+86 21 3756 6696
a r m s t r o n g f lu i d t e c h n o lo g y
são paulo established 1934 a r m s t r o n g f lu i d t e c h n o lo g y. c o m
+55 11 4785 1330

You might also like